1
SCHEMA TIPICO COLLEGAMENTI FRIGORIFERI ED ELETTRICI IMPIANTO VRF UFFICI ED ARCHIVI No Component 1 1 5 6 6 6 5 6 PP PP PP 7 ARCHIVIO T03 5,00/4,91 (3,70) [kW] 4,50/4,26 (4,26) [kW] 1,7 HP Equivalente Parete ARCHIVIO T03 5,00/4,91 (3,70) [kW] 4,50/4,26 (4,26) [kW] 1,7 HP Equivalente Parete ARCHIVIO T02 0,8 HP Equivalente Parete ARCHIVIO T02 5,00/4,92 (3,70) [kW] 4,50/4,27 (4,27) [kW] 1,7 HP Equivalente ARCHIVIO T01 5,00/4,94 (3,70) [kW] 4,50/4,34 (4,32) [kW] 1,7 HP Equivalente Parete UFFICIO T01 5,00/4,97 (3,70) [kW] 4,50/4,46 (4,32) [kW] 1,7 HP Equivalente Parete UFFICIO T02 3,20/3,19 (2,37) [kW] 2,80/2,79 (2,69) [kW] 1,0 HP Equivalente Parete GUARDIA T01 4,00/3,96 (3,04) [kW] 3,60/3,51 (3,51) [kW] 1,25 HP Equivalente Parete VTEC T01 3,20/3,17 (2,43) [kW] 2,80/2,73 (2,73) [kW] 1 HP Equivalente Parete CIRC T02 2,50/2,48 (1,90) [kW] 2,20/2,17 (2,17) [kW] 0,8 HP Equivalente Parete CIRC T01 2,50/2,49 (1,90) [kW] 2,20/2,18 (2,18) [kW] 0,8 HP Equivalente Parete BAR T01 18,00/17,90 (13,69) [kW] 16,00/15,84 (15,84) [kW] 6 HP Equivalente Canalizzato standard Lb La PP 60,20/59,74 (45,76) 53,70/52,78 (52,70) 63,00/45,80[kW] 56,00/53,67[kW] PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP Parete PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP PP 1 PP PP PP PP 8 AMPLIAMENTO IMPIANTO VRF 5 N L3 L1 L2 3 fasi + Terra - 50Hz 380V-415V AC U1/U2 U5/U6 N L3 L1 L2 U5/U6 U5/U6 Canalizzato standard 6 HP Equivalente BAR T01 N L 220V-240V AC Monofase - 50Hz U1/U2 A/B A/B Parete 0,8 HP Equivalente CIRC T01 U1/U2 Parete 0,8 HP Equivalente CIRC T02 U1/U2 Parete 1 HP Equivalente VTEC T01 U1/U2 Parete 1,25 HP Equivalente GUARDIA T01 U1/U2 U1/U2 Parete 1,7 HP Equivalente UFFICIO T01 U1/U2 Parete 1,7 HP Equivalente ARCHIVIO T01 U1/U2 Parete 1,7 HP Equivalente ARCHIVIO T02 U1/U2 Parete 0,8 HP Equivalente ARCHIVIO T02 U1/U2 Parete 1,7 HP Equivalente ARCHIVIO T03 U1/U2 Parete 1,7 HP Equivalente ARCHIVIO T03 U1/U2 PP PP PP 2,20/2,14 (2,14) [kW] 2,50/2,47 (1,90) [kW] UFFICIO T02 1,0 HP Equivalente Parete TABELLA TUBAZIONI FRIGORIFERE: Diametro pollici: Diam. Esterno x Sp. (mm) 1/4" [ 3/8" [ 1/2" [ 5/8" [ 3/4" [ 7/8" [ 1" [ 1" 1/8 [ 1" 3/8 [ 1" 5/8 [ 2" [ IMPIANTO ESISTENTE IMPIANTO ESISTENTE 1 - Rispettare sempre le lunghezze caratteristiche del sistema: R GLVWDQ]D PDVVLPD WUD OXQLWj HVWHUQD H OXQLWj LQWHUQD SL ORQWDQD PDVVLPH FRQVHQWLWH GDO VLVWHPD o sviluppo totale di tubazione (contando solo la tubazione del liquido o del gas) massime consentite dal sistema. R GLVWDQ]D PDVVLPD WUD SULPD GHULYD]LRQH JLXQWR R FROOHWWRUH H XQLWj LQWHUQD SL GLVWDQWH PDVVLPH FRQVHQWLWH GDO VLVWHPD 5LVSHWWDUH LO GLVOLYHOOR PDVVLPR WUD XQLWj HVWHUQD H XQLWj LQWHUQH PDVVLPH FRQVHQWLWH GDO VLVWHPD 3 - I collettori di collegamento devono essere installati in modo orizzontale ed in posti ispezionabili. , JLXQWL YDQQR SRVL]LRQDWL LQ PRGR YHUWLFDOH R RUL]]RQWDOH FRQ XQ DQJROR PDVVLPR GL HG LQ SRVWL LVSH]LRQDELOL , JLXQWL GL FROOHJDPHQWR WUD L PRGXOL YDQQR LQVWDOODWL LQ PRGR RUL]]RQWDOH FRQ XQ DQJROR PDVVLPR GL Ë QHFHVVDULR ODVFLDUH XQ WUDWWR rettilineo di tubazione di almeno 0,5 m all'ingressi del giunto. 6 - Utilizzare esclusivamente dei tubi di rame isolati termicamente, con i diametri previsti dal progetto e del tipo adatto per impianti frigoriferi GLDPHWUL GLYHUVL YDULDQR OD YHORFLWj GHO JDV H OD FDSDFLWj GL UHFXSHUR GHOOROLR /H WXED]LRQL YDQQR LVRODWH VHSDUDWDPHQWH 7 - Le saldature vanno eseguite a "forte" con rame fosforoso (lega UNIO), in atmosfera d'azoto, operazione che consiste nel saturare le WXED]LRQL FRQ D]RWR DQLGUR FKH VRVWLWXHQGRVL DOODULD QRQ FUHD RVVLGR DOOLQWHUQR GHOOH VWHVVH /D]RWR VL SXz LPPHWWHUH QHOOH WXED]LRQL direttamente dagli attacchi di carica posti sulle valvole di mandata e ritorno delle motocondensanti, oppure si possono saldare delle prese di pressione su giunti e collettori. Per l'immissione dell'azoto occorre usare un riduttore di pressione collegato alla bombola, aperto leggermente, IDUj SDVVDUH XQD TXDQWLWj PLQLPD LQ PRGR GD VDWXUDUH OD WXED]LRQH VHQ]D SHUz LPSHGLUQH OD VDOGDWXUD 8 - Non lasciare tratti di tubazioni ciechi nell'attesa di collegare altri apparecchi interni (queste tubazioni si riempiranno di refrigerante e di olio, che vengono sottratti al circuito). 9 - Lasciare le connessioni (saldature) scoperte in modo da poterle controllare successivamente. 10 - Controllare minuziosamente i punti di collegamento, saldature e flange (la perdita di refrigerante scarica l'impianto facendogli perdere progressivamente d'efficienza). 1 - Eseguire le flange di collegamento alle sezioni interne non dimenticandosi di lubrificare l'utensile, la flangia e il filetto del bocchettone; con ROLR GHOOR VWHVVR WLSR XWLOL]]DWR GDO FRPSUHVVRUH XQD FRQQHVVLRQH ROHDWD ULGXFH GHO OD SRVVLELOLWj GL SHUGLWD GL UHIULJHUDQWH FDXVD SULQFLSDOH GL URWWXUD Gu XQ FRQGL]LRQDWRUH 6WULQJHUH L ERFFKHWWRQL FRQ FXUD HYLWDQGR GL WRUFHUH OH WXED]LRQL 11 - Una volta eseguito e chiuso il circuito, pressarlo SENZA APRIRE LE VALVOLE sino a 40 bar (R410a). L'operazione va eseguita in tre passi: o Pressare sino a 3 bar e lasciare in pressione per almeno tre minuti o Se la pressione non scende, pressare per almeno 3 min. sino a 15 bar o Se la pressione non scende, pressare sino a 40 bar per R410a per almeno 24 ore. 12 - Una volta certi della tenuta del circuito, eseguire l'operazione di vuoto con una pompa a due stadi, "rompendolo" con azoto almeno due YROWH LQ PRGR FKH HVVR WUDVFLQL FRQ VH HYHQWXDOL SDUWLFHOOH GL XPLGLWj R LPSXULWj 8QD YROWD VFDULFDWR OD]RWR VL ULSUHQGH ORSHUD]LRQH GL YXRWR FKH QRQ KD XQ WHPSR ILVVR VH OD SRPSD q LQ EXRQH FRQGL]LRQL VL SXz IDU JLUDUH SHU ROWUH RUH PDJJLRUH H LO SHULRGR GL PHVVD LQ YXRWR minore e' il rischio di danneggiamento del circuito frigorifero in futuro. 13 - Misurare sempre le lunghezze delle tubazioni del liquido, nei vari diametri previsti dal progetto, calcolare le cariche addizionali necessarie H DQQRWDUOH VXOOH PDFFKLQH HVWHUQH 'RSR DYHU HVHJXLWR OD FDULFD DGGL]LRQDOH q SRVVLELOH DSULUH OH YDOYROH GHOOD VH]LRQH HVWHUQD H PHWWHUH LQ PRWR LO VLVWHPD VH q VWDWD GDWD WHQVLRQH DOOD VH]LRQH HVWHUQD DOPHQR VHL RUH SULPD Max. corr. ass. 27,1 A + 27,1 A Max. corr. ass. 8,2 A RACCOMANDAZIONI PER L'INSTALLAZIONE LINEE ELETTRICHE Nell'installazione si raccomanda di rispettare rigorosamente le indicazioni fornite dal costruttore, a titolo esemplificativo di seguito indicate: Le linee di potenza delle motocondensanti devono essere trifasi dotate di neutro (R - S - T - N) per la tensione di 400V, Le linee di potenza delle sezioni interne devono essere monofasi per la tensione di 230V. Le linee di potenza sia delle motocondensanti sia delle sezioni interne devono essere complete di interruttore magnetotermico GLIIHUHQ]LDOH H GL HYHQWXDOL LQWHUUXWWRUL GL VLFXUH]]D 1HL SUHVVL GHOOD PRUVHWWLHUD GL DOLPHQWD]LRQH GHOOD VH]LRQH HVWHUQD GRYUj HVVHUH LQVWDOODWR un sezionatore di sicurezza come da normativa vigente. Le linee di potenza devono essere dimensionate secondo le potenze elettriche impegnate. Le motocondensanti e le sezioni interne devono essere collegate a reti di terra eseguite secondo le disposizioni vigenti. Le linee di segnale contraddistinte dai morsetti A - B - C (selezione caldo/freddo); F1 - F2 (controllo e comando); P1 - P2 (comandi); T1 - T2 (on/off forzato) devono: essere posate nella propria guaina o tubo in PVC separato e indipendente da altri; tali linee devono inoltre distare almeno 30 cm. da ogni linea di potenza sia 230V sia 400V di computer, radio, TV, telefoniche o altro. $YHUH SUHIHULELOPHQWH FRORUL GHL FRQGXWWRUL GLYHUVL OXQR GDJOL DOWUL SHU IDFLOLWj GL LGHQWLILFD]LRQH Per le linee di segnale utilizzare cavi con guaina non schermati. La sezione del cavo deve essere compresa tra 0,75 e 1,25 mm2. Usare solo cavi con guaina con l'esatto numero di conduttori richiesto. (Bipolari quando sono indicati due fili e tripolari quando sono LQGLFDWL WUH ILOL 0$, WULSRODUL DO SRVWR GHL ELSRODUL FRQ XQ FRQGXWWRUH QRQ FROOHJDWR TXHVWR SXz SURYRFDUH GLVWRUVLRQL QHO VHJQDOH 3ULPD GL GDUH WHQVLRQH DOOLPSLDQWR DFFHUWDUVL FKH L FDYL GL DOLPHQWD]LRQH VLDQR FROOHJDWL FRUUHWWDPHQWH GRSR q WURSSR WDUGL 5LFRUGDUH FKH DQFKH VH VROR XQD GHOOH VH]LRQL LQWHUQH QRQ q DOLPHQWDWD HOHWWULFDPHQWH WXWWR LO VLVWHPD QRQ IXQ]LRQD QRQ LQVWDOODUH eventuali sezionatori nei locali inaccessibili). !! N. B. !! TRATTASI DELLA REALIZZAZIONE DI UN AMPLIAMENTO DI IMPIANTO VRF IN EDIFICIO ESISTENTE, PER CUI TUTTE LE 81,7 ,17(51( (' (67(51( , &20321(17, (/(77,&, (' ,'5$8/,&, */, $&&(6625, 9$5, /( 5(*2/$=,21, ( SUPERVISIONI CHE SI ANDRANNO AD INSTALLARE, DOVRANNO ESSERE PERFETTAMENTE FUNZIONANTI, COMPATIBILI ED INTEGRABILI CON L'IMPIANTO ESISTENTE. SISTEMI "VRV / VRF" - PRECAUZIONI DA TENERE PER UNA CORRETTA INSTALLAZIONE [SALVO DIVERSE INDICAZIONI DELLA CASA COSTRUTTRICE] IMPIANTO ESISTENTE AMPLIAMENTO IMPIANTO VRF ELABORATO N. b g h c e d f REV. a DATA FILE OGGETTO PROGETTO ESECUTIVO DIS. APPR. PROGETTAZIONE Tel. +39 041.5785711 Fax +39 041.4355933 [email protected] 30035 Mirano Venezia - Italia www.fm-ingegneria.com PROGETTO EMISSIONE TITOLO STAZIONE APPALTANTE REGIONE AUTONOMA FRIULI VENEZIA GIULIA 'LUH]LRQH FHQWUDOH LQIUDVWUXWWXUH PRELOLWj SLDQLILFD]LRQH territoriale, lavori pubblici, edilizia Servizio lavori pubblici Via Giulia, 75/1 - 34126 TRIESTE IMPIANTO MECCANICO - PIANO TERRA SCHEMA AMPLIAMENTO IMP. VRF ESISTENTE Me101 AGOSTO 2015 -- 1071_Me101.a.dwg 1071/14 AG AG DZ TT 8QLWj PRWRFRQGHQVDQWL HVLVWHQWL GD +3 Giunto di derivazione < 26 HP Giunto di derivazione da 14.2 a 25.2 HP Giunto di derivazione da 6.4 a 14.2 HP Giunto di derivazione da 6.4 a 14.2 HP Giunto di derivazione da 6.4 a 14.2 HP Giunto di derivazione < 6.4 HP Selettrice di flusso < 4 HP Giunto di derivazione <6.4 HP Giunto di derivazione <6.4 HP 5 1 5 6 7 LEGENDA LEGENDA TUBAZIONI: IMPIANTO A 3 TUBI - DIAMETRO TUBAZIONE ASPIRAZIONE LATO GAS - DIAMETRO TUBAZIONE SCARICO LATO GAS - DIAMETRO TUBAZIONE LIQUIDO 8 LEGENDA UNITA' INTERNE: - Nome unita' interne - Tipologia - Modello &DSDFLWj - 5DIIUHGGDPHQWR QRPLQDOH &DSDFLWj FRUUHWWD &DSDFLWj UHVD - 5LVFDOGDPHQWR QRPLQDOH &DSDFLWj FRUUHWWD &DSDFLWj UHVD D & LEGENDA UNITA' ESTERNE: 0RGHOOR XQLWj HVWHUQD - 5DIIUHGGDPHQWR QRPLQDOH &DSDFLWj FRUUHWWD &DSDFLWj UHVD - 5LVFDOGDPHQWR QRPLQDOH &DSDFLWj FRUUHWWD &DSDFLWj D UHVD & Collegamenti Sistema di controllo BUS Collegamenti elettrici Tubazioni gas refrigerante isolate 8QLWj PRWRFRQGHQVDQWH HVLVWHQWH 8QLWj HYDSRUDQWH FDQDOL]]DELOH HVLVWHQWH 8QLWj D SDUHWH HVLVWHQWH 8QLWj HYDSRUDQWH D SDUHWH SUHVHQWH D SLq GRSHUD VROD LQVWDOOD]LRQH 8QLWj HYDSRUDQWH D SDUHWH di nuova fornitura ed installazione Selettrice di flusso di nuova fornitura ed installazione Selettrice di flusso esistente Giunto di derivazione a 2 tubi < 6.4 HP Giunto di derivazione a 3 tubi < 6.4 HP 8QLWj PRWRFRQGHQVDQWL HVLVWHQWL GD +3 Selettrice di flusso < 4 HP Selettrice di flusso < 4 HP Selettrice di flusso < 4 HP Selettrice di flusso < 4 HP Selettrice di flusso < 4 HP Selettrice di flusso < 4 HP Selettrice di flusso < 4 HP Selettrice di flusso < 4 HP Selettrice di flusso < 4 HP 09/2015 1071_Me101.a Note verificatore A.S. T.T.

Transcript of RIPARTITORE DI FLUSSO SENZA BOTOLA …...12 - Una volta certi della tenuta del circuito, eseguire...

RIPARTITORE DI FLUSSO SENZA BOTOLA D'ISPEZIONE

GIUNTO DI DERIVAZIONE A Y DINUOVA FORNITURA E INSTALLAZIONE

UNITA' ESTERNA MOTOCONDENSANTE DA 10 HPDI NUOVA FORNITURA E INSTALLAZIONE

GIUNTO DI DERIVAZIONE A Y ESISTENTE(inizio ampliamento impianto VRF)

+ 0,00 m

+ 0,64 m

+ 0,64 m

+ 0,64 m

+ 0,64 m

+ 0,64 m

+ 0,64 m

+ 0,00 m+ 0,02 m

- 0,04 m- 0,04 m

+ 0,02 m

+ 0,00 m

+ 0,64 m

+ 0,14 m

+ 0,00 m + 0,07 m

+ 0,08 m + 0,08 m

+ 0,14 m

+ 0,00 m

+ 0,00 m

+ 0,00 m

+ 0,00 m

+ 0,435 m

+ 0,285 m

+ 0,135 m

+ 0,585 m+ 0,00 m + 0,00 m

+ 0,585 m

KEY MAP - PIANO TERRA

SCHEMA TIPICO COLLEGAMENTI FRIGORIFERI ED ELETTRICI IMPIANTO VRF UFFICI ED ARCHIVI

No Component

1

15666

5

6

Ø 19,1mmØ 22,2mmØ 28,6mm 7

ARCHIVIO T03

5,00/4,91 (3,70) [kW]4,50/4,26 (4,26) [kW]1,7 HP EquivalenteParete

ARCHIVIO T03

5,00/4,91 (3,70) [kW]4,50/4,26 (4,26) [kW]1,7 HP EquivalenteParete

ARCHIVIO T02

0,8 HP EquivalenteParete

ARCHIVIO T02

5,00/4,92 (3,70) [kW]4,50/4,27 (4,27) [kW]1,7 HP Equivalente

ARCHIVIO T01

5,00/4,94 (3,70) [kW]4,50/4,34 (4,32) [kW]1,7 HP EquivalenteParete

UFFICIO T01

5,00/4,97 (3,70) [kW]4,50/4,46 (4,32) [kW]1,7 HP EquivalenteParete

UFFICIO T02

3,20/3,19 (2,37) [kW]2,80/2,79 (2,69) [kW]1,0 HP EquivalenteParete

GUARDIA T01

4,00/3,96 (3,04) [kW]3,60/3,51 (3,51) [kW]1,25 HP EquivalenteParete

VTEC T01

3,20/3,17 (2,43) [kW]2,80/2,73 (2,73) [kW]1 HP EquivalenteParete

CIRC T02

2,50/2,48 (1,90) [kW]2,20/2,17 (2,17) [kW]0,8 HP EquivalenteParete

CIRC T01

2,50/2,49 (1,90) [kW]2,20/2,18 (2,18) [kW]0,8 HP EquivalenteParete

BAR T01

18,00/17,90 (13,69) [kW]16,00/15,84 (15,84) [kW]6 HP EquivalenteCanalizzato standard

LbLaØ 9,5mm

60,20/59,74 (45,76)53,70/52,78 (52,70)

63,00/45,80[kW]56,00/53,67[kW]

Ø 12,7mmØ 19,1mmØ 22,2mm

Ø 19,1mmØ 22,2mm

Ø 12,7mm

Ø 12,7mmØ 19,1mmØ 22,2mm

Ø 12,7mmØ 19,1mmØ 22,2mm

Ø 12,7mmØ 19,1mmØ 22,2mm

Ø 12,7mmØ 19,1mmØ 22,2mm

Ø 9,50mmØ 12,7mmØ 15,9mm

Ø 12,7mmØ 15,9mm

Ø 15,9mmØ 9,50mm Ø 9,50mmØ 9,50mmØ 6,35mm

Ø 12,70mmØ 6,35mm

Ø 12,7mmØ 15,9mm

Ø 9,50mm

Ø 15,9mmØ 9,50mm

Ø 12,70mmØ 6,35mm

Ø 12,70mmØ 6,35mm

Parete

Ø 9,50mmØ 12,7mmØ 15,9mm

Ø 12,70mmØ 6,35mmØ 9,50mm

Ø 12,7mmØ 15,9mm

Ø 12,70mmØ 6,35mmØ 9,50mm

Ø 12,7mmØ 15,9mm

Ø 9,50mmØ 6,35mm

Ø 9,50mmØ 12,7mmØ 15,9mm

Ø 15,9mmØ 9,5mm

Ø 9,50mmØ 12,7mmØ 15,9mm

Ø 9,50mmØ 12,7mmØ 15,9mm

Ø 9,50mmØ 6,35mm

Ø 9,50mmØ 6,35mm

Ø 15,9mmØ 9,50mm

1

Ø 9,50mmØ 6,35mm

Ø 9,50mmØ 6,35mm

8

AMPLIAMENTO IMPIANTO VRF

5

N

L3

L1

L2

3 fasi + Terra - 50Hz

380V-415V AC

U1/U2

U5/U6

N

L3

L1

L2

U5/U6

U5/U6

Canalizzato standard6 HP Equivalente

BAR T01

N

L

220V-240V AC

Monofase - 50Hz

U1/U2

A/B

A/B

Parete0,8 HP Equivalente

CIRC T01

U1/U2

Parete0,8 HP Equivalente

CIRC T02

U1/U2

Parete1 HP Equivalente

VTEC T01

U1/U2

Parete1,25 HP Equivalente

GUARDIA T01

U1/U2

U1/U2

Parete1,7 HP Equivalente

UFFICIO T01

U1/U2

Parete1,7 HP Equivalente

ARCHIVIO T01

U1/U2

Parete1,7 HP Equivalente

ARCHIVIO T02

U1/U2

Parete0,8 HP Equivalente

ARCHIVIO T02

U1/U2

Parete1,7 HP Equivalente

ARCHIVIO T03

U1/U2

Parete1,7 HP Equivalente

ARCHIVIO T03

U1/U2

Ø 19,1mmØ 22,2mmØ 28,6mm

2,20/2,14 (2,14) [kW]2,50/2,47 (1,90) [kW]

UFFICIO T02

1,0 HP EquivalenteParete

TABELLA TUBAZIONI FRIGORIFERE:

Diametro pollici: Diam. Esterno x Sp. (mm)

1/4" Ø 6,35 x 1

3/8" Ø 9,52 x 1

1/2" Ø 12,70 x 1

5/8" Ø 15,87 x 1

3/4" Ø 19,05 x 1

7/8" Ø 22,22 x 1

1" Ø 25,40 x 1

1" 1/8 Ø 28,57 x 1,2

1" 3/8 Ø 34,92 x 1,2

1" 5/8 Ø 41,27 x 1,2

2" Ø 53.97 x 1,6

IMPIANTO ESISTENTE

IMPIANTO ESISTENTE

1 - Rispettare sempre le lunghezze caratteristiche del sistema: o distanza massima tra l'unità esterna e l'unità interna più lontana massime consentite dal sistema. o sviluppo totale di tubazione (contando solo la tubazione del liquido o del gas) massime consentite dal sistema. o distanza massima tra prima derivazione (giunto o collettore) e unità interna più distante massime consentite dal sistema.2 - Rispettare il dislivello massimo tra unità esterna e unità interne massime consentite dal sistema.3 - I collettori di collegamento devono essere installati in modo orizzontale ed in posti ispezionabili.4 - I giunti vanno posizionati in modo verticale o orizzontale (con un angolo massimo di 30°) ed in posti ispezionabili.5 - I giunti di collegamento tra i moduli vanno installati in modo orizzontale (con un angolo massimo di 15°). È necessario lasciare un trattorettilineo di tubazione di almeno 0,5 m all'ingressi del giunto.6 - Utilizzare esclusivamente dei tubi di rame isolati termicamente, con i diametri previsti dal progetto e del tipo adatto per impianti frigoriferi(diametri diversi variano la velocità del gas e la capacità di recupero dell'olio). Le tubazioni vanno isolate separatamente.7 - Le saldature vanno eseguite a "forte" con rame fosforoso (lega UNIO), in atmosfera d'azoto, operazione che consiste nel saturare letubazioni con azoto anidro che, sostituendosi all'aria, non crea ossido all'interno delle stesse. L'azoto si può immettere nelle tubazionidirettamente dagli attacchi di carica posti sulle valvole di mandata e ritorno delle motocondensanti, oppure si possono saldare delle prese dipressione su giunti e collettori. Per l'immissione dell'azoto occorre usare un riduttore di pressione collegato alla bombola, aperto leggermente,farà passare una quantità minima in modo da saturare la tubazione, senza però impedirne la saldatura.8 - Non lasciare tratti di tubazioni ciechi nell'attesa di collegare altri apparecchi interni (queste tubazioni si riempiranno di refrigerante e di olio,che vengono sottratti al circuito).9 - Lasciare le connessioni (saldature) scoperte in modo da poterle controllare successivamente.10 - Controllare minuziosamente i punti di collegamento, saldature e flange (la perdita di refrigerante scarica l'impianto facendogli perdereprogressivamente d'efficienza).1 - Eseguire le flange di collegamento alle sezioni interne non dimenticandosi di lubrificare l'utensile, la flangia e il filetto del bocchettone; conolio dello stesso tipo utilizzato dal compressore (una connessione oleata riduce del 70% la possibilità di perdita di refrigerante, causa principaledi rottura dì un condizionatore). Stringere i bocchettoni con cura, evitando di torcere le tubazioni.11 - Una volta eseguito e chiuso il circuito, pressarlo SENZA APRIRE LE VALVOLE sino a 40 bar (R410a). L'operazione va eseguita in tre passi: o Pressare sino a 3 bar e lasciare in pressione per almeno tre minuti o Se la pressione non scende, pressare per almeno 3 min. sino a 15 bar o Se la pressione non scende, pressare sino a 40 bar per R410a per almeno 24 ore.12 - Una volta certi della tenuta del circuito, eseguire l'operazione di vuoto con una pompa a due stadi, "rompendolo" con azoto almeno duevolte in modo che esso trascini con se eventuali particelle di umidità o impurità. Una volta scaricato l'azoto, si riprende l'operazione di vuoto,che non ha un tempo fisso (se la pompa è in buone condizioni si può far girare per oltre 48 ore); maggiore e' il periodo di messa in vuoto,minore e' il rischio di danneggiamento del circuito frigorifero in futuro.13 - Misurare sempre le lunghezze delle tubazioni del liquido, nei vari diametri previsti dal progetto, calcolare le cariche addizionali necessariee annotarle sulle macchine esterne. Dopo aver eseguito la carica addizionale è possibile aprire le valvole della sezione esterna e mettere inmoto il sistema (se è stata data tensione alla sezione esterna almeno sei ore prima).

Max. corr. ass. 27,1 A + 27,1 A

Max. corr. ass. 8,2 A

RACCOMANDAZIONI PER L'INSTALLAZIONE LINEE ELETTRICHENell'installazione si raccomanda di rispettare rigorosamente le indicazioni fornite dal costruttore, a titolo esemplificativo di seguito indicate:Le linee di potenza delle motocondensanti devono essere trifasi dotate di neutro (R - S - T - N) per la tensione di 400V,Le linee di potenza delle sezioni interne devono essere monofasi per la tensione di 230V.Le linee di potenza sia delle motocondensanti sia delle sezioni interne devono essere complete di interruttore magnetotermicodifferenziale e di eventuali interruttori di sicurezza. Nei pressi della morsettiera di alimentazione della sezione esterna, dovrà essere installatoun sezionatore di sicurezza come da normativa vigente.Le linee di potenza devono essere dimensionate secondo le potenze elettriche impegnate.Le motocondensanti e le sezioni interne devono essere collegate a reti di terra eseguite secondo le disposizioni vigenti.Le linee di segnale contraddistinte dai morsetti A - B - C (selezione caldo/freddo); F1 - F2 (controllo e comando); P1 - P2 (comandi); T1 - T2(on/off forzato) devono: essere posate nella propria guaina o tubo in PVC separato e indipendente da altri; tali linee devono inoltre distarealmeno 30 cm. da ogni linea di potenza sia 230V sia 400V di computer, radio, TV, telefoniche o altro.Avere preferibilmente colori dei conduttori diversi l'uno dagli altri per facilità di identificazione.Per le linee di segnale utilizzare cavi con guaina non schermati. La sezione del cavo deve essere compresa tra 0,75 e 1,25 mm2.Usare solo cavi con guaina con l'esatto numero di conduttori richiesto. (Bipolari quando sono indicati due fili e tripolari quando sonoindicati tre fili (MAI tripolari al posto dei bipolari con un conduttore non collegato, questo può provocare distorsioni nel segnale)Prima di dare tensione all'impianto accertarsi che i cavi di alimentazione siano collegati correttamente (dopo è troppo tardi).Ricordare che anche se solo una delle sezioni interne non è alimentata elettricamente, tutto il sistema non funziona (non installareeventuali sezionatori nei locali inaccessibili).

!! N. B. !!TRATTASI DELLA REALIZZAZIONE DI UN AMPLIAMENTO DI IMPIANTO VRF IN EDIFICIO ESISTENTE, PER CUI TUTTE LEUNITÀ INTERNE ED ESTERNE, I COMPONENTI ELETTICI ED IDRAULICI, GLI ACCESSORI VARI, LE REGOLAZIONI ESUPERVISIONI CHE SI ANDRANNO AD INSTALLARE, DOVRANNO ESSERE PERFETTAMENTE FUNZIONANTI,COMPATIBILI ED INTEGRABILI CON L'IMPIANTO ESISTENTE.

SISTEMI "VRV / VRF" - PRECAUZIONI DA TENERE PER UNA CORRETTA INSTALLAZIONE [SALVO DIVERSE INDICAZIONI DELLA CASA COSTRUTTRICE]

IMPIANTO ESISTENTE

AMPLIAMENTO IMPIANTO VRF

ELABORATO N.

b

g

h

c

e

d

f

REV.

a

DATA FILE OGGETTO

PROGETTO ESECUTIVO

DIS. APPR.

PROGETTAZIONE

Tel. +39 041.5785711

Fax +39 041.4355933

[email protected]

30035 Mirano

Venezia - Italia

www.fm-ingegneria.com

PROGETTO

EMISSIONE

TITOLO

STAZIONE APPALTANTE

REGIONE AUTONOMA FRIULI VENEZIA GIULIA

Direzione centrale infrastrutture, mobilità, pianificazione

territoriale, lavori pubblici, edilizia

Servizio lavori pubblici

Via Giulia, 75/1 - 34126 TRIESTE

IMPIANTO MECCANICO - PIANO TERRA

RISCALDAMENTO E RAFFRESCAMENTO

Me100

AGOSTO 2015 1:50 1071_Me100.a.dwg 1071/14

AG AG DZ TT

ELABORATO N.

b

g

h

c

e

d

f

REV.

a

DATA FILE OGGETTO

PROGETTO ESECUTIVO

DIS. APPR.

PROGETTAZIONE

Tel. +39 041.5785711

Fax +39 041.4355933

[email protected]

30035 Mirano

Venezia - Italia

www.fm-ingegneria.com

PROGETTO

EMISSIONE

TITOLO

STAZIONE APPALTANTE

REGIONE AUTONOMA FRIULI VENEZIA GIULIA

Direzione centrale infrastrutture, mobilità, pianificazione

territoriale, lavori pubblici, edilizia

Servizio lavori pubblici

Via Giulia, 75/1 - 34126 TRIESTE

IMPIANTO MECCANICO - PIANO TERRA

SCHEMA AMPLIAMENTO IMP. VRF ESISTENTE

Me101

AGOSTO 2015 -- 1071_Me101.a.dwg 1071/14

AG AG DZ TT

Unità motocondensanti esistenti da 10 HP

Giunto di derivazione< 26 HP

Giunto di derivazioneda 14.2 a 25.2 HP

Giunto diderivazione

da 6.4 a14.2 HP

Giunto diderivazione

da 6.4 a14.2 HP

Giunto diderivazione

da 6.4 a14.2 HP

Giunto diderivazione

< 6.4 HP

Selettricedi flusso< 4 HP

Giunto diderivazione

<6.4 HP

Giunto diderivazione

<6.4 HP

5

1

5

6

7

LEGENDA

LEGENDA TUBAZIONI: IMPIANTO A 3 TUBI

- DIAMETRO TUBAZIONE ASPIRAZIONE LATO GAS- DIAMETRO TUBAZIONE SCARICO LATO GAS- DIAMETRO TUBAZIONE LIQUIDO

8

LEGENDA UNITA' INTERNE:

- Nome unita' interne- Tipologia- Modello- Capacità- Raffreddamento nominale / Capacità corretta (Capacità resa)- Riscaldamento nominale / Capacità corretta (Capacità resa a -5°C)

LEGENDA UNITA' ESTERNE:

- Modello unità esterna- Raffreddamento nominale / Capacità corretta (Capacità resa)- Riscaldamento nominale / Capacità corretta (Capacità a resa -5°C)

Collegamenti Sistema di controllo BUS

Collegamenti elettrici

Tubazioni gas refrigerante isolate

Unità motocondensante esistente

Unità evaporante canalizzabile esistente

Unità a parete esistente

Unità evaporante a parete, presentea piè d'opera, sola installazione

Unità evaporante a paretedi nuova fornitura ed installazione

Selettrice di flussodi nuova fornitura ed installazione

Selettrice di flusso esistente

Giunto di derivazione a 2 tubi < 6.4 HP

Giunto di derivazione a 3 tubi < 6.4 HP

Unità motocondensanti esistenti da 10 HP

Selettricedi flusso< 4 HP

Selettricedi flusso< 4 HP

Selettricedi flusso< 4 HP

Selettricedi flusso< 4 HP

Selettricedi flusso< 4 HP

Selettricedi flusso< 4 HP

Selettricedi flusso< 4 HP

Selettricedi flusso< 4 HP

Selettricedi flusso< 4 HP

Quota di installazione fondo canala PVCQ.f.c.

09/2015 1071_Me100.a Note verificatore A.S. T.T. 09/2015 1071_Me101.a Note verificatore A.S. T.T.