PLC: SIMATIC S7-1500 più TIA Portal V12 SP 1 4 4 4 4 4 4 4 ... · PLC: SIMATIC S7-1500 più TIA...
Transcript of PLC: SIMATIC S7-1500 più TIA Portal V12 SP 1 4 4 4 4 4 4 4 ... · PLC: SIMATIC S7-1500 più TIA...
Nr. 2013/1.10/32 Data: 26.07.13
PLC: SIMATIC S7-1500 più TIA Portal V12 SP 1
Il TIA Portal V12 Service Pack 1 è rilasciato e pronto per fare un download (Le informazioni esistono ancora solo in tedesco)
Condizione:
La versione TIA Portal V12 deve essere installata e l’utente deve aggiornare tutti i software, non può aggiornare soltanto un software!
STEP 7 V12 SP1:
Informazione: http://support.automation.siemens.com/WW/view/de/76276623 Download: http://support.automation.siemens.com/WW/view/de/75277515
WinCC V12 SP1: Informazione: http://support.automation.siemens.com/WW/view/de/73947391 Download: http://support.automation.siemens.com/WW/view/de/73956248
STARTDRIVE V12 SP1: Informazione: http://support.automation.siemens.com/WW/view/de/77330014 Download: http://support.automation.siemens.com/WW/view/de/68034568
TIA Selection Tool
Offline Version: www.siemens.com/tia-selection-tool
Online Version (JAVA):
https://eb.automation.siemens.com/mall/it/it/Catalog/Configurators
Tutorial: https://www.automation.siemens.com/mcms/topics/en/simatic/tia-selection-
tool/Pages/tab.aspx?tabcardname=Tutorials#
Restricted © Siemens AG 2013 All rights reserved. siemens.com/answers
1. STEP 7 TIA PORTAL V12 SP 12. WinCC TIA Portal V12 SP 1
TIA PORTAL V12 SP 1 http://support.automation.siemens.com/WW/view/en/67639464
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 2 I IA AS Milano – Team TIA Portal V12
TIA Portal V12 SP 1Informazione generale
CompatibilitàProgetto V11 in V12 SP 1
Release of V12 SP1 / SUS delivery
Download gratuitosul Service&Support dal 24.07
Performance è migliorataStabilità ancora è okay
• STEP 7 SUS verrà consegnato prima e compresaStartdrive AND WinCC Comfort/Advanced DVD
• Clienti riceverà WinCC due volte, se hanno ancheun WinCC SUS contratto
• Dal 26 luglio nuove ordine verràconsegnato con V12 SP1I contratti SUS riceveranno fra 4
settimane I DVD con SP 1
Compatibility mode V11Compatibility mode V11 can be used in V12 SP1 (same as in V12).Projects of V11 can beopened/engineered/stored with TIA Portal V12 SP1. After engineering with V12 SP1 theproject can be used in TIA Portal V11 SP2.
Installazione del SP 1 possibilein parallele con STEP 7 Classico, TIA Portal V10.5 o V11 NON V12
Restricted © Siemens AG 2013 All rights reserved. siemens.com/answers
STEP 7 TIA PORTAL V12 SP 1 http://support.automation.siemens.com/WW/view/en/67639464
Orazio VinciSupporto Tecnico
S7-300/400/DPS7-1500SCLTIA Portal STEP 7
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 4 I IA AS Milano – Team TIA Portal V12
Compatibility of V12 SP1 - projects and devices Upgrade V12 -> V12 SP1
Compatibility at Upgrade V12 to V12 SP1• No compatible repository of V12 and V12 SP1 projects due to new features
• Projects opened in V12 SP1, can’t be edited with V12 anymore• When opening a V12 project with TIA Portal V12 SP1 the user will be advised to upgrade the project • The original V12 project is still available in parallel
• Details HMI• Panels and RT Advanced remain the configured runtime version (V11 or V12) at project upgrade (ES)• Runtime Professional will upgraded automatically to V12 SP1 at project upgrade (ES)• WinCC V12 SP1 allows editing of devices in the runtime versions V11 and V12• The configured runtime version activate the available functionality of the devices• Version changes (V11 V12) will be done by “Change device/version…”
• Details PLC• Engineered V11/V12 PLCs can be opened with STEP 7 V12 SP1• Engineered V12 SP1 PLCs (S7-300, S7-400) can be opened with STEP 7 V12• Engineered V12 SP1 PLCs (S7-1200, S7-1500) can’t be opened with STEP 7 V12
• In the live list V12 all contents (e.g. blocks) with V12 SP1 engineered PLC’s will be marked with a prohibition sign (e.g. opening of a block not possible)
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 5 I IA AS Milano – Team TIA Portal V12
V12 ESV11
project(compatible)
V12 project
V11 ES
V11project
Download of projectPLC
Engineering
S7-1200 S7-300S7-400 S7-1500 V1.0
PLC
V12 SP1 V11
project(compatible)
V12 SP1project
S7-1500 V1.1
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 6 I IA AS Milano – Team TIA Portal V12
V12 SP1 ES
Download di progetti nel runtime HMI Panel
Engineering
HMI V11 HMI V12
HMI Runtime
V11 ESV11 project
HMI V11 Version
V12 ESV11 project(compatible)
HMI V11 Version
V12 project
HMI V11 Version
HMI V12 Version
V11 project(compatible)
HMI V11 Version
V12 SP1 projectHMI V11 Version
HMI V12 Version
HMI V12 SP1 Version
HMI V12 SP1
CAMBIO FW A V11
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 7 I IA AS Milano – Team TIA Portal V12
V12 SP1 ES
Download di progetti nel runtime HMI Panel
Engineering
HMI V11 HMI V12
HMI Runtime
V11 ESV11 project
HMI V11 Version
V12 ESV11 project(compatible)
HMI V11 Version
V12 project
HMI V11 Version
HMI V12 Version
V11 project(compatible)
HMI V11 Version
V12 SP1 projectHMI V11 Version
HMI V12 Version
HMI V12 SP1 Version
HMI V12 SP1
CAMBIO FW A V11
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 8 I IA AS Milano – Team TIA Portal V12
V12 SP1 ES
Download di progetti nel runtime HMI Panel
Engineering
HMI V11 HMI V12
HMI Runtime
V11 ESV11 project
HMI V11 Version
V12 ESV11 project(compatible)
HMI V11 Version
V12 project
HMI V11 Version
HMI V12 Version
V11 project(compatible)
HMI V11 Version
V12 SP1 projectHMI V11 Version
HMI V12 Version
HMI V12 SP1 Version
HMI V12 SP1
CAMBIO FW A V12
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 9 I IA AS Milano – Team TIA Portal V12
V12 SP1 ES
Download di progetti nel runtime HMI Panel
Engineering
HMI V11 HMI V12
HMI Runtime
V11 ESV11 project
HMI V11 Version
V12 ESV11 project(compatible)
HMI V11 Version
V12 project
HMI V11 Version
HMI V12 Version
V11 project(compatible)
HMI V11 Version
V12 SP1 projectHMI V11 Version
HMI V12 Version
HMI V12 SP1 Version
HMI V12 SP1
CAMBIO FW A V12 SP1
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 10 I IA AS Milano – Team TIA Portal V12
STEP 7 Language InnovationsS7-Graph
Availability of S7-Graph with S7-1500 too+
Select GRAPH
Add FB
S7-1500 CPU
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 11 I IA AS Milano – Team TIA Portal V12
STEP 7 Language Innovations New Instruction - MB_CLIENT / MB_SERVER
Communication via MODUBS TCP
• S7-1500 can communicate in Modbus TCP with blocks inside the library ‘Communication’
• The library is free of charge (without licence) and yet available inside the library of TIA Portal V12 SP1
+
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 12 I IA AS Milano – Team TIA Portal V12
NEW in SP1: Simulation of PID Professional and FailsafeCommunication between PLCSIM-Instances with the following instructions:- PUT/GET- BSend/Brcv- Master-MasterCommunication to local WinCC Runtime
S7-PLCSIM Simulation S7-1500
Simulation of S7-1500 PLC-functionality with Look & Feel of the TIA-Portal+
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 13 I IA AS Milano – Team TIA Portal V12
System Usability Reinitialize DB
Easy optimization of parameters during commissioning:• The start value for the set points can be taken over
to the working memory as actual value directly.
Simplified and fast commissioning+
1. Define setpoint
2. Snapshot of actual values
3. Apply snapshot values for setpoints as
start values
4. Apply start values to the working memory of the PLC as
actual value
23
4
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 14 I IA AS Milano – Team TIA Portal V12
STEP 7 Language Innovations User defined data type on I/O
Structured and symbolic access on I/O
Define user defined data types for in- and outputs:
+
1. Define user defined type (UDT)
2. Reference tag with UDT to an in- or output
3. Use I/O
Reference structured in- or outputs as a user defined data type. For example to send and receive telegrams for drive.
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 15 I IA AS Milano – Team TIA Portal V12
System Usability Simplified block view
Fast overview for the whole PLC-program
• Possibility to have a detailed view of all blocks in the PLC without folder division.
+
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 16 I IA AS Milano – Team TIA Portal V12
System Usability Advanced possibilities to navigate within blocks
Simple navigation within the code
• New functionality in cross reference:
• New functionality: “Go to read/write access”
+
Restricted © Siemens AG 2013 All rights reserved. siemens.com/answers
WinCC TIA PORTAL V12 SP 1 http://support.automation.siemens.com/WW/view/en/67639464
Daniela Amigoni PM
WinCCAdvan.,PanelsTIA Portal WinCC
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 18 I IA AS Milano – Team TIA Portal V12
Mobile Panel 277(F) IWLAN in WinCC V12 SP1Highlights
Support of Mobile Panel 277F IWLAN
Support of F-FBs in global library (S7-300F and S7-400F)
Easy installation of F-FBs using CD delivered with Mobile Panel 277F IWLAN
Configuration of F-functionality requires Safety Advanced V12 (sett 2013)
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 19 I IA AS Milano – Team TIA Portal V12
SIMATIC WinCC V12 SP1Diagnosis service
System diagnosis viewer• Overview of accessible devices and status information of the plant• Switch between device and detail view• Common concept for Comfort Panels, RT Advanced, RT Professional,
CPU Display & CPU web server• View is also available for Basic Panels
Newwith SP1
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 20 I IA AS Milano – Team TIA Portal V12
SIMATIC WinCC V12 SP1Diagnosis service
STEP 7 HMI Web server CPU-DisplayHMI
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 21 I IA AS Milano – Team TIA Portal V12
SIMATIC WinCC V12 SP1Download WinCC Runtime Professional - Extension of Offline-Download
Offline Download Dialog
Selectable whether• logging• alarms• recipesshall be overwritten on the target device.
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 22 I IA AS Milano – Team TIA Portal V12
SIMATIC HMI Comfort PanelsUse of existing projects - Easy Migration into TIA Portal
TIA Portal
Scenario 1: Changeover of engineering system to TIA PortalPLC and HMI in TIA Portal
WinCC V1x
STEP7 V1x
WinCC flexible
STEP7 V5.5
1.Migration of integrated project via „Migrate project “
Convert of project in TIA Portal project.
Original panel is kept.
2.Device change „Change device/version“ at the push of a button
Change of original panel to successor
All data are kept (screens, connections,…)
1.
S7-300/400 S7-300/400
2. WinCC V1x
Scenario 2: Changeover to WinCC (TIA Portal) Mixed configuration: PLC in STEP7 5.5, HMI in WinCC (TIA Portal)
TIA PortalWinCC V1xWinCC flexible
STEP7 V5.5
1. Migration of WinCC flexible project via „Migrate project “
Convert of project in TIA Portal project.
Original panel is kept.
2. Device change „Change device/version“ at the push of a button
Change of original panel to successor
All data are kept (screens, connections,…)
1.
S7-300/400
2. WinCC V1x
Process communication
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 23 I IA AS Milano – Team TIA Portal V12
SIMATIC HMI Comfort PanelsMixed configuration - extension of the STEP 7 project after migration
When it makes sense to use the TagConverter?Mixed configuration: STEP 7 Classic and WinCC (TIA Portal) after migration of a WinCC flexible projects and extension of the STEP 7 project.
•The TagConverter can be used while engineering after migration. Using the TagConverter it is easy to synchronize tag configuration data in engineering, if the addresses were changed in STEP 7 or if the STEP 7 project was extended.
•The TagConverter is not necessary for process communication in runtime.
•The TagConverter is not necessary for migration.
Scenario 3: Synchronization after changes in STEP 7 ClassicMixed configuration: PLC in STEP7 5.5, HMI in WinCC (TIA Portal)
TIA PortalWinCC V1xWinCC flexible
STEP7 V5.5
1.
S7-300/400
2. WinCC V1x
Changed addresses
Synchronization via TagConverter
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 24 I IA AS Milano – Team TIA Portal V12
SIMATIC HMI Comfort PanelsMixed configuration - new projects
Scenario 4: Engineering of new HMI projectsMixed configuration: PLC in STEP7 5.5, new HMI in WinCC (TIA Portal)
TIA PortalSTEP 7 V5.5
S7-300/400WinCC V1x
1. Programming of PLC with STEP7 V5.5
2. Creating a new project with WinCC (TIA Portal).
No address data of PLC in HMI
3. Converting of tags/symbols of STEP7 V5.5 via TagConverter.
4. Import of the file of TagConverter in the tag table of the panel in
WinCC (TIA Portal)
Synchronization of data while engineering
When it makes sense to use the TagConverter?Mixed configuration: STEP 7 Classic and WinCC (TIA Portal) and creation of a new project
•With the TagConverter tag lists and symbols can be read from STEP 7 Classic and imported in WinCC (TIA Portal). Engineering is easy.
•The TagConverter can be used while engineering. Using the TagConverter it is easy to synchronize tag configuration data in engineering.
•The TagConverter is not necessary for process communication in runtime.
1. 2.
3. 4.
Process communicationpossible
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 25 I IA AS Milano – Team TIA Portal V12
SIMATIC HMI Comfort Panels Collaboration STEP 7 Classic and WinCC (TIA Portal)
• September 2013 improvement of usability of TagConverter
• WinCC V13 Collaboration of STEP 7 Classic and WinCC (TIA Portal)
• Data blocks and symbols
• Integration: Alarm_S and RSE
TIA PortalV11/12
S7 ClassicProject
XLSX Filesexport of DBs using
TIA PortalV11/12
TagConverter XLSX File
Export of DBs using
TagConverter Tags only
TIA PortalV13
Collaboration STEP 7 Classic and WinCC (TIA Portal)
full integration – no restrictions
Tags only
TagConverter
S7 ClassicProject
S7 ClassicProject
text printerToda
ySt
ep 1
Sept
. 201
3St
ep 2
Restricted © Siemens AG 2013 All rights reserved.2013 – LIVE MEETING – TRAINING TIA PORTAL V12 Page 26 I IA AS Milano – Team TIA Portal V12
SIMATIC HMI Comfort Panels New and improved TagConverter
Functionality
•New TagConverter can export the DBs and symbols directly from
the STEP 7 Classic Projekt.
•No need to export each DB using the text printer.
•Several DBs can be converted at the same time.
•Not all tags have to be converted, HMI relevant tags can be
selected.
•One single file has to be imported in Tia Portal which contains all
relevant tags and symbols.
Conversion of tags and symbols only. ALARM_S and ReportSystemError not possible.
09/2013