Post on 14-Oct-2015
description
AgipFoglio / di Compilato Data
/
Rev.
1
NORMALIZZAZIONE INTERNA
CODICE - Code
Sheet - of Compiled Date
0INTERNAL NORMALIZATION
F.V. Giugno '96
1
06047.MAT.ELE.STDTUBO
ConduitTUBO FLESSIBILEFlexible coupling 06051.MAT.ELE.STD
TERMINALEBushing
TFFA
Q.t
Q.ty
DIM.
Size
SIGLA Tag
CEI-UNELCOMMER.
Trade
CODICE
Code
DOCUMENTO DINORMALIZZAZIONE
INTERNA
InternalNormalizationRef. Document
DESCRIZIONE
Description
PO
S.
1
2
3
5
SC./AD
EYS
1
06767.ICO.ELE.STD
TIPICO DI COLLEGAMENTO CON FLESSIBILE CORTO A MOTORE EEx-d
Typical connection of EEx-d motor with short coupling
06051.MAT.ELE.STDRACCORDO DI BLOCCAGGIO
Sealing fitting
2
VERTICALE (V1) E ORIZZONTALE (B3 o B5) SU BASAMENTOCON ARRIVO DEL TUBO DAL BASSOESECUZIONE A PROVA DI ESPLOSIONE (CLASSE 1 ZONA 1)
vertical (V1) or horizontal (B3 or B5) base mountedwith conduit incoming from belowexplosion proof execution (class 1 zone 1)
SIMBOLO - Symbol
EAM-BLK-054GS
EAM-BLK-050B..
EAM-BLK-054...
se necessariaif necessary
1
1
NOTE
Notes
La sigla del Costruttore ha valore puramente indicativoPer la messa a terra vedi 06773.ICO.ELE.STD
The trade tag is indicative onlyFor grounding see 06773.ICO.ELE.STD
6
06052.MAT.ELE.STD 14RIDUZIONE
Reducer REBEAM-BLK-055..
CAVO DI POTENZAPower cable
EAM-BLK-055L DB 106052.MAT.ELE.STD
2 m
Documento di proprieta' aziendale. La Societa' tutelera' i propri diritti a termini di legge. This document is Company property. The Company lawfully reserves all rights.
5 6
PIANO PAVIMENTO
EEx-d motorMOTORE EEx-d
PIANO PAVIMENTOgrade floor
1
grade floor
3
MOTORE EEx-d
EEx-d motor4
2
L
> 600 mm
grade floorPIANO PAVIMENTO
1
L
3
2
MOTORE EEx-d
EEx-d motor
1
3
LUNGHEZZA FLESSIBILE
L = 450 mm - conduit = 1"
4
length of flexible coupling
4
2
L
trenchSCAVO