Premier Sx

download Premier Sx

of 1

Transcript of Premier Sx

  • 7/30/2019 Premier Sx

    1/1

    ELECTRICAL SPECIFICATION

    The Premier SX Control Panel range is available in 1,2,4,6 and 8zones, housed in a light grey flame retardant ULV0 enclosure,designed to meet modern architectural surroundings, with aremovable hinged door. The Premier SX has been designedwith ease of installation in mind, in addition to the robustelectronic design expected from GLT Exports Ltd.

    Complies fully to EN54 Pt 2 & Pt 4 Microprocessor based Built in detector removal line integrity (no need for active

    E.O.L.) Space for up to 2 x 7AH 12V SLA Batteries Battery charger short circuit protection Zone short circuit protection Fire change over relay output Fault change over relay output Class Change Top, Bottom & Rear Cable Entries Zone isolate facility

    One man test Facility Front Panel Short circuit indication Programmable External Sounder delay (0-9 minutes in 1 minute

    increments) Earth fault indication Front panel delay override facility Suitable for surface & semi-flush installation CE Marked Meets the latest European low voltage directive Battery overcharge thermal protection IP 43

    Mo d el NPSX1 NPSX2 NPSX4 NPSX6 NPSX8

    Part No 37-050 37-051 37-052 37-053 37-054

    Detection Zones 1 2 4 6 8

    Mains Voltage 230 VAC +10%/-15% @ 50/60Hz

    System Voltage 24 VDC (Nominal)

    Zone Voltage 21 VDC (Nominal)

    Sounder Alarm O/P 2 x 400 mA @ 24V DC (Nominal)

    Fault Relay Output 1 x Relay SELV (1 Amp maximum)

    Fire Relay Output 1 x Relay SELV (1 Amp maximum)

    Zone Capacity 32 Devices per zone

    Remote Sounder Activation Via N/O contact (class change)

    Sounder Activation Delay 0-9 minutes in 1 minute increments

    Zone End of Line IN4002 Diode (Cathode stripe to +)

    Sounder End of Line 10K Resistor

    Charger Voltage 28.4V @ 20C (with battery disconnected)

    Charger Size 1.1 Amp

    Zone Short Circuit Protection 100mA

    Charger Short Circuit Protection Battery voltage less than 20 V

    Enclosure Size 355 L x 275 H x 100 D (mm)

    Weight 3.25kg (Excluding Batteries)

    Premier SX Fire Alarm Control Panel

    LPCB

    APPROVE

    D

    to EN54

    Pt 2

    & 4:1998

    1

    12 x 19mm grommet cable entries355mm

    275mm

    Flush/Wall

    Mount73mm

    60 mm

    20mm

    SEALED LEAD ACID

    BATTERY12V / 6 Ah

    ZONE1 ZONE2 SND 1ZONE8ZONE7ZONE6ZONE5ZONE4ZONE 3 SND 2 CLASSCHANGE

    + - + - + - + - + - + - + - + - + - + -

    EARTH

    FIRERELAY

    + -BATTERY24VSLA

    N O C MN C

    FAULTRELAY

    - +

    En54 pt4SUPPLY

    (OPTIONAL)

    N O C MN C

    ACAC

    FROM

    TRANSFORMER

    SECONDARY

    CONN1

    FS2BATTERY

    1.6A

    FS4SND1

    400mA

    FS3En54 SUP

    1.6A

    FS1CHARGER

    1.6A

    FS5SND2

    400mA

    LIVENEUT-EARTH

    RAL

    MAINSTO TRANSFORMER PRIMARY

    LIVE EARTHNEUTRAL

    MAINSFUSE

    1AHRCCERAMIC

    CONN5

    CONN 27

    1 2 3 4 5 6 7 8 91011 12 13

    1415 16

    17

    18

    19

    20

    0123

    4567

    8901 2

    39

    2 x 19mm knock-out cable entries

    SEALED LEAD ACID

    BATTERY12V / 6 Ah

    ZONE 1+ -

    ZONE 2+ -ZONE 2+ -

    ZONE 3+ -

    ZONE 4+ -

    ZONE 5+ -

    ZONE 6+ -ZONE 6+ -

    ZONE 7+ -ZONE 7 ZONE 8

    + -ZONE 8+ -

    SND 1+ -

    SND 2+ -SND 2 CLASS

    CHANGE

    FIRE RELAYNO CM NC

    FAULT RELAYNO CM NC

    -+ +

    --

    + +

    --

    If manual call points will be mixed with detectors,diode bases mustbe used (to allow power to call point if a head is removed)

    If ALL manual call points are at the start of the zone, or no call points arefitted to that zone, either standard bases or common bases can be used

    1N4002EndofLineDiode

    1N4002EndofLineDiode

    Zone +

    Zone -

    Zone +

    Zone -

    Call Point

    Call Point

    +IN +OUT

    -

    +IN +OUT

    -

    +IN +OUT

    -

    +IN +OUT

    -

    +IN +OUT

    -

    +IN +OUT