1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 1/72 GUIDA RAPIDA DI UTILIZZO Ichill 260 L/D DUO Ichill 261 L/D DUO (versione FW 1.9)

Transcript of (versione FW 1.9) - Emerson...

Page 1: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 1/72

GUIDA RAPIDA DI UTILIZZO Ichill 260 L/D DUO

Ichill 261 L/D DUO (versione FW 1.9)

Page 2: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 2/72

Indice

1. Av v ertenze Generali _______________ 2 2. Generalità _________________________ 3 3. Caratteristiche Serie IC200 L/D _____ 4 4. Interfaccia Utente __________________ 5 5. Terminale Remoto__________________ 7 6. Prima Installazione ________________ 7 7. Visualizzazione Delle

Grandezze Controllate______________ 8 8. Programmazione con la Hot key

64 _________________________________ 8 9. Programmazione Da Tastiera _______ 9 10. Il Menu Funzioni “Tasto M” ________ 12 11. Altre Visualizzazioni A Display_____ 14 12. Installazione E Montaggio _________ 14 13. Collegamenti Elettrici _____________ 16 14. Tabella Allarmi____________________ 17 15. Schema Di Collegamento__________ 19 16. Parametri Forma Tabellare ________ 28 17. Dati Tecnici _______________________ 71

1. Avvertenze Generali

Da leggere prima di procedere ulteriormente nell’utilizzo del

manuale.

Il presente manuale costituisce parte integrante del

prodotto e deve essere conservato presso l’apparecchio

per una facile e rapida consultazione.

Il regolatore non deve essere usato con funzioni diverse

da quelle di seguito descritte, in particolare non può

essere usato come dispositivo di sicurezza.

Prima di procedere verificare i limiti di applicazione.

Dixell Srl si riserva la facoltà di variare la

composizione dei propri prodotti, senza darne

comunicazione al cliente, garantendo in ogni caso

l’identica e immutata funzionalità degli stessi.

1.1 Precauzioni Di Sicurezza

Prima di connettere lo strumento verificare che la

tensione di alimentazione sia quella richiesta.

Esporre solo il frontale dello strumento agli agenti

atmosferici: protezione frontale IP54 (ip65 con guarnizione

retrofrontale opzionale). Impiegare il regolatore solo nei

limiti di funzionamento previsti.

Attenzione: prima di iniziare qualsiasi manutenzione

disinserire i collegamenti elettrici dello strumento.

Lo strumento non deve mai essere aperto.

In caso di malfunzionamento o guasto, rispedire lo

strumento al rivenditore o alla “DIXELL s.r.l.” (vedi

indirizzo) con una precisa descrizione del guasto.

Tenere conto della corrente massima applicabile a

ciascun relè (vedi Dati Tecnici).

Fare in modo che i cavi delle sonde, della alimentazione

del regolatore, della alimentazione dei carichi

rimangano separati e sufficientemente distanti fra di

loro, senza incrociarsi e senza formare spirali.

Installare le sonde in modo che non siano accessibili ad

eventuali utenti.

Nel caso di applicazioni in ambienti industriali

particolarmente critici, può essere utile inoltre adottare

filtri di rete (ns. mod. FT- PW filtro di rete ), (ns. mod.

FT- IL filtro da collegare in parallelo ai carichi induttivi).

Page 3: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 3/72

1.2 Manuale completo

Dixell S.r.l. si riserva il diritto di

modificare questa guida rapida

senza nessun preavviso. La

versione completa del manuale

può essere richiesta via E_mail

all’indirizzo

[email protected].

2. Generalità iCHILL serie 200L/D è un controllore elettronico per

applicazioni in unità chiller mono o bicircuito:

Aria/aria

Aria/acqua

Acqua/acqua

Motocondensanti

Tutte e quattro le tipologie con:

Pompa di calore a reversibilità del gas

2.1 Funzioni Principali Gestione di unità chiller:

Mono circuito fino a quattro compressori

Doppio circuito con numeri di compressori dispari tra i

circuiti

Doppio circuito fino a 6 compressori

Con compressori a vite

Avviamenti compressori configurabili:

Diretto

Part winding

Stella triangolo

Partenze soft configurabili:

Partenza con valvola di parzializzazione

Valvola partenza a vuoto

Valvola by pass gas esterna al compressore

Gestione parzializzazioni :

funzionamento continuo

funzionamento a gradini

funzionamento modulante (compressori a vite)

Rotazione e termoregolazione compressori

configurabile da parametro:

da n° ore di funzionamento

da n° avviamenti (spunti) ora

Funzione iniezione liquido compressori

Controllo con sonda PTC dedicata

Funzione allarme alta temperatura di mandata (scarico)

compressori

Controllo con sonda PTC dedicata

Gestione completa di due gruppi di pompaggio lato

acqua:

2 pompe lato evaporatore

2 pompe lato condensatore

Visualizzazione di default display personalizzata di tutte

le grandezze controllate

Temperature

Pressioni

Tempi / orologio in tempo reale

Altre visualizzazioni disponibili a display

Stato degli ingressi digitali preposti alla sicurezza del

chiller

Ore di funzionamento compressori

N° avviamenti (spunti) ora compressori

Ore di funzionamento pompe acqua evaporatore /

condensatore

Tempo mancante all’inizio dello sbrinamento dei due

circuiti

Percentuale di lavoro delle sei uscite proporzionali

Temperatura di mandata compressori

Reset allarmi con password personalizzata

Storico allarmi

Allarmi di termica compressore

Possibilità da tasto di abilitare / disabilitare il

funzionamento del singolo circuito frigorifero

Consente la manutenzione dello stesso

Consente un funzionamento “parzializzato” dell’unità

Possibilità da tasto di abilitare / disabilitare il

funzionamento del singolo compressore

Manutenzione del singolo compressore

Malfunzionamento

Gestione completa del pump down:

Con pressostato dedicato

Attraverso il pressostato di bassa

Attraverso il trasduttore di bassa pressione

Funzione Di Unloading circuito:

Da alta temperatura acqua in ingresso evaporatore

Da alta temperatura acqua in ingresso condensatore

(unità con recupero)

Da alta pressione di condensazione

Da bassa pressione di evaporazione

Funzione di segnalazione manutenzione carichi

controllati:

Compressori

Pompe evaporatore

Pompa condensatore

Funzione relè ausiliari circuito:

Due uscite relè completamente configurabili, anche

svincolate dal normale funzionamento della macchina

controllata, gestite tramite sonda temperatura NTC o

PTC o con trasduttore di pressione 4÷20mA – 0.5Volt

Funzionamento settimanale in energy saving:

Fino a tre fasce orarie giornaliere (strumento con

orologio a bordo)

Da ingresso digitale

Funzionamento settimanale con accensione e

spegnimento automatico:

Fino a tre fasce orarie giornaliere (strumento con

orologio a bordo)

Funzione di set point dinamico:

Gestito tramite ingresso analogico in temperatura

(sonda NTC) o ingresso in corrente 4÷20mA

Funzione change over :

Cambio di funzionamento in automatico tra chiller e

pompa di calore gestito tramite ingresso analogico in

temperatura (sonda NTC)

Funzione OFF da remoto :

Da ingresso digitale configurabile

Funzione chiller pompa di calore da remoto :

Page 4: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 4/72

Da ingresso digitale con logica configurabile

Funzione hot start :

Unità aria / aria

Gestione sbrinamento:

In temperatura in pressione o con entrambe (controllo

combinato)

Sbrinamento forzato per partenze con basse

temperature aria esterna

Da ingresso digitale o a tempo

Manuale da tasto

Funzione boiler:

Con gestione delle resistenze in integrazione o

riscaldamento in chiller o pompa di calore

N° 2 uscite per il controllo proporzionale della velocità

dei ventilatori di condensazione tramite modulo

esterno (inverter o taglio di fase monofase / trifase) con

segnale configurabile:

PWM

0÷10Volt

4÷20mA

N° 4 uscite per il controllo proporzionale 0÷10V o

ON/OFF

Per il controllo di servomotori in funzionamento in free

cooling o in recupero

Per il pilotaggio di un relè esterno

Gestione allarmi completa

Con data logger allarmi interno (fino a 100 eventi)

Supervisione / tele assistenza / monitoraggio

Collegabile tramite uscita RS485 con protocollo

Mod_Bus ai sistemi di supervisione Dixell per un

completo controllo e supervisione sia da locale che da

remoto

Fino a n° 2 terminali remoti con visualizzazione dei valori a

display personalizzata

con sonda NTC a bordo per la visualizzazione della

temperatura ambiente e la termoregolazione.

3. Caratteristiche Serie IC200 L/D

CARATTERISTICHE

IC260L/D IC261L/D

USCITE RELÈ

10

14

INGRESSI DIGITALI

18 Config Config

INGRESSI SONDA

6 NTC - PTC Config Config

4 NTC - PTC - 4÷20mA - 0 ÷ 5Volt Config Config

USCITE PROPORZIONALI

2 uscite per moduli ventole

condensazione (segnale PWM)

2 uscite per moduli ventole

condensazione (segnale 0÷10V o

4÷20mA)

Config Config

4 uscite analogiche 0÷10V per gestione

free cooling e recupero calore o

ON/OFF per pilotaggio relè esterno

Config Config

ULTERIORI USCITE

TTL / RS – 485 con protocollo Mod-

BusRtu

Uscita tastiera VI620 (fino a 2 terminali

remoti con sonda a bordo)

ALIMENTAZIONE

12 Vac/dc (+15%;-10%)

24 Vac/dc (± 10%) Opt Opt

DISPLAY SUPERIORE

Page 5: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 5/72

± 3 cifre con punto decimale

DISPLAY INFERIORE

± 4 cifre con punto decimale

ALTRO

Orologio interno Opt Opt

Buzzer Opt Opt

Config. = configurabile da parametro

Opt = opzionale

= standard

4. Interfaccia Utente

4.1 Significato dei led della tastiera dei modelli IC260L - IC261L

4.2 Significato Led Tasti Terminale Remoto VI620 / VI620S

Page 6: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 6/72

4.3 Le icone del Display

ICONA SIGNIFICATO / FUNZIONAMENTO

Gradi celsius:

Gradi fahrenheit:

Bar:

PSI Psi:

compressore 1

compressore 1

compressore 1

compressore 1

compressore 1

compressore 1

Icona allarme generale:

Icona resistenze antigelo / appoggio /

boiler:

Allarme di flussostato

Orologio in tempo reale:

Pompa acqua:

Ventole di condensazione

4.4 Significato / Funzionamento

Dei Led Display Inferiore

Led N° 1 – 2 (Strumento Con Orologio A Bordo)

Se nel display inferiore viene visualizzata l’ora si accende

l’icona orologio e lampeggiano i led n° 1 / 2

Led N° 1 – 2 In Menu Funzioni

All’interno del menu funzioni lampeggiano i led n° 1 / 2

quando viene visualizzato il tempo mancante all’inizio dello

sbrinamento del circuito n° 1 o del circuito n° 2

Led In Programmazione Parametri

Il led n° 3 nel livello Pr2 indica la visibilità mentre i led n° 1 / 2

se il parametro visualizzato è modificabile o no

I led n° 3 / 4 nel livello Pr3 indicano le visibilità e i led n° 1 / 2

se il parametro visualizzato è modificabile o no

4.5 Funzione Dei Tasti

TASTO AZIONE FUNZIONE

Premi e rilascia

Visualizza set point in chiller

(label SetC) in pompa di calore

(label SetH)

Premi e rilascia

2 volte

se la funzione di energy saving

o set point dinamico è abilitata il

led vicino al tasto lampeggia:

visualizza set reale di lavoro

(label Setr)

Premi 3

secondi e

rilascia

Modifica set chiller / pompa di

calore

In

programmazion

e premi e

rilascia

Seleziona un parametro o

conferma un valore

Premi e rilascia

con

visualizzazione

di una label

sonde nel

display inferiore

Modifica visualizzazione

display da circuito 1 a circuito 2

e viceversa

Premi e rilascia

Seleziona la visualizzazione nel

circuito n° 1 delle temperature /

pressioni nel display

In

programmazion

e premi e

rilascia

scorre i codici dei parametri o

ne incrementa il valore.

In

programmazion

e premi 1

secondo e

rilascia

1 volta visualizza il livello di

programmazione Pr2; 2 volta

visualizza il livello di

programmazione Pr3

Premi e rilascia

Seleziona la visualizzazione nel

circuito n° 2 delle temperature /

pressioni nel display

In

programmazion

e premi e

rilascia

Scorre i codici dei parametri o

ne decrementa il valore

Premi e rilascia

Accende spegne la macchina in

chiller, con unità accesa il led

vicino al tasto è acceso

Il led del tasto lampeggia se è

attivo il conteggio del tempo di

ritardo accensione da POWER

ON e in fase di spegnimento

con pump down

Premi e rilascia

Accende spegne la macchina in

pompa di calore, con unità

accesa il led vicino al tasto è

acceso

Il led del tasto lampeggia se è

attivo il conteggio del tempo di

ritardo accensione da power

ON e in fase di spegnimento

con pump down

Premi e rilascia permette di entrare in menu

funzioni

Page 7: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 7/72

Premi 3

secondi e

rilascia

Consente l’ingresso nel menu

di regolazione data ora

(strumento con orologio a

bordo)

In

programmazion

e premi e

rilascia

Permette di uscire dalle

famiglie di parametri

Premi e rilascia

Consente il funzionamento della

macchina in chiller con

recupero con unità in

funzionamento recupero il led

vicino al tasto è acceso

Premi e

rilascia

Consente il funzionamento della

macchina in chiller con free

cooling con unità in

funzionamento free cooling il

led vicino al tasto è acceso

4.6 Funzione Combinata Dei Tasti

4.7 Icone Frontale

ICONA LED FUNZIONE

Acceso Uscita relè ausiliaria n° 1 attiva

Spento Uscita relè ausiliaria n° 1

disattiva

Acceso Uscita relè ausiliaria n° 2 attiva

Spento Uscita relè ausiliaria n° 2

disattiva

Lampeggiant

e

Tempo attesa inizio

sbrinamento

Acceso fisso Ciclo di sbrinamento in corso

Spento Ciclo di sbrinamento ultimato

5. Terminale Remoto

È possibile collegare allo strumento fino a

due terminali remoti che sono disponibil i

anche con sonda NTC a bordo. La sonda a

bordo consente se voluto anche la

termoregolazione della macchina.

E’ possibile collegare in parallelo fino a

due terminali remoti ogni uno con sonda

NTC a bordo. Se si uti l izza un terminale

remoto con sonda a bordo è necessario:

Per i l terminale remoto n° 1 impostare

il PAR: CF74 = 1 sonda NTC a bordo

Per i l terminale remoto n° 2 impostare

il PAR: CF75 = 1 sonda NTC a bordo

I terminali remoti possono essere

“interfacciati” direttamente util izzando un

cavo SCHERMATO / INTRECCIATO ( ES.

Belden 8772 da min. 1 mm2 ) fino a 150M.

Il display superiore visualizza “noL” (no

link), nel caso di mancanza di

comunicazione tra lo strumento e il

terminale remoto. (polarità

dell’alimentazione non rispettata)

ATTENZIONE

Una non corretta selezione dell’indirizzo

seriale tramite l’interruttore a bordo del

terminale (v edi Fig.1) può causare un mal

funzionamento del terminale stesso.

Fig.1

Mod. VI620 - VI620S

6. Prima Installazione

6.1 Strumento Con Orologio A Bordo

Se alimentando lo strumento, sul display

inferiore appare il messaggio “rtC” alternato

con la temperatura / pressione significa

che è necessario regolare l’orologio. Se

TASTO AZIONE FUNZIONE

Premi 3 secondi e

rilascia

Ingresso in

programmazione

In programmazione

livello Pr3 tenere

premuto SET premi

e rilascia tasto

DOWN

Seleziona la

visibilità dei

parametri nei

livelli Pr1 / Pr2 /

Pr3

Premi e rilascia Esci dalla

programmazione

Premi per 5 secondi

(in pompa di calore

se le condizioni lo

consentono)

Sbrinamento

manuale

In programmazione

livello Pr3 tenere

premuto SET premi

e rilascia tasto

MENU

Decide la

modificabilità dei

parametri nei

menu di

programmazione

Page 8: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 8/72

le sonde predisposte al controllo dell’unità

non sono collegate o sono guaste sui due

display verrà visualizzato il relativo allarme.

Si può comunque procedere con la

regolazione dell’orologio o con la

programmazione. ATTENZIONE L’orologio

è un optional se si necessita di un utilizzo

di uno strumento con orologio a bordo lo

si dev e specificare nell’ordine di

acquisto.

Se lo strumento con orologio a bordo

rimane senza alimentazione per più di una

settimana (durata massima della batteria

tampone interna) al prossimo power ON

sarà necessario regolare l’orologio.

6.2 Come Regolare L’orologio

1. Premere il pulsante M per alcuni

secondi finché sul display inferiore

appare la scritta “Hour” e su quello

superiore l’ora memorizzata.

2. Premere il tasto SET: l ’ora inizia a

lampeggiare.

3. Regolare l’ora con i tasti down e UP.

Confermare l’ora premendo il tasto

SET; i l controllore visualizzerà

l ’impostazione successiva.

4. Ripetere le operazioni 2. 3. e 4. sugli

altri parametri dell ’orologio:

- Min: minuti (0÷60)

- UdAy: giorno della settimana (Sun =

domenica, Mon = lunedì, tuE =

martedì, UEd = mercoledì, tHu =

giovedì, Fri = venerdì, SAt = sabato)

- dAy: giorno del mese (0÷31)

- MntH: mese(1÷12)

- yEAr: anno (00÷99)

7. Visualizzazione Delle

Grandezze Controllate

In funzionamento normale viene

visualizzato di default sempre il circuito n°

1

Il circuito visualizzato viene indicato dal

LED Cir1 (circuito n° 1) acceso vicino al

tasto UP, o Cir2 (circuito n° 2) acceso

vicino al tasto DOWN.

- Come Visualizzare Le Grandezze

All’interno Di Un Circuito

Con il led Cir1 acceso se premo i tasti UP o

Down scorro tutte le grandezze controllate

nel circuito n° 1

Con il led Cir2 acceso se premo i tasti UP o

Down scorro tutte le grandezze controllate

nel circuito n° 2

Ad ogni grandezza selezionata corrisponde

un label che identifica i valori di

temperatura o pressioni visualizzate dai

display (vedi tabelle di visualizzazione

display superiore ed inferiore).

- Come Visualizzare Le Grandezze Del

Circuito n° 1 O Del Circuito n° 2

Per passare da un circuito all ’altro si deve

selezionare con i tasti UP o DOWN una

label di identificazione all ’interno di un

circuito e premere il tasto SET.

Esempio:

Fig.1 Led cir1 acceso: i l display superiore

visualizza la temperatura uscita

evaporatore circuito n° 1 ( 7.8°C), i l display

inferiore la label Out1, se premo il tasto

SET, cambio la v isualizzazione del

circuito. Fig.1

Fig.2 led cir2 acceso: i l display superiore

visualizza la temperatura uscita

evaporatore circuito n° 2 ( 7.9°C) il display

inferiore label Out2.

Fig.2

8. Programmazione con la Hot

key 64

8.1 Come Programmare lo

Strumento con Chiavetta già

Programmata (Download)

A strumento spento:

1) Inserire la chiavetta.

Page 9: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 9/72

2) Accendere lo strumento.

3) Inizia lo scarico dei dati dalla

chiavetta allo strumento.

Durante questa fase le regolazioni sono

bloccate e sul display inferiore viene

visualizzato il messaggio “dOL”

lampeggiante.

Alla fine sul display superiore appare il

messaggio:

“End “ Se la programmazione è andata a

buon fine (dopo 15s parte la regolazione).

“Err” Se la programmazione non è andata

a buon fine

In caso di errore lo strumento deve essere

spento e riacceso per ripetere l’operazione

o per partire con la normale regolazione.

8.2 Come Memorizzare I Parametri

Dello Strumento Sulla Chiavetta

(Upload)

A strumento acceso:

1. Inserire la chiavetta.

2. Entrare in menu funzioni

3. Selezionare la funzione UPL display

inferiore

4. Premere SET. Inizia lo scarico dei dati

dallo strumento alla chiavetta.

Durante questa fase sul display inferiore

viene visualizzato il messaggio “UPL”

lampeggiante.

Alla fine della fase di programmazione lo

strumento visualizza sul display superiore i

seguenti messaggi :

“End “ Se la programmazione è andata a

buon fine

“Err” Se la programmazione non è andata

a buon fine.

Per uscire dalla funzione UPL premere il

tasto M o aspettare il tempo di time-out.

(Ripetere i punti 1-4 per un nuovo

UPLOAD).

1) Selezionare il parametro “Pr2” display

inferiore valore della password display

superiore

2) Premere SET per abilitare la modifica

(valore lampeggiante)

3) Inserire la nuova password usando i

tasti o e n

4) Premere il tasto SET per confermare il

nuovo valore.

9. Programmazione Da Tastiera

Attraverso la tastiera e’ possibile modificare

i valori di tutti i parametri e impostare per

ogni uno visibil ità e modifica nei tre l ivell i

di programmazione disponibil i. I parametri

del controllore sono stati raccolti in famiglie

ognuna identificata con una label. Questo

permette all ’utente un rapido accesso nei

vari l ivell i ai parametri interessati.

Tre livell i di programmazione:

1. Pr1 livello utente

2. Pr2 livello assistenza

3. Pr3 livello costruttore

9.1 Valori Di Default Password

In programmazione password Livello Pr1 =

1

In programmazione password Livello Pr2 =

2

In programmazione password Livello Pr3 =

3

In menu funzioni password reset storico

allarmi e allarmi termica compressore = 0

(Parametro famiglia AL)

Tutte le password possono essere

modificate e personalizzate con v alori

che v anno da 0 a 999.

Per ogni parametro ci sono due liv elli di

v isibilità e modifica:

1. Il parametro può essere visibile e

modificabile

2. Il parametro può essere visibile ma

non modificabile

9.2 Come Entrare In

Programmazione Nei Livelli

Pr1 - Pr2 - Pr3

Liv ello Pr1:

Premere contemporaneamente i l tasti SET

+ DOWN per 3 sec il display superiore

visualizza la label PAS il display inferiore

label Pr1 (l ivello Pr1), lampeggiano i due

led cir1 / cir2 dei tasti UP e DOWN per

segnalare l’effettivo ingresso in

programmazione.

Liv ello Pr2:

Page 10: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 10/72

Entrati in programmazione quando si

visualizza la label Pr1 display inferiore,

PAS display superiore premere il tasto UP

per 2 secondi i l display inferiore visualizza

la label Pr2 secondo livello.

Liv ello Pr3:

Entrati in programmazione quando si

visualizza la label Pr2 display inferiore,

PAS display superiore premere il tasto UP

per 2 secondi i l display inferiore visualizza

la label Pr3 terzo livello.

Scelto i l l ivello premere il tasto SET display

superiore 0 lampeggiante

Con i tasti UP o DOWN imposto il valore

della password (l’ingresso in uno dei 3

l ivell i di programmazione viene

determinato dal valore della password) se

la password è corretta premo SET ed entro

nel l ivello di programmazione scelto

altrimenti viene riproposta la password.

(tutti e 3 i l ivell i contengono tutte le

famiglie di parametri)

ATTENZIONE: in tutti e tre i liv elli non e’

consentita la modifica dei v alori dei

parametri contenuti nella famiglia CF con

lo stato di funzionamento selezionato

unità in moto in chiller o in pompa di

calore della famiglia dF durante un ciclo

di sbrinamento. L’impossibilità di

modificare il v alore del parametro v iene

segnalata dal lampeggio dei led n° 1 e n°

2. Se si dev e modificarne il v alore uscire

dalla programmazione e posizionare

l’unita’ in stand-by e rientrare in

programmazione.

9.3 Come Cambiare Il Valore Di Un

Parametro

Entrare In Programmazione

1. Premere contemporaneamente il tasti

SET + DOWN per 3 sec

2. Selezionare il parametro desiderato

3. Premere il tasto SET per abilitare la

modifica del valore

4. Modificare il valore con i tasti UP o

DOWN

5. Premere “SET” per memorizzare il

nuovo valore e passare al codice del

parametro successivo

6. Uscita: Premere SET + UP, quando si

visualizza un parametro, o attendere

(15s) senza premere alcun tasto

NOTA: Il nuovo valore impostato viene

memorizzato anche quando si esce per

time out senza aver premuto il tasto SET.

9.4 Come Modificare Le

Password

LIVELLO Pr1

Per modificare la password è necessario

conoscere quella vecchia.

1. Entrare in programmazione livello Pr1

2. Selezionare una famiglia di parametri.

3. All ‘interno di questa famiglia

selezionare la funzione “Pr1 - 1”, Pr1

sul display inferiore, valore1 password

corrente sul display superiore, quindi

premere il tasto SET per abilitare la

modifica il display superiore visualizza

i l valore lampeggiante.

4. Con i tasti UP o DOWN Immettere la

NUOVA PASSWORD poi premere il

tasto SET per confermare il nuovo

valore

5. Il display superiore lampeggerà per

alcuni secondi e poi verrà visualizzato

il parametro successivo

6. Uscire dal modo programmazione

premendo SET + UP o attendere il

tempo di time out senza premere

alcun tasto.

LIVELLO Pr2

Per modificare la password è necessario

conoscere quella vecchia.

1. Entrare in programmazione livello Pr2

2. Selezionare una famiglia di parametri

3. All ‘interno di questa famiglia

selezionare la funzione “Pr2 - 2”, Pr2

sul display inferiore, valore 2 password

corrente sul display superiore, quindi

premere il tasto SET per abilitare la

modifica il display superiore visualizza

i l valore lampeggiante.

4. Con i tasti UP o DOWN Immettere la

NUOVA PASSWORD poi premere il

tasto SET per confermare il nuovo

valore

Page 11: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 11/72

5. Il display superiore lampeggerà per

alcuni secondi e poi verrà visualizzato

il parametro successivo

6. Uscire dal modo programmazione

premendo SET + UP o attendere il

tempo di time out senza premere

alcun tasto.

All’interno del l ivello Pr2 è possibile

modificare anche la password del l ivello

Pr1

LIVELLO Pr3

Per modificare la password è necessario

conoscere quella vecchia.

1. Entrare in programmazione livello Pr3

2. Selezionare una famiglia di parametri.

3. All ‘interno di questa famiglia

selezionare la funzione “Pr3 - 3”, Pr3

sul display inferiore, valore 3 password

corrente sul display superiore, quindi

premere il tasto SET per abilitare la

modifica il display superiore visualizza

i l valore lampeggiante.

4. Con i tasti UP o DOWN Immettere la

NUOVA PASSWORD poi premere il

tasto SET per confermare il nuovo

valore

5. Il display superiore lampeggerà per

alcuni secondi e poi verrà visualizzato

il parametro successivo

6. Uscire dal modo programmazione

premendo SET + UP o attendere il

tempo di time out senza premere

alcun tasto.

All’interno del l ivello Pr3 è possibile

modificare anche la password del l ivello

Pr1 / Pr2

9.5 Come Spostare Un Parametro

Da Livello Pr3 A Livello Pr2 A

Livello Pr1

Entrare In Programmazione Liv ello Pr3

Selezionare il parametro desiderato, se tutti

i led sono spenti significa che il parametro

visualizzato è visibile solo in Pr3

Per spostare il parametro dal l ivello Pr3 al

l ivello Pr2 / Pr1:

1. Tenere premuto il tasto SET

2. Premere e ri lasciare 1 volta i l tasto

DOWN i l led n° 3 e ° 4 si accendono

ora il parametro è visibile anche in Pr2

/ Pr1

Per riportare la visibil ità del parametro dal

l ivello Pr1 / Pr2 a livello Pr2:

1. Tenere premuto il tasto SET

2. Premere e ri lasciare 1 volta i l tasto

DOWN i l led n° 3 si spegne il

parametro ritorna visibile solo in Pr2

Per riportare la visibil ità del parametro dal

l ivello Pr2 al l ivello Pr3:

1. Tenere premuto il tasto SET

2. Premere e ri lasciare 1 volta i l tasto

DOWN i l led n° 4 si spegne il

parametro ritorna visibile solo in Pr3

9.6 Come Rendere Un Parametro

Visibile Ma Non Modificabile

E’ Possibile Modificare La Visibilità Solo

A Liv ello Pr3

ENTRARE IN PROGRAMMAZIONE

LIVELLO PR3

1. Selezionare il parametro desiderato

2. Tenere premuto il tasto SET

3. Premere e ri lasciare 1 volta i l tasto

MENU i l led n° 3 acceso fisso diventa

lampeggiante significa che quel

parametro è visibile in Pr1 ma non

modificabile

NEL LIVELLO Pr2

ENTRARE IN PROGRAMMAZIONE

LIVELLO PR3

1. Selezionare il parametro desiderato

2. Tenere premuto il tasto SET

3. Premere e ri lasciare 1 volta i l tasto

MENU i l led n° 4 acceso fisso diventa

lampeggiante significa che quel

parametro è visibile in Pr2 ma non

modificabile

I led n° 3 / 4 lampeggianti significano che

quel parametro è visibile in Pr1 / Pr2 ma

non è modificabile

Come rendere nuov amente v isibile e

modificabile un parametro a liv ello pr1 /

pr2

1. Tenere premuto il tasto SET

2. Premere e ri lasciare il tasto MENU i

led n° 3 / 4 diventano accesi fissi i l

parametro ridiventa visibile e

modificabile

Page 12: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 12/72

10. Il Menu Funzioni “Tasto M”

l ’ingresso nel menu funzioni da la

possibil ità di:

1) Visualizzare e resettare gli allarmi

presenti (funzione ALrM)

2) Resettare gli allarmi di termica

compressore presenti (funzione COtr)

3) Visualizzare e cancellare lo storico

allarmi (funzione ALOG)

4) Caricare i parametri dallo strumento

sulla chiavetta (funzione UPL)

5) Abilitare – disabilitare da tasto il

funzionamento di un singolo circuito

(funzione CrEn)

6) Abilitare – disabilitare da tasto il

funzionamento di un singolo

compressore (funzione COEn)

7) Visualizzare la temperatura di

mandata dei compressori (funzione

COdt)

8) Visualizzare e resettare le ore di

funzionamento dei carichi controllati

(funzione Hour)

9) Visualizzare e resettare il numero di

avviamenti (spunti) di ogni

compressore (funzione COSn)

10) Visualizzare la percentuale di

funzionamento delle uscite

proporzionali per i l controllo della

velocità delle ventole di

condensazione (funzione Cond)

11) Visualizzare la percentuale di

funzionamento delle 4 uscite

proporzionali 0 ÷ 10 Volt (funzione

Pout)

12) Visualizzare il tempo mancante per

l ’inizio dello sbrinamento dei due

circuiti (solo se l’unità è configurata

come pompa di calore) (funzione dF)

13) Visualizzare il valore delle sonde, del

set point e lo stato delle uscite del free

cooling (solo se l’unità è configurata

con Free cooling) (funzione FC)

14) Visualizzare il valore delle sonde, del

set point e lo stato delle uscite del

pannello solare (solo se l’unità è

configurata con pannelli solari)

(funzione SoL)

15) Visualizzare la temperatura delle

sonde che controllano le uscite

ausiliarie (funzione uS)

ACCESSO AL MENU FUNZIONI

Premere e ri lasciare il tasto M (menu)

USCITA DAL MENU FUNZIONI

Premere e ri lasciare il tasto M o aspettare il

tempo di time out .

Con i tasti UP o DOWN è possibile scorrere

ciclicamente la l ista delle funzioni.

10.1 Come Visualizzare Lo Stato Di

Un Allarme Ed Effettuarne Il

Reset

FUNZIONE ALrM

Entrare in menu funzioni

1. Con i tasti UP o DOWN selezionare la

funzione ALrM

2. Premere il tasto SET (Se non è

presente nessun allarme la pressione

del tasto SET non è abilitata)

3. Display inferiore label con codice

allarme, display superiore label rSt se

l ’allarme è resettabile se non è

resettabile label NO

4. Scorrere tutti gli allarmi presenti tasto

UP o DOWN

5. Se premo SET in corrispondenza della

label rSt resetto l’allarme e passo al

successivo, se anche questo è

resettabile premo Set, lo resetto e

passo al successivo. Se premo SET in

presenza di un allarme non resettabile

label NO non succede niente per

vedere il prossimo premo UP o DOWN

6. Per uscire dalla funzione ALrM ritorno

in visualizzazione normale premere il

tasto MENU o aspettare il tempo di

time - out

10.2 Come Resettare Un Allarme Di

Termica Compressore

presenti in base agli ingressi digitali

configurati come allarme termica

compressore

ATTENZIONE

La funzione COtr è presente nel menù

funzioni solo se viene raggiunto il numero

di interventi ora allarme termica

Page 13: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 13/72

compressore impostato nel Par. AL20.,

raggiunto il quale il

reset dell’allarme passa da riarmo

automatico a riarmo MANUALE

RESET ALLARME A RIARMO MANUALE

Entrare in menu funzioni

1. Con i tasti UP o DOWN selezionare la

funzione COtr display inferiore

2. Premere il tasto SET i l display inferiore

visualizza la label che identifica

l ’allarme di termica del compressore

ES. CO1r il display superiore

visualizza la label rSt se l’allarme è

resettabile se non è resettabile label

NO con i tasti UP o DOWN è possibile

scorrere tutte le label degli allarmi

attivi in ordine crescente

3. Se premo il tasto SET in presenza di

un allarme non resettabile label NO

non succede niente

4. Se premo il tasto SET in

corrispondenza della label rSt mi

viene chiesta la password per i l reset

display inferiore label ArSt display

superiore PAS.

5. Premere SET display inferiore PAS

display superiore 0 lampeggiante.

Immettere la password per la

cancellazione tasti UP o DOWN (valore

password vedi menù AL) Se la

password è corretta la label ArSt

lampeggia per 3sec, (conferma reset),

se la password non è corretta si

rivisualizza nel display inferiore PAS

nel display superiore 0 lampeggiante

e se non viene reimpostata dopo 5

sec. ritorno alla label CO1r

6. Per uscire dalla funzione COtr e

ritornare in visualizzazione normale

premere il tasto MENU o aspettare il

tempo di time - out.

7. Ripetere le operazioni 1 – 5 con gli

altri allarmi di termica compressori

10.3 Password Reset Allarmi Di

Termica Compressore

Il valore di default della password e’ 0 la

modifica del valore della password per i l

reset degli allarmi è consentito solo nel

l ivello di programmazione Pr3 (all’interno

dalla famiglia di parametri AL)

10.4 Come Vedere Lo Storico

Allarmi In Memoria

FUNZIONE ALOG

procedura per vedere lo storico allarmi in

memoria

(Ia funzione e i codici di allarme sono

presenti solo se presenti allarmi, nel caso di

più allarmi attivi la visualizzazione avviene

in ordine crescente )

Entrare in menu funzioni

1. Selezionare la funzione ALOG

2. Premere il tasto SET (Se non è

presente nessun allarme la pressione

del tasto SET non è abilitata)

3. Display inferiore label con codice

allarme, display superiore label “n” con

numero progressivo da 00 a 99

4. Scorrere tutti gli allarmi presenti tasto

UP – DOWN

5. Per uscire dalla funzione ALOG e

ritornare in visualizzazione normale

premere il tasto MENU o aspettare il

tempo di time - out

10.5 Come Cancellare Lo Storico

Allarmi In Memoria

FUNZIONE ALOG

procedura per cancellare lo storico allarmi

in memoria

1. Entrare in menu funzioni

2. Con i tasti UP o DOWN selezionare la

funzione ALOG display inferiore

3. Premere il tasto SET

4. All ’ interno della funzione ALOG

selezionare la label ArSt display

inferiore, display superiore PAS con i

tasti UP o DOWN

5. Premere il tasto SET display inferiore

PAS display superiore 0 lampeggiante

6. immettere la password per la

cancellazione (valore password dello

storico allarmi vedi famiglia di

parametri AL)

7. Se la password è corretta la label ArSt

lampeggia per 5sec, per confermare la

cancellazione. Dopo la cancellazione

si esce automaticamente dal menu

Page 14: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 14/72

funzioni e si ritorna in visualizzazione

normale

8. Se la password non è corretta si

rivisualizza PAS. Se non introduco la

password corretta, posso comunque

scorrere gli allarmi in memoria con i

tasti UP o DOWN

9. Per ritornare in visualizzazione

normale, premo MENU o aspetto il

time - out

10.6 Password Reset Storico

Allarmi

i l valore di default della password e’ 0 la

modifica del valore della password per i l

reset dello storico allarmi è consentito solo

nel l ivello di programmazione Pr3

all’interno dalla famiglia di parametri AL.

Gli allarmi contenuti in memoria sono

100, ogni allarme che v errà rilev ato al di

sopra di questo numero, cancellerà

automaticamente in memoria l’allarme più

v ecchio.

11. Altre Visualizzazioni A

Display

11.1 Come Visualizzare Il Set Point

Premere e ri lasciare i l tasto SET si

spengono i led che identificano i circuiti e

viene visualizzato il set point di lavoro

Con unità in stand by il display inferiore

visualizzerà SetC (set chil ler) e alla

seconda pressione SetH (set pompa di

calore ). Con unità in moto solo il set point

relativo allo stato di funzionamento

Il display superiore il valore impostato.

(la label SetH viene visualizzata solo per

unità configurata come pompa di calore)

11.2 Come Modificare Il Set Point

1) Premere il tasto SET per almeno 3 sec

si spengono i led che identificano i

circuiti e viene visualizzato il set point

di lavoro lampeggiante

2) Per modificare il valore agire sui tasti

UP o DOWN

Per memorizzare il nuovo set point,

premere il tasto SET o attendere il tempo di

time out per uscire dalla programmazione.

12. Installazione E Montaggio

12.1 Dima Di Foratura Ichill Serie

200 Formato L

Gli strumenti vanno montati a pannello

verticale, su foro 150x31mm, e fissati con 2

viti 3 x 2mm con distanza 165mm. Per

ottenere una protezione frontale IP65

util izzare la gomma di protezione frontale

mod. RG-L (opzionale); RG-LX per

strumenti nel formato INOX (opzionale) .

Evitare i luoghi soggetti a forti vibrazion i,

gas corrosivi, eccessiva sporcizia o umidità.

Le stesse indicazioni valgono anche per le

sonde. Lasciare aerata la zona in prossimità

delle feritoie di raffreddamento.

165150

31

Ø3 x2

12.2 Montaggio Vetrino e Calotte

Frontali con Apertura Verso il

Basso

Page 15: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 15/72

12.3 Montaggio Vetrino e Calotte

Frontali con Apertura Verso

L’alto

12.4 Montaggio Strumento Con

Frontalino In Metallo

12.5 Ichill Serie 200 Formato Din

Gli strumenti possono essere montati su

barra din o a muro su foro 4.3 mm

util izzando le apposite staffe di fissaggio

estraibil i. Evitare i luoghi soggetti a forti

vibrazioni, gas corrosivi, eccessiva sporcizia

o umidità. Le stesse indicazioni valgono

anche per le sonde. Lasciare aerata la zona

in prossimità delle feritoie di

raffreddamento.

AVVERTENZA: tutte le quote riportate nelle

figure che seguono sono espresse in mm.

12.6 Dime Di Foratura Terminale

Remoto Ichill VI620

Il terminale remoto può essere montato a

pannello, su foro 72x56 mm, e fissato con

viti o incassato all ’interno di un normale

porta frutto (interruttore luce civile o

commerciale) incassato nel muro in

verticale.

Per ottenere una protezione frontale IP65

util izzare la gomma di protezione frontale

mod. RG - V (opzionale).

Per il fissaggio esterno a muro e’

disponibile un adattatore per tastiere

verticali V-KIT come il lustrato in fig.1.

Colori disponibil i : Bianco – grigio – nero

Fig. 1

Evitare i luoghi soggetti a forti vibrazioni,

gas corrosivi, eccessiva sporcizia o umidità.

Le stesse indicazioni valgono anche per l e

sonde. Lasciare aerata la zona in prossimità

delle feritoie di raffreddamento.

Page 16: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 16/72

13. Collegamenti Elettrici

Lo strumento è dotato:

Di tre morsettiere sconnettibil i (MOLEX) 16

/ 8 / 22 vie per gli ingressi digitali /

analogici, e le uscite modulanti. Di 4

morsettiere sconnettibil i (STELVIO) 3 / 4 /

5 / 6 vie per le uscite relè

Di un connettore a cinque poli (uscita TTL /

RS485)

Di un connettore a due poli per i l

collegamento del terminale remoto

In tutti e quattro i modelli:

la sezione dei cavi di collegamento delle

morsettiere (MOLEX) 16 / 8 / 22 vie è di 0.5

mm2,

la sezione dei cavi di collegamento delle

morsettiere (STELVIO) 3 / 4 / 5 / 6 vie con

viti, consente un cablaggio di cavi con

sezione massima di 2.5 mm2

Il terminale remoto è dotato di una

morsettiera a 2 vie con vite con

collegamento di cavi con sezione massima

di 2.5 mm2

E’ disponibile un kit di cablaggio ingressi

digitali / analogici, uscite relè, uscite

proporzionali (cod. ordinazione LW30 KIT)

che comprende tre morsettiere sconnettibil i

MOLEX femmina cablate di una lunghezza

di 3 m. Tutti i fi l i del cablaggio riportano

(serigrafato) all ’inizio e alla fine il numero

del morsetto a cui sono collegati

E’ disponibile un kit di cablaggio

connettore a due poli con cavo per i l

collegamento del terminale remoto (cod.

ordinazione CAB/CJ30) con sezione

massima di 0.2 mm2

Prima di connettere i cavi assicurarsi che la

tensione di alimentazione sia conforme a

quella dello strumento. Separare i cavi di

collegamento delle sonde da quelli di

alimentazione, dalle uscite e dai

collegamenti di potenza. Non superare la

corrente massima consentita su ciascun

relè, vedi dati tecnici, in caso di carichi

superiori usare un teleruttore di adeguata

potenza.

Page 17: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 17/72

14. Tabella Allarmi

I codici e le segnalazioni di allarme sono composti da lettere e numeri che ne identificano le

diverse tipologie.

14.1 Tabella Blocco Uscite Allarme Di Macchina Tipo“A”

Cod.

Allarm

e

Descrizione allarme Com

p.

Res.

Antigelo

boiler

Res.

appoggi

o

Pompe dell’acqua /

ventilatore di mandata

Ventilaz.

cond.

Cir1

Cir2

Relè

ausiliari

o

AP1

...

AP12

Allarme sonda PB1 .. Pb12 Si (6)

Si (1)

Si

Si (6) Si (2)

AEFL Allarme flussostato pompa

acqua evaporatore Si Si (boiler)

Si pompa acqua evaporatore

(3) Si

ACFL Allarme flussostato pompa

acqua condensatore Si

Si pompa acqua condensatore

(3) Si

AHFL Allarme flussostato pompa

acqua sanitaria Si pompa acqua sanitaria

APFL Allarme flussostato pompa

acqua solare Si pompa acqua pannelli solari

AtSF Allarme termica ventilatore di

mandata Si Si Si ventilatore di mandata Si

AtE1 Allarme termica pompa

acqua evaporatore n° 1 Si (4)

Si (boiler)

(5) Si pompa acqua evaporatore Si

AtE2 Allarme termica pompa

acqua evaporatore n° 2 Si (4)

Si (boiler)

(5) Si pompa acqua evaporatore Si

AtC1 Allarme termica pompa

acqua condensatore n° 1 Si (4) Si pompa acqua condensatore Si

AtC2 Allarme termica pompa

acqua condensatore n° 2 Si (4) Si

AtAS Termica pompa acqua

sanitaria Si (6)

AtHS Termica resistenze acqua

sanitaria

AEE Allarme di EEprom Si Si Si Si

AFr Allarme frequenza di rete SI SI SI SI

ALSF Allarme sequenza fasi Si Si Si Si Si Si

ALc1 Allarme generico blocco

macchina SI SI SI SI

ALc2 Allarme generico blocco

macchina SI SI SI SI

ALSF Allarme sequenza fasi SI SI SI SI SI SI

ArtF Allarme orologio guasto da

sostituire

ArtC Segnalazione orologio da

regolare

AEUn

Segnalazione di unloading

alta temperatura acqua

evaporatore

ALti

Segnalazione bassa

temperatura aria ingresso

evaporatore unità aria / aria

AEP1

Segnalazione manutenzione

pompa acqua evaporatore n°

1

AEP2 Segnalazione manutenzione

Page 18: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 18/72

pompa acqua evaporatore n°

2

ACP1

Segnalazione manutenzione

pompa acqua condensatore

n° 1

ACP2

Segnalazione manutenzione

pompa acqua condensatore

n° 2

ASAn Manutenzione pompa acqua

calda sanitaria

ASun Manutenzione pompa acqua

pannelli solari

ACF1

...

ACF13

Allarme di configurazione SI

SI SI SI

AEUn

Segnalazione di unloading

alta temperatura ingresso

evaporatore

(1) = Se sonda configurata per il controllo dell’antigelo - boiler e Ar10 = 0

(2) = Se sonda configurata per il controllo dell’uscita relè ausiliario

(3) = Con allarme a riarmo manuale

(4) = Compressori spenti con solo n° 1 pompa acqua configurata o con n° 2 pompe acqua configurate e tutte e due in allarme termica

(5) = Resistenze boiler spente con solo n° 1 pompa acqua configurata o con n° 2 pompe acqua configurate e tutte e due in allarme

termica (in questo caso le resistenze boiler vengono attivate solo dal set antigelo a protezione dell’evaporatore)

(6) = Se la sonda in errore è una sonda di regolazione o di circuito (sonda di condensazione, sonda di aspirazione,..)

14.2 Tabella Blocco Uscite Allarme Di Circuito Tipo “B”

Cod.

Allarme

Descrizione allarme Compresso

ri

circuito

(n)

Compressori

altro circuito

Ventilazione di

Condensazion

e

Circuito (n)

Ventilazione

di

Condensazio

ne altro

circuito

b(n)HP Allarme pressostato di alta pressione circuito (n) Si Si dopo 60 sec.

b(n)LP Allarme pressostato di bassa pressione circuito

(n) Si

Si

b(n)AC Allarme antigelo in chiller circuito (n) Si Si

b(n)AH Allarme antigelo in pompa di calore circuito (n) Si Si

b(n)hP Allarme alta pressione condensazione trasduttore

circuito (n) Si Si dopo 60 sec.

b(n)hP Allarme alta temperatura condensazione sonda

NTC circuito (n) Si Si dopo 60 sec.

b(n)lP

Allarme bassa pressione condensazione -

(evaporazione con trasduttore di bassa pressione)

trasduttore circuito (n)

Si Si

b(n)lP Allarme bassa temperatura condensazione sonda

NTC circuito (n) Si

Si

b(n)tF Allarme termica ventilazione circuito (n) Si Si

b(n)PH Allarme pump down in fermata circuito (n) Si Si

b(n)PL Allarme pump down in avviamento circuito (n) Si Si

b(n)dF Segnalazione allarme di sbrinamento circuito (n)

b(n)Cu Segnalazione di unloading da alta temp. press.

conden. circuito (n)

b(n)Cu Segnalazione di unloading da bassa press. Si Si

Page 19: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 19/72

condensazione circuito (n)

b(n)rC Segnalazione di disabilitazione recupero circuito

(n)

b(n)ds Segnalazione funzionamento circuito (n)

disabilitato da tasto Si Si

b(n)Ac Segnalazione di antigelo in chiller circuito (n)

b(n)Ah Segnalazione di antigelo in pompa di calore

circuito (n)

Dove la lettera (n) identifica il circuito n° 1 o circuito n° 2

14.3 Tabella Blocco Uscite Allarmi Di Compressore Tipo “C”

Cod.

Allarm

e

Descrizione allarme Blocco Compressore

(n)

Blocco Compressori

non interessati

C(n)H

P Allarme pressostato di alta pressione compressore (n) Si No

C(n)o

P

Allarme pressostato / galleggiante olio compressore

(n) Si

No

C(n)tr Allarme termica compressore (n) Si No

C(n)dt Allarme alta temperatura di mandata compressore Si No

C(n)P

d Differenziale olio compressore Si

C(n)d

S

Segnalazione funzionamento compressore (n)

disabilitato da tasto Si No

C(n)M

n Segnalazione manutenzione compressore (n) No No

Dove la lettera (n) identifica il compressore n° 1, 2 , 3 , 4 , 5 , 6

15. Schema Di Collegamento

15.1 Risorse Hardware Modelli IC260L

N° 10 uscite digitali (relè)

N° 18 ingressi digitali (puliti)

N° 10 ingressi analogici: o tutti con sonda NTC o tramite configurazione da parametro 6 ingressi

sonda NTC / PTC e fino a 4 ingressi per trasduttore di pressione 4÷20mA o raziometrico 0÷

5.0Volt

N° 6 uscite modulanti

N° 1 uscita per i l collegamento fino a due terminali remoti

N° 1 uscita TTL per i l collegamento di una Hot Key 64 (chiavetta di programmazione)

trasformabile tramite modulo di interfaccia XJ485 Dixell in una uscita RS485 con protocollo di

comunicazione ModBUS

MAX corrente applicabile ai contatti relè 5(2)A 250V - MAX corrente applicabile ai comuni 12A

250V

Page 20: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 20/72

15.2 Risorse Hardware Modelli IC261L

N° 14 uscite digitali (relè)

N° 18 ingressi digitali (puliti)

N° 10 ingressi analogici: o tutti con sonda NTC o tramite configurazione da parametro 6 ingressi

sonda NTC / PTC e fino a 4 ingressi per trasduttore di pressione 4÷20mA o raziometrico 0÷

5.0Volt

N° 6 uscite modulanti

N° 1 uscita per i l collegamento fino a due terminali remoti

N° 1 uscita TTL per i l collegamento di una Hot Key 64 (chiavetta di programmazione)

trasformabile tramite modulo di interfaccia XJ485 Dixell in una uscita RS485 con protocollo di

comunicazione ModBUS

MAX corrente applicabile ai contatti relè 5(2)A 250V - MAX corrente applicabile ai comuni 12A

250V

15.3 Risorse Hardware Modelli IC260D

N° 10 uscite digitali (relè)

N° 18 ingressi digitali (puliti)

N° 10 ingressi analogici: o tutti con sonda NTC o tramite configurazione da parametro 6 ingressi

sonda NTC / PTC e fino a 4 ingressi per trasduttore di pressione 4÷20mA o raziometrico 0÷

5.0Volt

N° 6 uscite modulanti

N° 1 uscita per i l collegamento fino a due terminali remoti

N° 1 uscita TTL per i l collegamento di una Hot Key 64 (chiavetta di programmazione)

N° 1 uscita RS485 con protocollo di comunicazione ModBUS

Page 21: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 21/72

MAX corrente applicabile ai contatti relè 5(2)A 250V - MAX corrente applicabile ai comuni 12A

250V

15.4 Risorse Hardware Modelli IC261D

N° 14 uscite digitali (relè)

N° 18 ingressi digitali (puliti)

N° 10 ingressi analogici: o tutti con sonda NTC o tramite configurazione da parametro 6 ingressi

sonda NTC / PTC e fino a 4 ingressi per trasduttore di pressione 4÷20mA o raziometrico 0÷

5.0Volt

N° 6 uscite modulanti

N° 1 uscita per i l collegamento fino a due terminali remo ti

N° 1 uscita TTL per i l collegamento di una Hot Key 64 (chiavetta di programmazione)

N° 1 uscita RS485 con protocollo di comunicazione Mod_BUS

MAX corrente applicabile ai contatti relè 5(2)A 250V - MAX corrente applicabile ai comuni 12A

250V

Page 22: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 22/72

15.5 Configurazione Ingressi Analogici Pb1 - Pb2 - Pb7 - Pb8 - Pb9 - Pb10

Parametri :

CF08 = Configurazione PB1

CF09 = Configurazione PB2

CF14 = Configurazione PB7

CF15 = Configurazione PB8

CF16 = Configurazione PB9

CF17 = Configurazione PB10

0. Disabilitato

1. Sonda temperatura PTC di mandata compressore n° 1

2. Sonda temperatura PTC di mandata compressore n° 2

3. Sonda temperatura PTC di mandata compressore n° 3

4. Sonda temperatura PTC di mandata compressore n° 4

5. Sonda temperatura PTC di mandata compressore n° 5

6. Sonda temperatura PTC di mandata compressore n° 6

7. Sonda temperatura PTC temperatura pannello solare

8. Sonda temperatura NTC ingresso evaporatore

9. Sonda temperatura NTC uscita evaporatore n° 1

10. Sonda temperatura NTC uscita evaporatore n° 2

11. Sonda temperatura NTC uscita comune evaporatore /gestione resistenze appoggio (unità

aria/aria)

12. Sonda temp. NTC ingresso comune acqua calda condensatore

13. Sonda temp. NTC ingresso acqua calda condensatore circuito n° 1

14. Sonda temp. NTC ingresso acqua calda condensatore circuito n° 2

15. Sonda temp. NTC uscita acqua calda condensatore circuito n° 1

16. Sonda temp. NTC uscita acqua calda condensatore circuito n° 2

17. Sonda temp. NTC uscita comune acqua calda condensatore

18. Sonda temperatura NTC ingresso acqua impianto (free cooling)

19. Sonda temperatura NTC temperatura aria esterna set point dinamico / funzione boiler /

change over

20. Sonda temperatura NTC sbrinamento combinato circuito n° 1

21. Sonda temperatura NTC sbrinamento combinato circuito n° 2

22. Sonda temperatura NTC uscita ausiliaria circuito n° 1

23. Sonda temperatura NTC uscita ausiliaria circuito n° 2

24. Sonda temperatura NTC temperatura acqua calda sanitaria n. 1

25. Sonda temperatura NTC temperatura acqua calda sanitaria n. 2

26. Sonda temperatura NTC temperatura pannello solare

27. Sonda temperatura NTC condensazione circuito n° 1

28. Sonda temperatura NTC condensazione circuito n° 2

Se l’ingresso deve essere util izzato come ingresso digitale, la configurazione sarà da o1 a C73

ed assumerà il significato visibile in par. 2.3 “CONFIGURAZIONE INGRESSI DIGITALI ID1 –

ID18”

15.6 Configurazione Ingressi Analogici Pb3 - Pb4 - Pb5 - Pb6

Parametri :

CF10 = Configurazione PB3

CF11 = Configurazione PB4

Page 23: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 23/72

CF12 = Configurazione PB5

CF13 = Configurazione PB6

0. Disabilitato

1. Sonda temperatura PTC di mandata compressore n° 1

2. Sonda temperatura PTC di mandata compressore n° 2

3. Sonda temperatura PTC di mandata compressore n° 3

4. Sonda temperatura PTC di mandata compressore n° 4

5. Sonda temperatura PTC di mandata compressore n° 5

6. Sonda temperatura PTC di mandata compressore n° 6

7. Sonda temperatura PTC temperatura pannello solare

8. Sonda temperatura NTC ingresso evaporatore

9. Sonda temperatura NTC uscita evaporatore n° 1

10. Sonda temperatura NTC uscita evaporatore n° 2

11. Sonda temperatura NTC uscita comune evaporatore / gestiore resistenze appoggio (unità

aria/aria)

12. Sonda temp. NTC ingresso comune acqua calda condensatore

13. Sonda temp. NTC ingresso acqua calda condensatore circuito n° 1

14. Sonda temp. NTC ingresso acqua calda condensatore circuito n° 2

15. Sonda temp. NTC uscita acqua calda condensatore circuito n° 1

16. Sonda temp. NTC uscita acqua calda condensatore circuito n° 2

17. Sonda temp. NTC uscita comune acqua calda condensatore

18. Sonda temperatura NTC ingresso acqua impianto (free cooling cooling)

19. Sonda temperatura NTC temperatura aria esterna set point dina mico / funzione boiler /

change over

20. Sonda temperatura NTC sbrinamento combinato circuito n° 1

21. Sonda temperatura NTC sbrinamento combinato circuito n° 2

22. Sonda temperatura NTC uscita ausiliaria circuito n° 1

23. Sonda temperatura NTC uscita ausiliaria circuito n° 2

24. Sonda temperatura NTC temperatura acqua calda sanitaria n. 1

25. Sonda temperatura NTC temperatura acqua calda sanitaria n. 2

26. Sonda temperatura NTC temperatura pannello solare

27. Sonda condensazione circuito n° 1 (temperatura NTC / pressione 4÷20 mA / raziom etrico 0÷

5Volt)

28. Sonda condensazione circuito n° 2 (temperatura NTC / pressione 4÷20 mA / raziometrico 0÷

5Volt)

29. Sonda pressione evaporazione circuito n° 1

30. Sonda pressione evaporazione circuito n° 2

31. Sonda pressione uscita ausiliaria n° 1

32. Sonda pressione uscita ausiliaria n° 2

33. Sonda pressione 4..20 mA set point dinamico

34. Sonda pressione olio compressore 1 o circuito 1

35. Sonda pressione olio compressore 2 o circuito 2

Se l’ingresso deve essere util izzato come ingresso digitale, la configurazione sarà da o1 a C73

ed assumerà

i l significato visibile in par. 2.3 “CONFIGURAZIONE INGRESSI DIGITALI ID1 – ID18”

Page 24: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 24/72

15.7 Configurazione Ingressi Digitali Id1 – Id18

Parametri :

CF36 = Configurazione ID1…CF53 = Configurazione ID18

0. Disabilitato

1. ON / OFF remoto

2. Chiller / pompa di calore remoto

3. Flussostato / termica ventilatore di mandata

4. Flussostato lato caldo

5. Allarme antigelo circuito n° 1

6. Allarme antigelo circuito n° 2

7. Pressostato alta pressione circuito n° 1

8. Pressostato alta pressione circuito n° 2

9. Pressostato bassa pressione circuito n° 1

10. Pressostato bassa pressione circuito n° 2

11. Alta pressione compressore n° 1

12. Alta pressione compressore n° 2

13. Alta pressione compressore n° 3

14. Alta pressione compressore n° 4

15. Alta pressione compressore n° 5

16. Alta pressione compressore n° 6

17. Termica compressore n° 1

18. Termica compressore n° 2

19. Termica compressore n° 3

20. Termica compressore n° 4

21. Termica compressore n° 5

22. Termica compressore n° 6

23. Termica ventilatore di condensazione circuito n° 1

24. Termica ventilatore di condensazione circuito n° 2

25. Termica ventilatore di condensazione comune

26. Termica pompa acqua n° 1 evaporatore

27. Termica pompa acqua supporto evaporatore

28. Termica pompa acqua n° 1 condensatore

29. Termica pompa acqua supporto condensatore

30. Richiesta recupero circuito 1

31. Richiesta recupero circuito 2

32. Inizio/Fine sbrinamento circuito n° 1

33. Inizio/Fine sbrinamento circuito n° 2

34. Energy Saving

35. Pressostato / galleggiante olio compressore n° 1

36. Pressostato / galleggiante olio compressore n° 2

37. Pressostato / galleggiante olio compressore n° 3

38. Pressostato / galleggiante olio compressore n° 4

39. Pressostato / galleggiante olio compressore n° 5

40. Pressostato / galleggiante olio compressore n° 6

41. Pressostato di pump down circuito n° 1

42. Pressostato di pump down circuito n° 2

43. Ingresso digitale allarme generico blocco unità n° 1

44. Ingresso digitale allarme generico segnalazione / blocco unità n° 2

Page 25: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 25/72

45. Ingresso digitale funzionamento in automatico abilitazione RTC (fascia oraria) / manuale

(tastiera)

46. Ingresso digitale funzionamento con solo ventilazione di mandata

47. Ingresso digitale richiesta termoregolazione

48. Ingresso digitale richiesta chil ler

49. Ingresso digitale richiesta pompa di calore

50. Ingresso digitale richiesta gradino potenza n° 2

51. Ingresso digitale richiesta gradino potenza n° 3

52. Ingresso digitale richiesta gradino potenza n° 4

53. Ingresso digitale richiesta gradino potenza n° 5

54. Ingresso digitale richiesta gradino potenza n° 6

55. Ingresso digitale richiesta gradino potenza n° 7

56. Ingresso digitale richiesta gradino potenza n° 8

57. Ingresso digitale richiesta gradino potenza n° 9

58. Ingresso digitale richiesta gradino potenza n° 10

59. Ingresso digitale richiesta gradino potenza n° 11

60. Ingresso digitale richiesta gradino potenza n° 12

61. Ingresso digitale richiesta gradino potenza n° 13

62. Ingresso digitale richiesta gradino potenza n° 14

63. Ingresso digitale richiesta gradino potenza n° 15

64. Ingresso digitale richiesta gradino potenza n° 16

65. Flussostato pompa acqua calda sanitaria

66. Flussostato pompa acqua pannello solare

67. Abilitazione sola produzione acqua calda sanitaria

68. Termica resistenze acqua sanitaria

69. Termica pompa acqua sanitaria

70. Abilitazione secondo set point acqua sanitaria

71. Allarme sequenza fasi

72. Priorità al funzionamento dell’acqua sanitaria

73. Flussostato pompa FC

15.8 Configurazione Uscite Digitali RL1- RL14

Parametri:

CF54= Configurazione RL1…CF67= Configurazione RL14

0. Disabilitato

1. Allarme

2. Pompa acqua evaporatore / ventilatore di mandata

3. Pompa acqua supporto evaporatore

4. Resistenze antigelo / appoggio / boiler circuito n° 1

5. Resistenze antigelo / appoggio / boiler circuito n° 2

6. Pompa acqua condensatore recupero

7. Pompa acqua supporto condensatore recupero

8. Valvola di inversione chiller / pompa di calore circuito n° 1

9. Valvola di inversione chiller / pompa di calore circuito n° 2

10. 1° gradino ON/OFF ventilazione di condensazione circuito n° 1

11. 2° gradino ON/OFF ventilazione di condensazione circuito n° 1

12. 3° gradino ON/OFF ventilazione di condensazione circuito n° 1

Page 26: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 26/72

13. 4° gradino ON/OFF ventilazione di condensazione circuito n° 1

14. 1° gradino ON/OFF ventilazione di condensazione circuito n° 2

15. 2° gradino ON/OFF ventilazione di condensazione circuito n° 2

16. 3° gradino ON/OFF ventilazione di condensazione circuito n° 2

17. 4° gradino ON/OFF ventilazione di condensazione circuito n° 2

18. Solenoide pump-down circuito n° 1

19. Solenoide pump-down circuito n° 2

20. NON UTILIZZATO

21. NON UTILIZZATO

22. Valvola ON/OFF Free cooling

23. Uscita ausiliaria n° 1

24. Uscita ausiliaria n° 2

25. Valvola intermittente compressore a vite compressore n° 1

26. Valvola intermittente compressore a vite compressore n° 2

27. Valvola solenoide iniezione liquido compressore n° 1

28. Valvola solenoide iniezione liquido compressore n° 2

29. Valvola ON/OFF 1 per la produzione di acqua calda sanitaria

30. Valvola ON/OFF 2 per la produzione di acqua calda sanitaria

31. Resistenze (primo gradino) per la produzione di acqua calda sanitaria

32. Resistenze (secondo gradino) per la produzione di acqua calda sanitaria

33. Resistenze (terzo gradino) per la produzione di acqua calda sanitaria

34. Pompa pannelli solari

35. Valvola ON/OFF abilitazione/esclusione serpentina solare

36. Pompa acqua calda sanitaria

37. Scambiatore ibrido 1 circuito 1

38. Scambiatore ibrido 2 circuito 1

39. Scambiatore ibrido 1 circuito 2

40. Scambiatore ibrido 2 circuito 2

41. Stato macchina sbrinamento

42. Stato macchina raffrescamento (chil ler)

43. Stato macchina riscaldamento (pompa di calore)

44. Stato macchina acqua sanitaria

45. Stato macchina Std-By

46. Valvola solenoide lato acqua circuito 1

47. Valvola solenoide lato acqua circuito 2

48. Avviamento diretto : relè compressore 1

Avviamento PW: relè avvolgimento n° 1 compressore 1

Avviamento stella / triangolo: relè linea n° 1 compressore 1

49. Avviamento PW: relè avvolgimento n° 2 compressore 1

Avviamento stella / triangolo: relè linea n° 2 compressore 1

50. Relè centro stella avviamento stella / triangolo compressore 1

51. Parzializzazione n° 1 compressore 1

52. Parzializzazione n° 2 compressore 1

53. Parzializzazione n° 3 compressore 1

54. Valvola by pass gas in partenza compressore n° 1

55. Avviamento diretto: relè compressore 2

Avviamento PW: relè avvolgimento n° 1 compressore 2

Avviamento stella / triangolo: relè linea n° 1 compressore 2

Page 27: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 27/72

56. Avviamento PW: relè avvolgimento n° 2 compressore 2

Avviamento stella / triangolo: relè linea n° 2 compressore 2

57. Relè centro stella avviamento stella / triangolo compressore 2

58. Parzializzazione n° 1 compressore 2

59. Parzializzazione n° 2 compressore 2

60. Parzializzazione n° 3 compressore 2

61. Valvola by pass gas in partenza compressore n° 2

62. Avviamento diretto: relè compressore 3

Avviamento PW: relè avvolgimento n° 1 compressore 3

Avviamento stella / triangolo: relè linea n° 1 compressore 3

63. Avviamento PW: relè avvolgimento n° 2 compressore 3

Avviamento stella / triangolo: relè linea n° 1 compressore 3

64. Relè centro stella avviamento stella / triangolo compressore 3

65. Parzializzazione n° 1 compressore 3

66. Parzializzazione n° 2 compressore 3

67. Parzializzazione n° 3 compressore 3

68. Valvola by pass gas in partenza compressore n° 3

69. Avviamento diretto: relè compressore 4

Avviamento PW: relè avvolgimento n° 1 compressore 4

Avviamento stella / triangolo: relè linea n° 1 compressore 4

70. Avviamento PW: relè avvolgimento n° 2 compressore 4

Avviamento stella / triangolo: relè linea n° 1 compressore 4

71. Relè centro stella avviamento stella / triangolo compressore 4

72. Parzializzazione n° 1 compressore 4

73. Parzializzazione n° 2 compressore 4

74. Parzializzazione n° 3 compressore 4

75. Valvola by pass gas in partenza compressore n° 4

76. Compressore 5

77. Compressore 6

15.9 Configurazione N° 2 Uscite Proporzionali Controllo Condensazione

Uscite proporzionali per i l controllo della velocità delle ventole di cond ensazione con segnale

configurabile

Parametri:

CF68 = Configurazione controllo condensazione circuito n° 1

CF69 = Configurazione controllo condensazione circuito n° 2

0= 0 ÷ 10 Volt (comando modulo taglio di fase esterno per ventole monofase / trifase o in verter)

1= 4÷20mA (comando modulo taglio di fase esterno per ventole monofase/ trifase o inverter)

2= PWM (comando modulo taglio di fase esterno per ventole monofase)

15.10 Configurazione N° 4 Uscite Proporzionali 0 ÷ 10 Volt

Parametri:

CF70 = Configurazione uscita proporzionale n° 1

CF71 = Configurazione uscita proporzionale n° 2

CF72 = Configurazione uscita proporzionale n° 3

CF73 = Configurazione uscita proporzionale n° 4

0 Uscita disabilitata

1 pompa evaporatore con funzionamento modulante

Page 28: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 28/72

2 uscita modulante Free cooling

3 NON UTILIZZATO

4 uscita ausiliaria 0÷10V n° 1

5 uscita ausiliaria 0÷10V n° 2

6 uscita modulante compressore 1 circuito n° 1

7 uscita modulante compressore 1 circuito n° 2

Uscita ON / OFF pilotaggio relè, consente di configurare un uscita proporzionale con le stesse

caratteristiche di una uscita digitale. La visualizzazione a display andrà da o1 a c47, come per

le uscite digitali.

16. Parametri Forma Tabellare

SELEZIONE SOTTO - MENU

Label Significato

ALL Visualizza tutti i parametri

ST Visualizza solo i parametri di termoregolazione

CF Visualizza solo i parametri di configurazione

SD Visualizza solo i parametri Del set point dinamico

ES Visualizza solo i parametri energy saving e accensione / spegnimento automatico con

fasce orarie

Cr Visualizza solo i parametri centrale compressori

CO Visualizza solo i parametri compressori

US Visualizza solo i parametri uscita ausiliaria

FA Visualizza solo i parametri ventilazione

Ar Visualizza solo i parametri resistenza antigelo

DF Visualizza solo i parametri sbrinamento

FS Visualizza solo i parametri acqua calda sanitaria

AL Visualizza solo i parametri allarmi

Termoregolatore

Parametr

o

Descrizione min max udm Risoluzion

e

ST 1 Set point chiller

Permette di impostare il set point di lav oro in

f unzionamento chiller

ST02 ST03 °C/°F dec/int

Page 29: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 29/72

ST 2 Set minimo chiller

Stabilisce il limite minimo utilizzabile per l’impostazione

del set point di lav oro in chiller

-50.0

-58 ST01

°C

°F

Dec

int

ST 3 Set massimo chiller

Stabilisce il limite massimo utilizzabile per l’impostazione

del set point di lav oro in chiller

ST01 70.0

158

°C

°F

Dec

int

ST 4 Set point pompa di calore

Permette di impostare il set point di lav oro in

f unzionamento p.d.c.

ST05 ST06 °C/°F dec/int

ST 5 Set minimo pompa di calore

Stabilisce il limite minimo utilizzabile per l’impostazione

del set point di lav oro in pompa di calore

-50.0

-58 ST04

°C

°F

Dec

int

ST 6 Set massimo pompa di calore

Stabilisce il limite massimo utilizzabile per l’impostazione

del set point di lav oro in pompa di calore

ST04 70.0

158

°C

°F

Dec

int

ST 7 Banda di interv ento gradini di regolazione in chiller 0.1

0

25.0

45

°C

°F

Dec

int

ST 8 Banda di interv ento gradini di regolazione in pompa di

calore

0.1

0

25.0

45

°C

°F

Dec

int

ST 9 Def inisce la sonda per la termoregolazione della macchina

in f unzionamento chiller

0= Sonda temperatura NTC ingresso ev aporatore

1= Sonda temperatura NTC uscita ev aporatore n° 1

2= Sonda temperatura NTC uscita ev aporatore n° 2

3= Sonda temperatura NTC uscita comune ev aporatore

4= sonda temperatura terminale remoto n° 1

5= sonda temperatura terminale remoto n° 2

0

5

ST 10 Def inisce la sonda per la termoregolazione della macchina

in f unzionamento pompa di calore

0= Sonda temperatura NTC ingresso ev aporatore

1= Sonda temperatura NTC uscita ev aporatore n° 1

2= Sonda temperatura NTC uscita ev aporatore n° 2

3= Sonda temperatura NTC uscita comune ev aporatore

4= sonda temperatura terminale remoto n° 1

5= sonda temperatura terminale remoto n° 2

6= sonda temperatura NTC ingresso comune acqua

condensatore

7=sonda temperatura NTC ingresso acqua condensatore

circuito n° 1

8=sonda temperatura NTC ingresso acqua condensatore

circuito n° 2

9=sonda temperatura NTC uscita acqua condensatore

circuito n° 1

10=sonda temperatura NTC uscita acqua condensatore

circuito n° 2

11=sonda temperatura NTC uscita comune acqua

condensatore

ATTENZIONE

Se si necessita della stessa termoregolazione sia in

f unzionamento chiller che in f unzionamento pompa di

calore impostare la stesso v alore nei parametri ST09 e

ST10

0 11

Page 30: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 30/72

ST 11 Def inisce il tipo di termoregolazione

0= Proporzionale

1= Zona neutra

0 1

Visualizzazione display

parametr

o

Descrizione min max udm Risoluzion

e

dP 1 Def ault v isualizzazione display superiore 0 17

dP 2 Def ault v isualizzazione display inf eriore 0 21

Visualizzazione forzata display

dP 3 Def ault v isualizzazione f orzata display superiore /

inf eriore

0= v isualizzazione conf igurabile

1= display superiore IN ev aporatore / display inf eriore

OUT ev aporatore

2= display superiore IN condensatore / display inf eriore

OUT condensatore

3= display superiore temperatura / pressione di

condensazione / display inf eriore pressione di

ev aporazione

0 3

Visualizzazione forzata display terminali remoti

dP 4 Def ault v isualizzazione display superiore dei terminale

remoto n° 1

0= la v isualizzazione dipende dal v alore dei parametri

dP01 – dP02 – dP03

1= il display superiore v isualizza la temperatura misurata

dalla sonda NTC a bordo del terminale remoto n° 1

0 1

dP 5 Def ault v isualizzazione display superiore dei terminale

remoto n° 2

0= la v isualizzazione dipende dal v alore dei parametri

dP01 – dP02 – dP03

1= il display superiore v isualizza la temperatura misurata

dalla sonda NTC a bordo del terminale remoto n° 2

0 1

dP 6 Non utilizzato 0 35

dP 7 Non utilizzato 0 35

dP 8 Non utilizzato 0 35

dP 9 Non utilizzato 0 35

configurazione

parametr

o

Descrizione min max udm Risoluzion

e

Unità

CF 1 Def inisce il tipo di unità da controllare

0= Macchina aria / aria

1= Macchina aria / acqua

2= Macchina acqua / acqua

0 2

CF 2 Selezione f unzionamento unità

1= solo chiller

2= solo pompa di calore

3= chiller con pompa di calore

1 3

Page 31: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 31/72

CF 3 Unità motocondensante

0= no

1= si

0 1

Compressori

CF 4 Numero compressori circuito n° 1

1÷6 1 6

CF 5 Numero compressori presenti nel circuito n° 2

0= 0

1= 1

2= 2

3= 3

0 3

CF 6 Numero parzializzazioni per compressore

0= nessuna

1= 1

2= 2

3= 3

0 3

Ingressi analogici

CF 7 Funzionamento in temperatura o pressione da ingresso

analogico

0 = Funzionamento in temperatura / pressione NTC –

4÷20 mA :

La temperatura di condensazione v iene controllata tramite

sonda NTC mentre per il controllo della pressione di

ev aporazione dei circuito n° 1e n° 2 e della sonda di

pressione conf igurata come uscita ausiliaria n° 1 e n° 2 si

dev e utilizzare un trasduttore con ingresso 4÷20mA

1 = Funzionamento in pressione con ingresso 4÷20

mA:

Per il controllo delle pressioni di condensazione o di

ev aporazione si dev e utilizzare una trasduttore con

ingresso 4÷20mA

2 = Funzionamento in temperatura / pressione NTC –

0÷5V:

La temperatura di condensazione v iene controllata tramite

sonda NTC mentre per il controllo della pressione di

ev aporazione dei circuito n° 1e n° 2 e della sonda di

pressione conf igurata come uscita ausiliaria n° 1 e n° 2 si

dev e utilizzare un trasduttore raziometrico con ingresso

0÷5V

3 = Funzionamento in pressione con ingresso 0÷5V:

Per il controllo delle pressioni di condensazione o di

ev aporazione si dev e utilizzare un trasduttore raziometrico

con ingresso 0÷5V

0 3

CF 8 Conf igurazione PB1

Se conf igurato come ingresso digitale

0

o 1

28

c73

CF 9 Conf igurazione PB2

Se conf igurato come ingresso digitale

0

o 1

28

c73

CF 10 Conf igurazione PB3

Se conf igurato come ingresso digitale

0

o 1

35

c73

CF 11 Conf igurazione PB4

Se conf igurato come ingresso digitale

0

o 1

35

c73

Page 32: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 32/72

CF 12 Conf igurazione PB5

Se conf igurato come ingresso digitale

0

o 1

35

c73

CF 13 Conf igurazione PB6

Se conf igurato come ingresso digitale

0

o 1

35

c73

CF 14 Conf igurazione PB7

Se conf igurato come ingresso digitale

0

o 1

28

c73

CF 15 Conf igurazione PB8

Se conf igurato come ingresso digitale

0

o 1

28

c73

CF 16 Conf igurazione PB9

Se conf igurato come ingresso digitale

0

o 1

28

c73

CF 17 Conf igurazione PB10

Se conf igurato come ingresso digitale

0

o 1

28

c73

Offset sonde

CF 18 Of f set PB1 -12.0

-21

12.0

21

°C

°F

Dec

int

CF 19 Of f set PB2 -12.0

-21

12.0

21

°C

°F

Dec

int

CF 20 Of f set PB3 -12.0

-21

-5.0

-72

12.0

21

5.0

72

°C

°F

bar

psi

Dec

int

dec

int

CF 21 Of f set PB4 -12.0

-21

-5.0

-72

12.0

21

5.0

72

°C

°F

bar

psi

Dec

int

dec

int

CF 22 Of f set PB5

-12.0

-21

-5.0

-72

12.0

21

5.0

72

°C

°F

bar

psi

Dec

int

dec

int

CF 23 Of f set PB6 -12.0

-21

-5.0

-72

12.0

21

5.0

72

°C

°F

bar

psi

Dec

int

dec

int

CF 24 Of f set PB7 -12.0

-21

12.0

21

°C

°F

Dec

int

CF 25 Of f set PB8 -12.0

-21

12.0

21

°C

°F

Dec

int

CF 26 Of f set PB9 -12.0

-21

12.0

21

°C

°F

Dec

int

CF 27 Of f set PB10 -12.0

-21

12.0

21

°C

°F

Dec

int

CF 28 Valore di pressione a 4mA – 0.5 V trasduttore PB3 -1.0

-14

50.0

725

Bar

psi

Dec

int

CF 29 Valore di pressione a 20mA – 5 V trasduttore PB3 -1.0

-14

50.0

725

Bar

psi

Dec

int

CF 30 Valore di pressione a 4mA – 0.5 V trasduttore PB4 -1.0

-14

50.0

725

Bar

psi

Dec

int

CF 31 Valore di pressione a 20mA – 5 V trasduttore PB4 -1.0

-14

50.0

725

Bar

psi

Dec

int

CF 32 Valore di pressione a 4mA – 0.5 V trasduttore PB5 -1.0

-14

50.0

725

Bar

psi

Dec

int

Page 33: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 33/72

CF 33 Valore di pressione a 20mA – 5 V trasduttore PB5 -1.0

-14

50.0

725

Bar

psi

Dec

int

CF 34 Valore di pressione a 4mA – 0.5 V trasduttore PB6 -1.0

-14

50.0

725

Bar

psi

Dec

int

CF 35 Valore di pressione a 20mA – 5 V trasduttore PB6 -1.0

-14

50.0

725

Bar

psi

Dec

int

Ingressi digitali

CF 36 Conf igurazione ID1 0 -o1 c73

CF 37 Conf igurazione ID2 0 -o1 c73

CF 38 Conf igurazione ID3 0 -o1 c73

CF 39 Conf igurazione ID4 0 -o1 c73

CF 40 Conf igurazione ID5 0 -o1 c73

CF 41 Conf igurazione ID6 0 -o1 c73

CF 42 Conf igurazione ID7 0 -o1 c73

CF 43 Conf igurazione ID8 0 -o1 c73

CF 44 Conf igurazione ID9 0 -o1 c73

CF 45 Conf igurazione ID10 0 -o1 c73

CF 46 Conf igurazione ID11 0 -o1 c73

CF 47 Conf igurazione ID12 0 -o1 c73

CF 48 Conf igurazione ID13 0 -o1 c73

CF 49 Conf igurazione ID14 0 -o1 c73

CF 50 Conf igurazione ID15 0 -o1 c73

CF 51 Conf igurazione ID16 0 -o1 c73

CF 52 Conf igurazione ID17 0 -o1 c73

CF 53 Conf igurazione ID18 0 -o1 c73

Uscite relè

CF 54 Conf igurazione RL1 0 -o1 c77

CF 55 Conf igurazione RL2 0 -o1 c77

CF 56 Conf igurazione RL3 0 -o1 c77

CF 57 Conf igurazione RL4 0 -o1 c77

CF 58 Conf igurazione RL5 0 -o1 c77

CF 59 Conf igurazione RL6 0 -o1 c77

CF 60 Conf igurazione RL7 0 -o1 c77

CF 61 Conf igurazione RL8 0 -o1 c77

CF 62 Conf igurazione RL9 0 -o1 c77

CF 63 Conf igurazione RL10 0 -o1 c77

CF 64 Conf igurazione RL11 0 -o1 c77

CF 65 Conf igurazione RL12 0 -o1 c77

CF 66 Conf igurazione RL13 0 -o1 c77

CF 67 Conf igurazione RL14 0 -o1 c77

Uscite proporzionali condensazione

CF 68 Segnale uscita proporzionale controllo condensazione

circuito n° 1

0= 0 – 10V

1= 4 ÷ 20Ma

2= segnale PWM comando scheda triac esterno per

v entole monof ase

0 2

Page 34: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 34/72

CF 69 Segnale uscita proporzionale controllo condensazione

circuito n° 2

0= 0 – 10V

1= 4 ÷ 20Ma

2= segnale PWM comando scheda triac esterno per

v entole monof ase

0 2

Uscite modulanti

CF 70 Uscita proporzionale n° 1 (out3)

0= uscita disabilitata

1= pompa ev aporatore con f unzionamento modulante

2= uscita modulante per Free cooling

3= non utilizzato

4= uscita ausiliaria 0÷10V n° 1

5= uscita ausiliaria 0÷10V n° 2

6= uscita modulante compressore 1 circuito n° 1

7= uscita modulante compressore 1 circuito n° 2

Uscita ON / OFF pilotaggio relè

0

o 1

7

c47

CF 71 Uscita proporzionale n° 2 (out4)

0= uscita disabilitata

1= pompa ev aporatore con f unzionamento modulante

2= uscita modulante per Free cooling

3= non utilizzato

4= uscita ausiliaria 0÷10V n° 1

5= uscita ausiliaria 0÷10V n° 2

6= uscita modulante compressore 1 circuito n° 1

7= uscita modulante compressore 1 circuito n° 2

Uscita ON / OFF pilotaggio relè

0

o 1

7

c47

CF 72 Uscita proporzionale n° 3 (out5)

0= uscita disabilitata

1= pompa ev aporatore con f unzionamento modulante

2= uscita modulante per Free cooling

3= non utilizzato

4= uscita ausiliaria 0÷10V n° 1

5= uscita ausiliaria 0÷10V n° 2

6= uscita modulante compressore 1 circuito n° 1

7= uscita modulante compressore 1 circuito n° 2

Uscita ON / OFF pilotaggio relè

0

o 1

7

c47

CF 73 Uscita proporzionale n° 4 (out6)

0= uscita disabilitata

1= pompa ev aporatore con f unzionamento modulante

2= uscita modulante per Free cooling

3= non utilizzato

4= uscita ausiliaria 0÷10V n° 1

5= uscita ausiliaria 0÷10V n° 2

6= uscita modulante compressore 1 circuito n° 1

7= uscita modulante compressore 1 circuito n° 2

Uscita ON / OFF pilotaggio relè

0

o 1

7

c47

Terminale remoto

CF 74 Conf igurazione terminale remoto n° 1

0= assente

1= sonda NTC a bordo

2= senza sonda NTC a bordo

0 2

Page 35: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 35/72

CF 75 Conf igurazione terminale remoto n° 2

0= assente

1= sonda NTC a bordo

2= senza sonda NTC a bordo

0 2

CF 76 Of f set sonda NTC terminale remoto n° 1 -12.0

-21

12.0

21

°C

°F

Dec

int

CF 77 Of f set sonda NTC terminale remoto n° 2 -12.0

-21

12.0

21

°C

°F

Dec

int

Logica di funzionamento

CF 78 Logica di f unzionamento

0= chiller / pdc

1= chiller / pdc

0 1

Selezione funzionamento chiller / pompa di calore

CF 79 Selezione f unzionamento chiller / pompa di calore

0= da tastiera

1= da ingresso digitale

2= da ingresso analogico

0 2

Change over automatico

CF 80 Set change ov er automatico f unzionamento chiller /

pompa di calore se il Par. CF80=2

-50.0

-58

70.0

158

°C

°F

Dec

int

CF 81 Dif f erenziale change ov er automatico f unzionamento

chiller / pompa di calore se il Par. CF80=2

0.1

0

25.0

45

°C

°F

Dec

int

Selezione unità di misura

CF 82 Selezione °C o °F

0= °C / °BAR

1= °F / °psi

0 1

Selezione frequenza rete

CF 83 Selezione f requenza rete

0= 50 Hz

1= 60 Hz

2= Alimentazione in continua (da utilizzare se non sono

usate le uscite PWM per il controllo delle v entole di

condensazione)

0 2

Indirizzo seriale

CF 84 Indirizzo seriale 1 247

CF 85 Release f irmware

CF 86 Mappa parametri Eeprom

Termoregolazione compressori con potenza frigorifera differente

CF 87 Peso compressore n° 1 0 100%

CF 88 Peso compressore n° 2 0 100%

CF 89 Peso compressore n° 3 0 100%

CF 90 Peso compressore n° 4 0 100%

CF 91 Peso compressore n° 5 0 100%

CF 92 Peso compressore n° 6 0 100%

CF 93 N° massimo spunti compressori dopo 15 minuti di ON

0 = f unzione disabilitata 0 15

Abilitazione funzionamento compressori

Page 36: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 36/72

CF 94 Selezione abilitazione f unzionamento compressori

0 = chiller e pompa di calore

1 = solo chiller

2 = solo pompa di calore

0 2

Abilitazione unità con scambiatori ibridi

CF 95 Abilitazione unità con scambiatori ibridi (1=abilitata) 0 1

Abilitazione buzzer

CF 96 Abilitazione buzzer (0=disabilitato, 1=abilitato) 0 1

Modalità chiller

CF 97 Modalità chiller (1=con compressori, 2=solo FC, 3 =con

compressori e FC) 1 3

Set point dinamico

Parametri Descrizione min max udm Risoluzion

e

Sd 1

Incremento max set point dinamico in chiller

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 2

Incremento max set point dinamico in p.d.c.

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 3

Set temp. Aria esterna set point dinamico in chiller

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 4

Set temp. Aria esterna set point dinamico in p.d.c.

-30

-58

70.0

158

°C

°F

Dec

int

Sd 5 Dif f erenziale temp. Aria esterna set point dinamico in

chiller

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 6 Dif f erenziale temp. Aria esterna set point dinamico in

p.d.c.

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 7 Incremento max set point dinamico in chiller ausiliaria

analogica 1

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 8 Incremento max set point dinamico in p.d.c. ausiliaria

analogica 1

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 9 Set temp. Aria esterna set point dinamico in chiller

ausiliaria analogica 1

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 10 Set temp. Aria esterna set point dinamico in p.d.c.

ausiliaria analogica 1

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 11 Dif f erenziale temp. Aria esterna set point dinamico in

chiller ausiliaria analogica 1

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 12 Dif f erenziale temp. Aria esterna set point dinamico in

p.d.c. ausiliaria analogica 1

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 13 Incremento max set point dinamico in chiller ausiliaria

analogica 2

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 14 Incremento max set point dinamico in p.d.c. ausiliaria

analogica 2

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 15 Set temp. Aria esterna set point dinamico in chiller

ausiliaria analogica 2

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 16 Set temp. Aria esterna set point dinamico in p.d.c.

ausiliaria analogica 2

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 17 Dif f erenziale temp. Aria esterna set point dinamico in

chiller ausiliaria analogica 2

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 18 Dif f erenziale temp. Aria esterna set point dinamico in

p.d.c. ausiliaria analogica 2

-50.0

-54

30.0

54

°C

°F

Dec

int

Page 37: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 37/72

Sd 19 Incremento max set point dinamico in chiller relè ausiliario

1

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 20 Incremento max set point dinamico in p.d.c. relè

ausiliario 1

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 21 Set temp. Aria esterna set point dinamico in chiller relè

ausiliario 1

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 22 Set temp. Aria esterna set point dinamico in p.d.c. relè

ausiliario 1

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 23 Dif f erenziale temp. Aria esterna set point dinamico in

chiller relè ausiliario 1

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 24 Dif f erenziale temp. Aria esterna set point dinamico in

p.d.c. relè ausiliario 1

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 25 Incremento max set point dinamico in chiller relè ausiliario

2

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 26 Incremento max set point dinamico in p.d.c. relè

ausiliario 2

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 27 Set temp. Aria esterna set point dinamico in chiller relè

ausiliario 2

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 28 Set temp. Aria esterna set point dinamico in p.d.c. relè

ausiliario 2

-50.0

-58

70.0

158

°C

°F

Dec

int

Sd 29 Dif f erenziale temp. Aria esterna set point dinamico in

chiller relè ausiliario 2

-50.0

-54

30.0

54

°C

°F

Dec

int

Sd 30 Dif f erenziale temp. Aria esterna set point dinamico in

p.d.c. relè ausiliario 2

-50.0

-54

30.0

54

°C

°F

Dec

int

Energy saving

Parametri Descrizione min max udm Risoluzion

e

ES 1 Inizio f ascia di f unzionamento n ° 1 (0÷24) 0 24.00 Hr 10 Min

ES 2 Fine f ascia di f unzionamento n ° 1 (0÷24) 0 24.00 Hr 10 Min

ES 3 Inizio f ascia di f unzionamento n ° 2 (0÷24) 0 24.00 Hr 10 Min

ES 4 Fine f ascia di f unzionamento n ° 2 (0÷24) 0 24.00 Hr 10 Min

ES 5 Inizio f ascia di f unzionamento n ° 3 (0÷24) 0 24.00 Hr 10 Min

ES 6 Fine f ascia di f unzionamento n ° 3 (0÷24) 0 24.00 Hr 10 Min

ES 7 Lunedì f unzionamento con f ascia oraria in energy sav ing

Lunedì f unzionamento con accensione / spegnimento

automatico

0 - 0 7 - 7

ES 8 Martedì f unzionamento con f ascia oraria in energy sav ing

Martedì f unzionamento con accensione / spegnimento

automatico

0 - 0 7 - 7

ES 9 Mercoledì f unzionamento con f ascia oraria in energy

sav ing

Mercoledì f unzionamento con accensione / spegnimento

automatico

0 - 0 7 - 7

ES 10 Giov edì f unzionamento con f ascia oraria in energy

sav ing

Giov edì f unzionamento con accensione / spegnimento

automatico

0 - 0 7 - 7

ES 11 Venerdì f unzionamento con f ascia oraria in energy sav ing

Venerdì f unzionamento con accensione / spegnimento

automatico

0 - 0 7 - 7

Page 38: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 38/72

ES 12 Sabato f unzionamento con f ascia oraria in energy sav ing

Sabato f unzionamento con accensione / spegnimento

automatico

0 - 0 7 - 7

ES 13 Domenica f unzionamento con f ascia oraria in energy

sav ing

Domenica f unzionamento con accensione / spegnimento

automatico

0 - 0 7 - 7

ES 14 Incremento set energy sav ing in f unzionamento chiller -50.0

-54

30.0

54

°C

°F

Dec

int

ES 15 Dif f erenziale energy sav ing in f unzionamento chiller 0.1

0

25.0

45

°C

°F

Dec

int

ES 16 Incremento set energy sav ing in f unzionamento pompa di

calore

-50.0

-54

30.0

54

°C

°F

Dec

int

ES 17 Dif f erenziale energy sav ing in f unzionamento pompa di

calore

0.1

0

25.0

45

°C

°F

Dec

int

ES 18 Tempo massimo di f unzionamento unità in OFF da RTC

se v iene f orzata in ON da tasto 1 250

10

min min

ES 19 Start of the Time band 1 Sanitary water (0÷24) 0 24.00 Hr 10 Min

ES 20 End of the Time band 1 Sanitary water (0÷24) 0 24.00 Hr 10 Min

ES 21 Start of the Time band 2 Sanitary water (0÷24) 0 24.00 Hr 10 Min

ES 22 End of the Time band 2 Sanitary water (0÷24) 0 24.00 Hr 10 Min

ES 23 Start of the Time band 3 Sanitary water (0÷24) 0 24.00 Hr 10 Min

ES 24 End of the Time band 3 Sanitary water (0÷24) 0 24.00 Hr 10 Min

ES 25 Monday : energy sav ing activ ated

Lunedì f unzionamento con f ascia oraria acqua sanitaria 0 7

ES 26 Martedì f unzionamento con f ascia oraria acqua sanitaria 0 7

ES 27 Mercoledì f unzionamento con f ascia oraria acqua

sanitaria 0 7

ES 28 Giov edì f unzionamento con f ascia oraria acqua sanitaria 0 7

ES 29 Venerdì f unzionamento con f ascia oraria acqua sanitaria 0 7

ES 30 Sabato f unzionamento con f ascia oraria acqua sanitaria 0 7

ES 31 Domenica f unzionamento con f ascia oraria acqua

sanitaria 0 7

ES 32 Incremento set acqua sanitaria energy sav ing -30.0

-54

30.0

54

°C

°F

Dec

int

ES 33 Dif f erenziale acqua sanitaria in f ascia oraria/ingresso

digitale

0.1

0

25.0

45

°C

°F

Dec

int

Centrale compressori

Parametri Descrizione min max udm Risoluzion

e

Cr1 Def inisce il tipo di termoregolazione centrale f rigorif era

0 = disabilitata

1= regolazione con sonda def inita da ST09

2 = abilitato con sonda di aspirazione (ev aporazione)

(motocondensanti e pompa di calore v engono

automaticamente disabilitati)

0 2

Cr2 Set point compressori sonda di aspirazione (ev aporazione)

Permette di impostare il set point di lav oro della sonda di

aspirazione

Cr03 Cr04 Bar

Psi

Dec

int

Page 39: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 39/72

Cr3 Set minimo compressori sonda di aspirazione

(ev aporazione)

Stabilisce il limite minimo utilizzabile per l’impostazione

del set point di lav oro della sonda di aspirazione

0 Cr03 Bar

Psi

Dec

int

Cr4 Set massimo compressori sonda di aspirazione

(ev aporazione)

Stabilisce il limite massimo utilizzabile per l’impostazione

del set point di lav oro della sonda di aspirazione

Cr03 50

725

Bar

Psi

Dec

int

Cr5 Banda di interv ento gradini di regolazione della sonda di

aspirazione

0.1

1

14.0

203

Bar

Psi

Dec

int

Cr6 Incremento set energy sav ing in f unzionamento centrale 0.0

0

50.0

725

Bar

psi

Dec

int

Cr7 Dif f erenziale energy sav ing in f unzionamento centrale 0.1

1

14.0

203

Bar

Psi

Dec

int

Cr8 N° compressori da inserire in caso di guasto sonda

preposta al loro controllo

0 ÷ 6

0 6

Cr9 N° di gradini di v entilazione di condensazione di circuito

da inserire in caso di guasto sonda preposta al loro

controllo

0 ÷ 4

0 4

Compressore

Parametri Descrizione min max udm Risoluzio

ne

CO 1 Tempo minimo accensione compressore

Determina il tempo durante il quale il compressore dev e

rimanere attivo dopo la sua accensione, anche se ne

cessa la richiesta.

0 250 10

sec 10 sec

CO 2 Tempo minimo spegnimento compressore

Determina il tempo durante il quale il compressore dev e

rimanere disattivo, anche se ne è richiesta la

riaccensione. Durante questa f ase il led relativ o al

compressore lampeggia.

0 250 10

sec 10 sec

CO 3 Ritardo accensione tra 2 compressori / gradini

Con due compressori stabilisce il ritardo di accensione tra

i due, per ridurre gli assorbimenti agli spunti. Durante

questa f ase il led relativ o al compressore lampeggia.

(solo per il compressore )

Con unità con un compressore parzializzato. Determina il

tempo di accensione della solenoide di parzializzazione per

una partenza alla minima capacità (v edi av v iamento

compressori)

1 250 Sec

CO 4 Ritardo spegnimento tra 2 compressori / gradini

Stabilisce il ritardo di spegnimento tra i due compressori

due gradini di parzializzazione

0 250 Sec

Page 40: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 40/72

CO 5 Ritardo all’accensione compressori da power ON

Accensione intesa come alimentazione f isica del controllo

.

Ritarda l’attiv azione di tutte le uscite per distribuire gli

assorbimenti di rete e proteggere il/i compressore/i da

ripetute accensioni in caso di f requenti mancanze di

alimentazione di rete

0 250 10

Sec 10 sec

parzializzazioni

CO 6 Funzionamento parzializzazioni (v edi f unzionamento

parzializzazioni)

0= inserimento ON/OFF a gradini

1= inserimento continuo a gradini azione diretta

2= inserimento continuo a gradini azione inv ersa

3= Inserimento a gradini continuo diretto globale

0 3

CO 7 Abilitazione al f unzionamento della potenza minima del

compressore / gestione partenza a v uoto

0 = Abilita la potenza minima solo alla partenza del

compressore (partenza con la minima capacità / partenza

a v uoto v alv ola in OFF a compressore spento )

1= Abilita la potenza minima alla partenza del

compressore e in termoregolazione (partenza con la

minima capacità / partenza a v uoto v alv ola in OFF a

compressore spento )

2 = Compressori a v ite abilita la potenza minima solo alla

partenza del compressore (partenza con la minima

capacità / partenza a v uoto v alv ola in ON a compressore

spento )

3= Compressori a v ite abilita la potenza minima alla

partenza del compressore e in termoregolazione (partenza

con la minima capacità / partenza a v uoto v alv ola in ON

a compressore spento )

0 3

CO 8 Tempo di ON relè comando v alv ola intermittente comp. a

v ite se il v alore del parametro è 0 la f unzione v iene

disabilitata

0 250 Sec

CO 9 Tempo di OFF relè comando v alv ola intermittente comp.

a v ite 0 250 Sec

Avviamento compressore

CO 10 Av v iamento compressore

0= diretto ( v edi av v iamento compressori )

1= part - winding ( v edi av v iamento compressori )

2= stella triangolo ( v edi av v iamento compressori )

0 2

CO 11 Se CO10= 1 tempo av v iamento part - winding Consente

di v ariare l’aggancio dei due div ersi relè che alimentano i

due av v olgimenti del motore.

Se CO10= 2 Tempo av v iamento stella triangolo consente

di v ariare il tempo di f unzionamento contemporaneo del

relè della linea n° 1 e del relè che chiude il collegamento

di centro stella. (v edi par. av v iamento part – winding /

stella triangolo)

0 100 Dec.

di Sec 0.1 sec

Page 41: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 41/72

CO 12 Se CO10= 2 tempo av v iamento stella triangolo Consente

di v ariare il tempo dallo sgancio del relè centro stella

all’aggancio del relè della linea n° 2. (v edi par.

av v iamento stella triangolo)

0 50 Dec.

di Sec 0.1 sec

CO 13 Tempo di accensione con v alv ola by pass gas / v alv ola

partenza a v uoto compressore (v edi f unzionamento

parzializzazioni)

0 250 sec

Rotazione – bilanciamento – termoregolazione compressori

CO 14 Rotazione compressori (v edi rotazioni compressori)

0 = Sequenza f issa

1 = Rotazione abilitata con termoregolazione compressori

in base alle ore di f unzionamento

2 = Rotazione abilitata con termoregolazione compressori

in base agli av v iamenti ora (spunti)

0 2

CO 15 Bilanciamento dei circuiti (v edi bilanciamento dei circuiti)

0= saturazione dei circuiti

1= bilanciamento dei circuiti

0 1

Pompa acqua evaporatore

CO 16 Modo operativ o pompa ev aporatore / v entilatore di

mandata (v edi f unzionamento pompa acqua ev aporatore)

0= Assente la pompa e il v entilatore di mandata non

v engono gestiti.

1= Funzionamento Continuo: l’attiv azione della pompa

acqua / v entilatore di mandata si ha all’accensione della

macchina (selezione f unzionamento chiller / p.d.c.).

2= Funzionamento su chiamata del compressore:

l’accensione e lo spegnimento della pompa e del

v entilatore di mandata sono legati all’accensione e allo

spegnimento del compressore.

0 2

CO 17 Ritardo ON compressore dalla partenza pompa /

v entilatore di mandata (v edi f unzionamento pompa acqua

ev aporatore / condensatore)

1 250 sec 10sec

CO 18 Ritardo OFF pompa acqua ev aporatore / v entilatore di

mandata dallo spegnimento compressore. Questo tempo

v iene rispettato anche quando si posiziona l’unità in stand

by (v edi f unzionamento pompa acqua ev aporatore)

0 250 Min

CO 19 N° ore per rotazione f orzata pompe ev aporatore (v edi

f unzionamento gruppo di pompaggio ev aporatore) 0 999 10Hr 10Hr

CO 20 Tempo f unzionamento pompe contemporaneo dopo

rotazione f orzata pompe (v edi f unzionamento gruppo di

pompaggio ev aporatore)

0 250 Sec

Pompa acqua condensatore

CO 21 Modo operativ o pompa condensatore (v edi f unzionamento

pompa acqua condensatore)

0= Assente la pompa non v iene gestita.

1= Funzionamento Continuo l’accensione e lo

spegnimento della pompa sono legati all’accensione e allo

spegnimento dell’unità.

2= Funzionamento su chiamata del compressore

l’accensione e lo spegnimento della pompa sono legati

all’accensione e allo spegnimento del compressore.

0 2

Page 42: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 42/72

CO 22 Libero

CO 23 Ritardo OFF pompa condensatore dallo spegnimento

compressore. Questo tempo v iene rispettato anche

quando si posiziona l’unità in stand by (v edi

f unzionamento pompa acqua condensatore)

0 250 Min

CO 24 N° ore per rotazione f orzata pompe condensatore

(v edi f unzionamento gruppo di pompaggio ev aporatore) 0 999 10Hr 10Hr

CO 25 Tempo f unzionamento pompe contemporaneo dopo

rotazione f orzata pompe condensatore

(v edi f unzionamento gruppo di pompaggio ev aporatore)

0 250 Sec

Manutenzione carichi

CO 26 Set Contaore compressore 1 (v edi cap. f unzione richiesta

manutenzione ) 0 999 10 Hr 10 Hr

CO 27 Set Contaore compressore 2 (v edi cap. f unzione richiesta

manutenzione ) 0 999 10 Hr 10 Hr

CO 28 Set Contaore compressore 3 (v edi cap. f unzione richiesta

manutenzione ) 0 999 10 Hr 10 Hr

CO 29 Set Contaore compressore 4 (v edi cap. f unzione richiesta

manutenzione ) 0 999 10 Hr 10 Hr

CO 30 Set Contaore compressore 5 (v edi cap. f unzione richiesta

manutenzione ) 0 999 10 Hr 10 Hr

CO 31 Set Contaore compressore 6 (v edi cap. f unzione richiesta

manutenzione ) 0 999 10 Hr 10 Hr

CO 32 Set Contaore pompa / v entilatore di mandata (v edi cap.

f unzione richiesta manutenzione ) 0 999 10 Hr 10 Hr

CO 33 Set Contaore pompa ev aporatore n° 2 (v edi cap. f unzione

richiesta manutenzione ) 0 999 10 Hr 10 Hr

CO 34 Set Contaore pompa condensatore (v edi cap. f unzione

richiesta manutenzione ) 0 999 10 Hr 10 Hr

CO 35 Set Contaore pompa condensatore n° 2 (v edi cap.

f unzione richiesta manutenzione ) 0 999 10 Hr 10 Hr

Pump down

CO 36 Funzionamento pump down (v edi cap f unzionamento

accensione spegnimento con pump down)

0= f unzione disabilitata

1= spegnimento con pump down senza pump – down in

av v iamento

2= spegnimento con pump down con pump – down in

av v iamento

3= spegnimento con pump down solo in f unzionamento

chiller senza pump – down in av v iamento

4= spegnimento con pump down solo in f unzionamento

chiller con pump – down in av v iamento

0 4

CO 37 Set pressione di pump down (v edi cap f unzionamento

accensione spegnimento con pump down)

0.0

0

50.0

725

Bar

psi

Dec

int

CO 38 Dif f erenziale pressione di pump down (v edi cap

f unzionamento accensione spegnimento con pump down)

0.1

1

12.0

174

Bar

psi

Dec

int

CO 39 Tempo massimo di permanenza in Pump – down in

av v iamento e in f ermata (v edi cap f unzionamento

accensione spegnimento con pump down)

0 250 Sec

Page 43: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 43/72

Unloading evaporatore

CO 40 Set point f unzione di unloading compressori in

f unzionamento chiller da alta temperatura ingresso acqua

ev aporatore (v edi f unzione di unloading)

-50.0

-58

70.0

158

°C

°F

Dec

int

CO 41 Dif f erenziale relè unloading. Comp. da alta temperatura

ingresso acqua ev aporatore (v edi f unzione di unloading)

0.1

0

25.0

45

°C

°F

Dec

int

CO 42 Tempo di ritardo inserimento f unzione di unloading Comp.

da alta temperatura ingresso acqua ev aporatore (v edi

f unzione di unloading)

1 250 10

Sec 10 sec

CO 43 Tempo MAX di permanenza in f unzionamento unloading

Comp. da alta temperatura ingresso acqua ev aporatore 0 250 Min

Unloading condensatore chiller – pompa di calore

CO 44 Set point unloading Comp. temperatura / pressione in

f unzionamento chiller

(v edi f unzione di unloading)

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

CO 45 Dif f erenziale unloading. Comp. temperatura / pressione in

f unzionamento chiller / (v edi f unzione di unloading)

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

CO 46 Set point unloading Comp. temperatura / pressione in

f unzionamento p.d.c. (v edi f unzione di unloading)

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

CO 47 Dif f erenziale unloading Comp. temperatura / pressione in

f unzionamento p.d.c. (v edi f unzione di unloading)

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

CO 48 Tempo MAX di permanenza in f unzionamento unloading

compressori da temperatura / pressione 1 250 Min

CO 49 Scelta dei gradini per circuito da inserire in f unzionamento

unloading

1= n° 1 gradino

2= n° 2 gradini

3= n° 3 gradini

1 3

CO 50 Tempo minimo di f unzionamento in ON gradino di

parzializzazione dopo l’ingresso in unloading (solo per

compressore con parzializzazioni)

0 250 Sec

Funzione iniezione liquido compressori

CO 51 Set point attiv azione v alv ola solenoide iniezione liquido 0

32

150

302

°C

°F

Dec / int

int

CO 52 Dif f erenziale disattiv azione v alv ola solenoide iniezione

liquido

0.1

0

25.0

45

°C

°F

Dec

int

Gestione risorse in funzionamento zona neutra

CO 53 Tempo massimo permanenza in zona neutra senza

inserimento risorse con almeno una risorsa inserita 0 250 Min 10 Min

CO 54 Tempo massimo permanenza in zona neutra senza la

rotazione delle risorse 0 999 Hr 1Hr

Unloading bassa temperatura acqua evaporatore

Page 44: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 44/72

CO 55 Set point unloading compressore da bassa temperatura

acqua ev aporatore

-50.0

-58

70.0

158

°C

°F

Dec

int

CO 56 Dif f erenziale unloading compressore da bassa

temperatura acqua ev aporatore

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

CO 57 Tempo MAX di permanenza in f unzionamento unloading

compressori da bassa temperatura acqua ev aporatore 0 250 Min

Pump down a tempo

CO 58 Tempo di pump down in av v iamento

CO58 = 0 f unzione disabilitata

CO58 ≠ 0 f unzione abilitata per il tempo impostato

0 250 Sec

CO 59 Tempo di pump down in f ermata

CO59 = 0 f unzione disabilitata

CO59 ≠ 0 f unzione abilitata per il tempo impostato

0 250 Sec

Compressore con controllo modulante

CO 60 Tempo di f unzionamento compressore alla massima

v elocità da richiesta termoregolazione

0 = f unzione disabilitata

0 250 sec

CO 61 Minimo v alore per l’uscita analogica compressore a

inv erter 0÷10V allo spunto 0 100 %

CO 62 Interv allo di implemento potenza del compressore a

inv erter allo spunto 0 250 sec

CO 63 Determina la minima percentuale di f unzionamento

continuativ o del compressore a inv erter sotto la quale

parte il conteggio del tempo CO64

0 = f unzione disabilitata

0 100 %

CO 64 Tempo MAX di f unzionamento continuativ o del

compressore a inv erter con percentuale di f unzionamento

sotto CO63

0 = f unzione disabilitata

0 250 Min 10 Min

CO 65 Tempo di f unzionamento del compressore a inv erter

f orzato alla massima v elocità 0 250 sec sec

CO 66 Tempo massimo di f unzionamento continuativ o

compressore a inv erter trascorso il quale v iene spento il

compressore modulante e in base alla rotazione v iene

f orzato l’inserimento di un altro compressore

0 = f unzione disabilitata

0 999 Hr 1Hr

CO 67 Minimo v alore per l’uscita analogica compressore a

inv erter 0÷10V n° 5 circuito n° 1 1

CO6

8 %

CO 68 Massimo v alore per l’uscita analogica compressore a

inv erter 0÷10V n° 5 circuito n° 1 CO67 100 %

CO 69 Minimo v alore per l’uscita analogica compressore a

inv erter 0÷10V n° 6 circuito n° 2 1

CO7

0 %

CO 70 Massimo v alore per l’uscita analogica compressore a

inv erter 0÷10V n° 6 circuito n° 2 CO69 100 %

CO 71 Interv allo di implemento potenza a regime 1 250 sec

Funzione rotazione forzata compressore

CO 72 Tempo massimo di f unzionamento continuativ o singolo

compressore nel circuito

0 250 Min

Page 45: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 45/72

Manutenzione carichi

CO 73 Set contaore pompa H2O saniitaria 0 999 10 Hr 10 Hr

CO 74 Set contaore pompa pannelli solari 0 999 10 Hr 10 Hr

CO 75 Tempo di inv ersione v alv ola su f ermo compressore 0 250 sec

Parzializzazione macchina

CO 76 Limitazione del numero di gradini in f unzionamento Chiller 1 10

CO 77 Limitazione del numero di gradini in f unzionamento Pompa

di Calore

1 10

CO 78 Limitazione del numero di gradini in f unzionamento Acqua

Sanitaria

1 10

CO 79 Massima % di uscita compressore a Inv erter in

f unzionamento Chiller

1 100 %

CO 80 Massima % di uscita compressore a Inv erter in

f unzionamento Pompa di Calore

1 100 %

CO 81 Massima % di uscita compressore a Inv erter in

f unzionamento Acqua Sanitaria

1 100 %

CO 82 Temperatura aria esterna per riduzione v elocità

compressore in pompa di calore

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

CO 83 Isteresi temperatura aria esterna per riduzione v elocità

compressore in pompa di calore

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

CO 84 Velocità massima compressore ad inv erter per

supersamento soglia temperatura aria esterna 0 100 %

CO 85 Tempo di disattiv azione pompa acqua ev aporatore con

macchina a set point 0 250

10

min

CO 86 Tempo di disattiv azione pompa acqua ev aporatore con

macchina spenta (std-by o OFF) 0 250

10

Ore

CO 87 Tempo di attiv azione pompa acqua ev aporatore 0 250 Sec 10sec

CO 88 Tempo di disattiv azione pompa acqua condensatore con

macchina a set point 0 250

10

min

CO 89 Tempo di disattiv azione pompa acqua condensatore con

macchina spenta (std-by o OFF) 0 250

10

Ore

CO 90 Tempo di attiv azione pompa acqua condensatore 0 250 Sec 10sec

CO 91 Tempo minimo tra due accensioni dello stesso

compressore 0 250 sec

CO 92 Anticipo attiv azione v alv ola solenoide lato acqua rispetto

ad accensione compressore 0 250 sec

CO 93 Ritardo disattiv azione v alv ola solenoide lato acqua

rispetto a spegnimento compressore 0 250 sec

CO 94 % output of the inv erter compressor in def rost 0 100 %

CO 95 Set ore pompa FC 0 999 10 Hr 10 Hr

CO 96 Valore uscita analogica del compressore a inv erter in

unloading 0 100 %

Menù relè ausiliari

Parametri Descrizione min max udm Risoluzion

e

Relè ausiliario n° 1

Page 46: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 46/72

US 1 Funzionamento relè ausiliario n° 1 (v edi f unzione e graf ici

relè ausiliario)

0= non abilitato

1= sempre abilitato azione diretta

2= abilitato azione diretta solo con unità in ON

3= sempre abilitato azione inv ersa

4= abilitato azione inv ersa solo con unità in ON

0 4

US 2 Conf igurazione ingresso analogico per la gestione del relè

ausiliario circuito n° 1 consente di scegliere la sonda da

PB1 a PB10 per la gestione della f unzione

1 10

US 3

Set minimo estiv o uscita relè ausiliario 1

-50.0

-58

0.0

0

US5

°C

°F

Bar

Psi

Dec

int

Dec

int

US 4

Set massimo estiv o uscita relè ausiliario 1

US5

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 5

Set point estiv o uscita relè ausiliario 1

US3 US4

°C

°F

Bar

Psi

Dec

int

Dec

int

US 6

Set minimo inv ernale uscita relè ausiliario 1

-50.0

-58

0.0

0

US8

°C

°F

Bar

Psi

Dec

int

Dec

int

US 7

Set massimo inv ernale uscita relè ausiliario 1

US8

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 8

Set point inv ernale uscita relè ausiliario 1

US6 US7

°C

°F

Bar

Psi

Dec

int

Dec

int

US 9

Dif f erenziale estiv o relè ausiliario 1

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 10

Dif f erenziale inv ernale relè ausiliario 1

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

Relè ausiliario n° 2

US 11 Funzionamento relè ausiliario n° 2 (v edi f unzione e graf ici

relè ausiliario)

0= non abilitato

1= sempre abilitato azione diretta

2= abilitato azione diretta solo con unità in ON

3= sempre abilitato azione inv ersa

4= abilitato azione inv ersa solo con unità in ON

0 4

Page 47: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 47/72

US 12 Conf igurazione ingresso analogico per la gestione del relè

ausiliario circuito n° 2 consente di scegliere la sonda da

PB1 a PB10 per la gestione della f unzione

1 10

US 13

Set minimo estiv o uscita relè ausiliario 2

-50.0

-58

0.0

0

US15

°C

°F

Bar

Psi

Dec

int

Dec

int

US 14

Set massimo estiv o uscita relè ausiliario 2

US1

5

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 15

Set point estiv o uscita relè ausiliario 2

US1

3 US14

°C

°F

Bar

Psi

Dec

int

Dec

int

US 16

Set minimo inv ernale uscita relè ausiliario 2

-50.0

-58

0.0

0

US18

°C

°F

Bar

Psi

Dec

int

Dec

int

US 17

Set massimo inv ernale uscita relè ausiliario 2

US1

8

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 18

Set point inv ernale uscita relè ausiliario 2

US1

6 US17

°C

°F

Bar

Psi

Dec

int

Dec

int

US 19

Dif f erenziale estiv o relè ausiliario 2

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 20

Dif f erenziale inv ernale relè ausiliario 2

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 21 Tempo massimo attiv azione relè ausiliari 0 250 min

Uscita proporzionale 0÷10V ausiliaria n° 1

US 22 Funzionamento uscita proporzionale ausiliaria n° 1

0= non abilitata

1= sempre abilitata azione diretta

2= abilitata azione diretta solo con unità in ON

3= sempre abilitata azione inv ersa

4= abilitata azione inv ersa solo con unità in ON

0 4

US 23 Conf igurazione ingresso analogico per la gestione

dell’uscita ausiliaria n° 1 consente di scegliere la sonda da

PB1 a PB10 per la gestione della f unzione

1 10

US 24

Set minimo estiv o uscita analogica ausiliaria 1

-50.0

-58

0.0

0

US26

°C

°F

Bar

Psi

Dec

int

Dec

int

Page 48: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 48/72

US 25

Set massimo estiv o uscita analogica ausiliaria 1

US2

6

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 26

Set estiv o uscita analogica ausiliaria 1

US2

4 US25

°C

°F

Bar

Psi

Dec

int

Dec

int

US 27

Set minimo inv ernale uscita analogica ausiliaria 1

-50.0

-58

0.0

0

US29

°C

°F

Bar

Psi

Dec

int

Dec

int

US 28

Set massimo inv ernale uscita analogica ausiliaria 1

US2

9

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 29

Set inv ernale uscita analogica ausiliaria 1

US2

7 US28

°C

°F

Bar

Psi

Dec

int

Dec

int

US 30

Dif f erenziale estiv o uscita analogica ausiliaria 1

0.0

0

0.0

0

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 31

Dif f erenziale inv ernale uscita analogica ausiliaria 1

0.0

0

0.0

0

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 32 Valore minimo uscita analogica ausiliaria 1 0 US33 %

US 33

Valore massimo uscita analogica ausiliaria 1

US3

2 100 %

Uscita proporzionale 0÷10V ausiliaria n° 2

US 34 Funzionamento uscita proporzionale ausiliaria n° 2 (v edi

f unzione e graf ici uscite ausiliarie)

0= non abilitata

1= sempre abilitata azione diretta

2= abilitata azione diretta solo con unità in ON

3= sempre abilitata azione inv ersa

4= abilitata azione inv ersa solo con unità in ON

0 4

US 35 Conf igurazione ingresso analogico per la gestione

dell’uscita ausiliaria n° 2 consente di scegliere la sonda da

PB1 a PB10 per la gestione della f unzione

1 10

US 36

Set minimo estiv o uscita analogica ausiliaria 2

-50.0

-58

0.0

0

US38

°C

°F

Bar

Psi

Dec

int

Dec

int

US 37

Set massimo estiv o uscita analogica ausiliaria 2

US3

8

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

Page 49: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 49/72

US 38

Set estiv o uscita analogica ausiliaria 2

US3

6 US37

°C

°F

Bar

Psi

Dec

int

Dec

int

US 39

Set minimo inv ernale uscita analogica ausiliaria 2

-50.0

-58

0.0

0

US41

°C

°F

Bar

Psi

Dec

int

Dec

int

US 40

Set massimo inv ernale uscita analogica ausiliaria 2

US4

1

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 41

Set inv ernale uscita analogica ausiliaria 2

US3

9 US40

°C

°F

Bar

Psi

Dec

int

Dec

int

US 42

Dif f erenziale estiv o uscita analogica ausiliaria 2

0.1

0

0.1

0

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 43

Dif f erenziale inv ernale uscita analogica ausiliaria 2

0.1

0

0.1

0

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 44 Valore minimo uscita analogica ausiliaria 2 0 US45 %

US 45

Valore massimo uscita analogica ausiliaria 2

US4

4 100 %

Valore minimo uscita modulante

US 46 Forzatura a 0 dell’uscita analogica al di sotto del v alore

minimo 0 1

Pompa evaporatore modulante

US 47 Selezione sonda 1 per f unzionamento pompa modulante in

chiller 0 10

US 48 Selezione sonda 2 per f unzionamento pompa modulante in

chiller 0 10

US 49

Set point per massima v elocità pompa modulante in

chiller

30.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 50

Banda proporzionale regolazione pompa modulante in

chiller

0.0

0

0.0

0

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 51 Minima v elocità pompa modulante in chiller 0 100 %

US 52 Massima v elocità pompa modulante in chiller 0 100 %

US 53 Selezione sonda 1 per f unzionamento pompa modulante in

Pompa di calore 0 10

US 54 Selezione sonda 2 per f unzionamento pompa modulante in

Pompa di calore 0 10

Page 50: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 50/72

US 55

Set point per massima v elocità pompa modulante in

Pompa di calore

30.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

US 56

Banda proporzionale regolazione pompa modulante in

Pompa di calore

0.0

0

0.0

0

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

US 57 Minima v elocità pompa modulante in Pompa di calore 0 100 %

US 58 Massima v elocità pompa modulante in Pompa di calore 0 100 %

US 59 Velocità pompa modulante durante il f ree cooling 0 100 %

US 60 Velocità pompa modulante a compressore spento 0 100 %

Abilitazione uscite ausiliarie

US 61 Abilitazione uscita relè ausiliario 1

1= solo chiller

2= solo pompa di calore

3= chiller e pompa di calore

1 3

US 62 Abilitazione uscita relè ausiliario 2

1= solo chiller

2= solo pompa di calore

3= chiller e pompa di calore

1 3

US 63 Abilitazione uscita analogica ausiliaria 1

1= solo chiller

2= solo pompa di calore

3= chiller e pompa di calore

1 3

US 64 Abilitazione uscita analogica ausiliaria 2

1= solo chiller

2= solo pompa di calore

3= chiller e pompa di calore

1 3

Ventilazione di condensazione

Parametri Descrizione min max udm Risoluzion

e

FA 1 Regolazione v entole

0= assente

1=sempre accese

2= inserimento ON/OFF a gradini

3= inserimento ON/OFF continuo a gradini

4= regolatore proporzionale di v elocità

0 4

FA 2 Modo f unzionamento v entole

0= dipendenti dal compressore

1= indipendenti dal compressore

0 1

FA 3 Tempo di spunto v entole MAX v elocità dopo ON (TRIAC).

Ad ogni partenza, il v entilatore, indipendentemente dalla

temperatura / pressione di condensazione , v iene

alimentato alla massima tensione per il tempo FA03,

scaduto il quale il v entilatore prosegue alla v elocità

impostata dal regolatore.

0 250 Sec

FA 4 Sf asamento v entole 0 8

Micro

Sec 250s

Page 51: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 51/72

FA 5 Ventilazione condensazione unica o separata

0= unica

1= separata

0 1

FA 6 Pre v entilazione in chiller prima di ON compressore

Permette di impostare un tempo di accensione delle

v entole alla massima v elocità in chiller prima

dell’accensione del compressore, al f ine di anticipare

l’aumento improv v iso di temperatura / pressione di

condensazione (che l’accensione del compressore

comporta) e migliorarne la regolazione ( solo se FA01 = 4

)

0 250 Sec

Funzionamento in chiller

FA 7 Minima v elocità di f unzionamento delle v entole in chiller

Permette di impostare un v alore minimo della regolazione

proporzionale delle v entole in chiller. Viene espressa in

percentuale, da 0 a 100% della massima tensione

consentita.

30 100 %

FA 8 Massima v elocità di f unzionamento delle v entole in chiller

Permette di impostare un v alore massimo della

regolazione proporzionale delle v entole in chiller. Viene

espressa in percentuale, da 0 a 100% della massima

tensione consentita.

30 100 %

FA 9 Regolazione proporzionale

Set temperatura / pressione minima v elocità v entole in

chiller permette di impostare il v alore di temperatura /

pressione di condensazione in f unzionamento chiller a

cui corrisponde la minima v elocità del v entilatore.

Regolazione a gradini

SET 1°GRADINO Permette di impostare il v alore di

temperatura / pressione di condensazione in

f unzionamento chiller a cui corrisponde il f unzionamento

in ON dell’uscita relè conf igurata come 1° gradino di

v elocità v entilazione di condensazione.

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 10 Regolazione proporzionale

Set temperatura / pressione massima v elocità v entole in

chiller permette di impostare il v alore di temperatura /

pressione di condensazione in f unzionamento chiller a

cui corrisponde la massima v elocità del v entilatore.

Regolazione a gradini

SET 2°GRADINO Permette di impostare il v alore di

temperatura / pressione di condensazione in

f unzionamento chiller a cui corrisponde il f unzionamento

in ON dell’uscita relè conf igurata come 2° gradino di

v elocità v entilazione di condensazione.

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

Page 52: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 52/72

FA 11 Regolazione proporzionale

Banda proporzionale regolazione v entilatori in chiller

Permette di impostare un dif f erenziale di temperatura /

pressione a cui corrisponde una v ariazione dal minimo al

massimo della v elocità dei v entilatori.

Regolazione a gradini

Con il Par. FA01 = 2 / 3 div enta il dif f erenziale sul gradino

stesso del circuito n° 1 in f unzionamento chiller (v edi

graf ico regolazione v entole).

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 12 Regolazione proporzionale

Dif f erenziale CUT- OFF in chiller Permette di impostare

un dif f erenziale di temperatura / pressione in chiller per lo

spegnimento del v entilatore.

Regolazione a gradini

Con il Par. FA01 = 2 / 3 div enta il dif f erenziale sul gradino

stesso del circuito n° 2 in f unzionamento chiller (v edi

graf ico regolazione v entole).

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 13 Ov er ride CUT- OFF in chiller Permette di impostare un

dif f erenziale di temperatura / pressione in chiller in cui il

v entilatore rimane alla minima v elocità.

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 14 Tempo ritardo CUT - OFF Permette di impostare un

tempo di ritardo dell’attiv azione della f unzione CUT – OFF

alla partenza delle v entole.

Se alla partenza del compressore il regolatore

proporzionale richiede lo spegnimento del v entilatore (cut -

of f ) e FA140 per il tempo impostato il v entilatore v errà

f orzato alla minima v elocità. Se FA14=0 la f unzione non è

abilitata.

0 250 Sec

FA 15 Velocità night f unction in chiller Permette di impostare un

v alore massimo della regolazione proporzionale delle

v entole in chiller. Viene espressa in percentuale, da 0 a

100% della massima tensione consentita.

0 100 %

Funzionamento in pompa di calore

FA 16 Minima v elocità v entole in pompa di calore. Permette di

impostare un v alore minimo della regolazione

proporzionale delle v entole in p.d.c. Viene espressa in

percentuale, da 0 a 100% della massima tensione

consentita.

0 100 %

FA 17 Massima v elocità v entole in pompa di calore. Permette di

impostare un v alore massimo della regolazione

proporzionale delle v entole in p.d.c. Viene espressa in

percentuale, da 0 a 100% della massima tensione

consentita.

0 100 %

Page 53: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 53/72

FA 18 Regolazione proporzionale

Set temperatura / pressione massima v elocità v entole in

p.d.c. Permette di impostare il v alore di temperatura /

pressione di condensazione in f unzionamento p.d.c a cui

corrisponde la minima v elocità del v entilatore.

Regolazione a gradini

SET 1°GRADINO Permette di impostare il v alore di

temperatura / pressione di condensazione in

f unzionamento pompa di calore a cui corrisponde il

f unzionamento in ON dell’uscita relè conf igurata come 1°

gradino di v elocità v entilazione di condensazione.

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 19 Regolazione proporzionale

Set temperatura / pressione minima v elocità v entole in

p.d.c. Permette di impostare il v alore di temperatura /

pressione di condensazione in f unzionamento p.d.c. a cui

corrisponde la massima v elocità del v entilatore.

Regolazione a gradini

SET 2°GRADINO Permette di impostare il v alore di

temperatura / pressione di condensazione in

f unzionamento pompa di calore a cui corrisponde il

f unzionamento in ON dell’uscita relè conf igurata come 2°

gradino di v elocità v entilazione di condensazione.

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 20 Regolazione proporzionale

Banda proporzionale regolazione v entilatori in pompa di

calore

Permette di impostare un dif f erenziale di temperatura /

pressione a cui corrisponde una v ariazione dal minimo al

massimo della v elocità dei v entilatori.

Regolazione a gradini

Con il Par. FA01 = 2 / 3 div enta il dif f erenziale sul gradino

stesso del circuito n° 1 in f unzionamento pompa di calore

(v edi graf ico regolazione v entole).

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 21 Regolazione proporzionale

Dif f erenziale CUT- OFF in pompa di calore permette di

impostare un dif f erenziale di temperatura / pressione in

chiller per lo spegnimento del v entilatore.

Regolazione a gradini

Con il Par. FA01 = 2 / 3 div enta il dif f erenziale sul gradino

stesso del circuito n° 2 in f unzionamento pompa di calore

(v edi graf ico regolazione v entole).

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 22 Ov er ride CUT- OFF in p.d.c. Permette di impostare un

dif f erenziale di temperatura / pressione in p.d.c. in cui il

v entilatore rimane alla minima v elocità.

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 23 Velocità night f unction in p.d.c. Permette di impostare un

v alore massimo della regolazione proporzionale delle

v entole in p.d.c. Viene espressa in percentuale, da 0 a

100% della massima tensione consentita.

0 100 %

Hot start

FA 24 Set point hot start -50.0

-58

70.0

158

°C

°F

Dec

int

Page 54: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 54/72

FA 25 Dif f erenziale hot start 0.1

0

25.0

45

°C

°F

Dec

int

3 / 4 Gradino di ventilazione di condensazione in chiller

FA 26 Regolazione a gradini

SET 3°GRADINO Permette di impostare il v alore di

temperatura / pressione di condensazione in

f unzionamento chiller a cui corrisponde il f unzionamento

in ON dell’uscita relè conf igurata come 3° gradino di

v elocità v entilazione di condensazione

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 27 Regolazione a gradini

SET 4°GRADINO Permette di impostare il v alore di

temperatura / pressione di condensazione in

f unzionamento chiller a cui corrisponde il f unzionamento

in ON dell’uscita relè conf igurata come 3° gradino di

v elocità v entilazione di condensazione

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

3 / 4 Gradino di ventilazione di condensazione in pompa di calore

FA 28 Regolazione a gradini

SET 3°GRADINO Permette di impostare il v alore di

temperatura / pressione di condensazione in

f unzionamento pompa di calore a cui corrisponde il

f unzionamento in ON dell’uscita relè conf igurata come 3°

gradino di v elocità v entilazione di condensazione

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

FA 29 Regolazione a gradini

SET 4°GRADINO Permette di impostare il v alore di

temperatura / pressione di condensazione in

f unzionamento pompa di calore a cui corrisponde il

f unzionamento in ON dell’usc ita relè conf igurata come 3°

gradino di v elocità v entilazione di condensazione

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

Preventilazione in Pompa di calore

FA 30 Pre v entilazione in Pompa di calore.

Permette di impostare un tempo di accensione delle

v entole alla massima v elocità in Pompa di calore prima

dell’accensione del compressore (solo se FA01 = 4 )

0 250 Sec Sec

FA 31 Postv entilazione in Pompa di calore.

Permette di mantenere la v entilazione attiv a per un certo

tempo dopo lo spegnimento del compressore

0 250 Sec 10Sec

FA 32 Temperatura aria esterna per postv entilazione in pompa di

calore

-50.0

-58

70.0

158

°C

°F

Dec

int

FA 33 Velocità v entole durante postv entilazione 0 100 %

Resistenze antigelo – appoggio - boiler

Parametri Descrizione min max udm Risoluzion

e

Ar 1 Set point resistenze antigelo / appoggio (unità aria/aria) in

f unzionamento chiller

Permette di impostare un v alore di temperatura al di sotto

del quale v engono attiv ate le resistenze di antigelo

-50.0

-58

70.0

158

°C

°F

Dec

int

Ar 2 banda di regolazione resistenze antigelo / appoggio in

chiller

0.1

0

25.0

45

°C

°F

Dec

Int

Page 55: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 55/72

Ar 3 Set point resistenze antigelo / appoggio (unità aria/aria) in

f unzionamento pompa di calore

Permette di impostare un v alore di temperatura al di sotto

del quale v engono attiv ate le resistenze di antigelo

-50.0

-58

70.0

158

°C

°F

Dec

int

Ar 4 Banda di regolazione resistenze antigelo / appoggio in

pompa di calore

0.1

0

25.0

45

°C

°F

Dec

int

Ar 5 Funzionamento resistenze antigelo / appoggio in

sbrinamento

0= accese solo da termoregolatore

1= accese da termoregolatore e durante il ciclo di

sbrinamento

0 1

Ar 6 Sonda di regolazione resistenze antigelo / appoggio in

chiller

0= disabilitata

1= regola su ingresso ev aporatore

2= regola su uscita ev aporatore 1 / 2

3= regola su uscita ev aporatore 1 / 2 e uscita comune

0 3

Ar 7 Sonda di regolazione resistenze antigelo / appoggio in

pompa di calore

0= disabilitata

1= regola su ingresso ev aporatore

2= regola su uscita ev aporatore 1 / 2

3= regola su uscita ev aporatore 1 / 2 e uscita comune

0 3

Ar 8 Sonda di regolazione resistenze antigelo condensatore

0= disabilitata

1= regola sonda ingresso acqua condensatore comune

2= regola sonda ingresso acqua condensatore comune e

ingresso condensatore 1 / 2

3= regola sonda uscita acqua condensatore 1 / 2

4= regola su uscita condensatore 1 / 2 e uscita comune

0 4

Ar 9 Determina il f unzionamento delle resistenze antigelo

pompa/e acqua ev aporatore / condensatore quando lo

strumento è in OFF remoto o STAND-BY

0=sempre spente in OFF remoto o STAND – BY

1=accese in OFF remoto o STAND – BY (accese in

f unzione della richiesta del termoregolatore)

0 1

Ar 10 Determina il f unzionamento delle resistenze antigelo

ev aporatore / condensatore in caso di guasto di una

sonda preposta al loro controllo

0 = Spente in caso di guasto sonda

1= Accese in caso di guasto sonda

0 1

Funzione boiler

Ar 11 Funzione boiler

0=disabilitata

1=abilitata con controllo in integrazione

2=abilitata con controllo in riscaldamento

0 2

Ar 12 Set point aria esterna attiv azione resistenze boiler -50.0

-58

70.0

158

°C

°F

Dec

int

Ar 13 Dif f erenziale aria esterna disattiv azione resistenze boiler 0.1

0

25.0

45

°C

°F

Dec

int

Ar 14 Tempo ritardo attiv azione resistenze boiler 0 250 Min

Page 56: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 56/72

Funzione boiler in chiller

Ar 15 Set point resistenze boiler in chiller -50.0

-58

70.0

158

°C

°F

Dec

int

Ar 16 Banda proporzionale resistenze boiler in chiller 0.1

0

25.0

45

°C

°F

Dec

int

Funzione boiler in pompa di calore

Ar 17 Set point resistenze boiler in pompa di calore -50.0

-58

70.0

158

°C

°F

Dec

int

Ar 18 Banda proporzionale resistenze boiler in f unzionamento

pompa di calore

0.1

0

25.0

45

°C

°F

Dec

int

Ar 19 Set point aria esterna disattiv azione compressori in

f unzionamento integrazione

-50.0

-58

70.0

158

°C

°F

Dec

int

Ar 20 Dif f erenziale aria esterna attiv azione compressori in

f unzionamento integrazione

0.1

0

25.0

45

°C

°F

Dec

int

Allarme antigelo

Ar21 Sonda di regolazione allarme antigelo in chiller

0= disabilitata

1= regola su ingresso ev aporatore

2= regola su uscita ev aporatore 1 / 2

3= regola su uscita ev aporatore 1 / 2 e uscita comune

4= regola su Temperatura aria esterna

0 4

Ar22 Sonda di regolazione allarme antigelo in pompa di calore

0= disabilitata

1= regola su ingresso ev aporatore

2= regola su uscita ev aporatore 1 / 2

3= regola su uscita ev aporatore 1 / 2 e uscita comune

4= regola su Temperatura aria esterna

0 4

Ar23 Sonda di regolazione allarme antigelo condensatore

0= disabilitata

1= regola sonda ingresso acqua condensatore comune

2= regola sonda ingresso acqua condensatore comune e

ingresso condensatore 1 / 2

3= regola sonda uscita acqua condensatore 1 / 2

4= regola su uscita condensatore 1 / 2 e uscita comune

0 4

Funzionamento pompa acqua evaporatore con allarme antigelo

Ar24 Determina il f unzionamento della pompa/e acqua

ev aporatore per antigelo quando lo strumento è in OFF o

Stand-by

0= sempre spente in OFF remoto o Stand-by

1= accese in OFF remoto o Stand-by (accese in f unzione

della richiesta del termoregolatore

0 1

Ar25 Sonda di regolazione f unzionamento pompa/e acqua

ev aporatore per antigelo

0= disabilitata

1= regola su ingresso ev aporatore

2= regola su uscita ev aporatore 1 / 2

3= regola su uscita ev aporatore 1 / 2 e uscita comune

4= regola su Temperatura aria esterna

0 4

Ar26 Set point attiv azione pompa acqua ev aporatore in

f unzionamento antigelo su sonda di termoregolazione

-50.0

-58

70.0

158

°C

°F

Dec

int

Page 57: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 57/72

Ar27 Dif f erenziale disattiv azione pompa acqua ev aporatore in

f unzionamento antigelo su sonda di termoregolazione

0.1

0

25.0

45

°C

°F

Dec

int

Sbrinamento

Parametri Descrizione min max udm Risoluzion

e

dF 1 Modalità di sbrinamento

0= sbrinamento disabilitato

1= temperatura / pressione

2= inizio dipende dal v alore del par. dF24 f ine per tempo

3= inizio dipende dal v alore del par. dF24 f ine per contatto

esterno

4= con v entilazione di condensazione

5= inizio per contatto esterno e f ine dipende dal v alore del

par. dF24

0 5

dF 2 Temperatura pressione inizio sbrinamento -50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

Int

dF 3 Temperatura pressione f ine sbrinamento -50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

Int

dF 4 Durata minima sbrinamento 0 250 Sec

dF 5 Durata massima sbrinamento 0 250 Min

dF 6 Tempo di ritardo tra lo sbrinamento di due circuiti 0 250 Min

dF 7 Tempo di attesa in OFF compressore prima dello

sbrinamento 0 250 Sec

dF 8 Tempo di attesa in OFF compressore dopo lo

sbrinamento 0 250 Sec

dF 9 Interv allo di sbrinamento nello stesso circuito 1 99 Min

dF 10 Set temperatura inizio ciclo sbrinamento combinato

circuito n° 1 dopo conteggio par. DF10

-50.0

-58

70.0

158

°C

°F

Dec

int

dF 11 Set temperatura f ine ciclo di sbrinamento combinato

circuito n° 1

-50.0

-58

70.0

158

°C

°F

Dec

int

dF 12 Set temperatura inizio ciclo sbrinamento combinato

circuito n° 2 dopo conteggio par. DF10

-50.0

-58

70.0

158

°C

°F

Dec

int

dF 13 Set temperatura f ine ciclo di sbrinamento combinato

circuito n° 2

-50.0

-58

70.0

158

°C

°F

Dec

int

dF 14 Forzatura in ON attiv a tutti i gradini in sbrinamento nel

circuito n° 1

0= disabilitata

1= abilitata

0 1

dF 15 Forzatura in ON attiv a tutti i gradini in sbrinamento nel

circuito n° 2

0= disabilitata

1= abilitata

0 1

dF 16 Tempo di ritardo accensione tra due compressori in

sbrinamento 0 250 Sec

Page 58: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 58/72

dF 17 Abilitazione ON v entilazione durante lo sbrinamento /

gocciolamento

0= disabilitata

1= abilitata solo sbrinamento

2= abilitata in sbrinamento / gocciolamento

0 2

dF 18 Set pressione / temperatura f orzatura ON v entilazione in

sbrinamento

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

Int

Sbrinamento forzato

dF 19 Tempo minimo di attesa prima di uno sbrinamento f orzato 0 250 sec

dF 20 Set temperatura / pressione sbrinamento f orzato -50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

dF 21 Dif f erenziale sbrinamento f orzato 0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

Modalità di sbrinamento

dF 22 Inizio del ciclo di sbrinamento in unità con due circuiti

0= indipendente

1= se entrambi hanno raggiunto la richiesta di inizio

sbrinamento

2= se almeno uno ha raggiunto la richiesta di inizio

sbrinamento

0 2

dF 23 Fine del ciclo di sbrinamento in unità con due circuiti e la

v entilazione di condensazione unica

0= indipendente

1= se entrambi hanno raggiunto la condizione di f ine

sbrinamento

2= se almeno uno ha raggiunto la condizione di f ine

sbrinamento

0 2

Inizio fine sbrinamento da ingresso analogico

dF 24 Sonda che determina inizio f ine sbrinamento

0= inizio e f ine con sonda di temperatura / pressione di

condensazione

1= inizio con sonda di pressione di ev aporazione f ine con

sonda di temperatura / pressione di condensazione

2= inizio con sonda di temperatura / pressione di

condensazione f ine con sonda di pressione ev aporazione

3= inizio e f ine per pressione di ev aporazione

0 3

Funzionamento ventilatore di mandata in sbrinamento

dF 25 Blocco v entilatore di mandata durante lo sbrinamento

0= Non abilitato

1= Abilitato

0 1

Sbrinamento con ventilatori di condensazione

dF 26 Set abilitazione sbrinamento con v entilatori di

condensazione

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

Page 59: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 59/72

Scambiatori ibridi

dF 27 Set temperatura/pressione estiv a di scambio 1

scambiatori ibridi

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

dF 28 Set temperatura/pressione estiv a di scambio 2

scambiatori ibridi

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

dF 29 Dif f erenziale estiv o temperatura di scambio 1 scambiatori

ibridi

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

dF 30 Dif f erenziale estiv o temperatura di scambio 2 scambiatori

ibridi

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

dF 31 Set temperatura/pressione inv ernale di scambio 1

scambiatori ibridi

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

dF 32 Set temperatura/pressione inv ernale di scambio 2

scambiatori ibridi

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

dF 33 Dif f erenziale temperatura/pressione inv ernale di scambio

1 scambiatori ibridi

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

dF 34 Dif f erenziale temperatura/pressione inv ernale di scambio

2 scambiatori ibridi

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

dF 35 Sonda per la gestione degli scambiatori ibridi

0= temperatura aria esterna

1= temperatura/pressione di condensazione

0 1

dF 36 Tempo di f orzatura batterie f razionate in modalità estiv a

alla partenza del compressore 0 250 sec

Set point dinamico in sbrinamento

dF 37

Incremento massimo set point dinamico in sbrinamento

-50.0

-54

30.0

54

°C

°F

Dec

int

dF 38 Set temperatura aria esterna set point dinamico in

sbrinamento

-50.0

-58

70.0

158

°C

°F

Dec

int

dF 39 Dif f erenziale temperatura aria esterna set point dinamico

in sbrinamento

-50.0

-54

30.0

54

°C

°F

Dec

int

Recupero

Parametri Descrizione min max ud

m

Risoluzio

ne

Page 60: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 60/72

rC 1 Funzionamento recupero

0 = disabilitato

1 = 2 circuiti idraulici separati

2 = 2 circuiti idraulici in parallelo

0 2

rC 2 Tempo di disattiv azione f orzata gradino 0 250 Sec

rC 3 Tempo di disattiv azione f orzata gradino dopo la rotazione

della v alv ola recupero 0 250 Sec

rC 4 Tempo minimo f unzionamento in recupero 0 250 Min

rC 5 Ritardo minimo tra f ine recupero e recupero successiv o 0 250 Min

rC 6 Set disabilitazione f unzione recupero -30.0

-22

0.0

0

70.0

158

50.0

725

°C

°F

Bar

Psi

Dec

int

Dec

int

rC 7 Dif f erenziale abilitazione f unzione recupero 0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

rC 8 Tempo massimo disabilitazione recupero da pressione /

temperatura di condensazione 0 250 Min

rC 9 Disabilitazione v entole in recupero 0 1

Acqua calda sanitaria

Parametri Descrizione min max udm Risoluzion

e

FS 1 Abilitazione produzione acqua calda sanitaria o acqua

calda sanitaria e f ree cooling

0 = disabilitato

1 = produzione acqua calda sanitaria con ritorno

comune,

riscaldamento/raf f reddamento

2 = produzione acqua calda sanitaria con ritorno

dedicato,

riscaldamento/raf f reddamento

0 2

FS 2 Priorità di f unzionamento

0 = riscaldamento / raf f reddamento

1 = acqua calda sanitaria

2 = acqua sanitaria da ingresso digitale

0 2

FS 3 Set point acqua calda sanitaria

Permette di impostare il set point di lav oro per la

produzione di acqua calda sanitaria

FS05 FS06 °C/°F dec/int

FS 4 Banda di interv ento gradini di regolazione acqua calda

sanitaria

0.1

0

25.0

45

°C

°F

Dec

int

FS 5 Minimo v alore setpoint acqua calda sanitaria

Stabilisce il limite minimo utilizzabile per l’impostazione

del set point acqua calda sanitaria

-50.0

-58 FS06

°C

°F

Dec

int

FS 6 Massimo v alore setpoint acqua calda sanitaria

Stabilisce il limite massimo utilizzabile per l’impostazione

del set point acqua calda sanitaria

FS05 70.0

158

°C

°F

Dec

int

FS 7 Attiv azione gradini per raggiungimento setpoint H20

sanitaria

0 = attiv a tutti i compressori

1 = attiv a compressori e resistenze

0 1

Page 61: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 61/72

FS 8 Inserimento resistenze in termoregolazione Acqua calda

sanitaria

0= no

1= si

0 1

FS 9 Tempo per inserimento tutti i compressori e resistenze in

produzione acqua calda sanitaria 0 250 Min

FS 10 Ritardo eccitazione uscite per la produzione di acqua

calda sanitaria 0 250 sec int

FS 11 Ritardo inv ersione ciclo durante la produzione di acqua

calda sanitaria 0 250 sec int

FS 12 Tipo di attiv azione Antilegionella

0 = a tempo

1= a f ascia oraria

2= giornaliera

0 2

FS 13 Ritardo di tempo tra due cicli di produzione Antilegionella.

Se il v alore v iene impostato a 0 la f unzione v iene

disabilitata.

0 250 Hr 0

FS 14 Set point Antilegionella

Permette di impostare il set point di lav oro Antilegionella FS15 FS16 °C/°F dec/int

FS 15 Minimo v alore setpoint antilegionella

Stabilisce il limite minimo utilizzabile per l’impostazione

del set point Antilegionella

-50.0

-58 FS14

°C

°F

Dec

int

FS 16 Massimo v alore setpoint antilegionella

Stabilisce il limite massimo utilizzabile per l’impostazione

del set point Antilegionella

FS14 70.0

158

°C

°F

Dec

int

FS 17 Ora attiv azione Antilegionella 0 24.00 Hr 10 min

FS 18 Giorno attiv azione Antilegionella

1=domenica ……. 7=sabato 0 7

FS 19 Tempo di permanenza in produzione Antilegionella 1 250 min

FS 20 Banda spegnimento resistenze in Antilegionella 0.1

0

25.0

45

°C

°F

Dec

int

FS 21 Dif f erenziale abilitazione f unzionamento f ree cooling 0.1

25.0

45

°C

°F

Dec

int

FS 22 Iseteresi f unzionamento f ree cooling 0.1

0

25.0

45

°C

°F

Dec

int

FS 23 Set point acqua per integrazione pannelli solari

Permette di impostare il set point di lav oro dei pannelli

solari

FS25 FS26 °C/°F dec/int

FS 24 Banda di interv ento per integrazione pannelli solari 0.1

0

25.0

45

°C

°F

Dec

int

FS 25 Set minimo acqua pannelli solari

Stabilisce il limite minimo utilizzabile per l’impostazione del

set point pannelli solari

-50.0

-58 FS23

°C

°F

Dec

int

FS 26 Set massimo acqua pannelli solari

Stabilisce il limite massimo utilizzabile per l’impostazione

del set point pannelli solari

FS23 70.0

158

°C

°F

Dec

int

FS 27 Ritardo inv ersione uscite Acqua calda sanitaria da

accensione pompa Acqua calda sanitaria 0 250 sec

FS 28 Ritardo spegnimento pompa Acqua calda sanitaria da

inv ersione uscite Acqua calda sanitaria 0 250 sec

FS 29 Tempo massimo di permanenza in f unzione antilegionella 0 250 min

Page 62: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 62/72

FS 30 Set point interruzione produzione acqua calda sanitaria -50.0

-58

70.0

158

°C

°F

FS 31 Dif f erenziale riabilitazione produzione acqua calda

sanitaria

0.1

0

25.0

45

°C

°F

FS 32 Durata minima interruzione produzione acqua calda

sanitaria 0 250 min

FS 33 Abilitazione f unzionamento continuo pompa acqua calda

sanitaria 0 1

FS 34 Tempo spegnimento pompa Free cooling per macchina

con raf f rescamento a solo Frecooling 0 250 min

FS 35 Tempo accensione pompa Free cooling per macchina con

raf f rescamento a solo Frecooling 0 250 sec

FS 36 Tempo massimo di permanenza in Free cooling 0 250 min

FS 37 Set point di regolazione del Free cooling -50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

FS 38 Banda proporzionale di regolazione del Free coling 0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

Bar

Psi

Dec

int

Dec

int

FS 39 Valore minimo uscita v alv ola per Free cooling 0 100 %

FS 40 Valore massimo uscita v alv ola per Free cooling 0 100 %

FS 41 Selezione sonda T1 per Free cooling

0=disabilitata, 1=Pb1, 2=Pb2, etc. 0 10

FS 42 Selezione sonda T1 per Free cooling

0=disabilitata, 1=Pb1, 2=Pb2, etc. 0 10

FS 43 Set point aria esterna per f orzatura v entole

condensazione alla massima v elocità

-50.0

-58

70.0

158

°C

°F

FS 44 Dif f erenziale aria esterna per f orzatura v entole

condensazione alla massima v elocità

0.1

0

25.0

45

°C

°F

FS 45 Tempo di ritardo regolazione v entole di condensazione in

f ree cooling 0 250 min

FS 46 Tipo di f unzionamento del ciclo di antilegionella

0= compressori e resistenze

1= prima compressori e poi resistenze

2= solo resistenze

3= solo compressori

0 3

FS 47 Disabilitazione pompa ev aporatore in produzione acqua

sanitaria

0= abiltata

1= disabilitata

0 1

FS 48 Selezione sonda per uscita f orzata dalla produzione di

acqua calda sanitaria

0= f unzione disabilitata

1= sonda Pb1

2= sonda Pb2

...

0 10

FS 49 Inizio regolazione acqua calda sanitaria

0= alla richiesta di tutti i gradini

1= alla richiesta del primo gradino

0 1

Page 63: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 63/72

FS 50 Set point disattiv azione compressori durante il ciclo di

antilegionella

-50.0

-58

70.0

158

°C

°F

FS 51 Tempi di sicurezza del compressore in caso di chiamata di

acqua calda sanitaria

0= tempi di sicurezza non rispettati

1= tempi di sicurezza rispettati

0 1

FS 52 Set point bassa temperatura acqua calda sanitaria -50.0

-58

70.0

158

°C

°F

FS 53 Banda proporzionale bassa temperatura acqua calda

sanitaria

0.1

0

25.0

45

°C

°F

FS 54 Selezione sonda per regolazione bassa temperatura acqua

calda sanitaria

0= non utilizzata

1= Pb1

2= Pb2

...

0 10

FS 55 Abilitazione pannelli solari in riscaldamento/ integrazione

alla produzione di acqua calda sanitaria

0= non abilitati

1= integrazione

2= riscaldamento

0 2

FS 56 Abilitazione pannelli solari in riscaldamento o in

integrazione al riscaldamento

0= non abilitati

1= integrazione

2= riscaldamento

0 2

FS 57 Selezione sonda per Dt pannelli solari in produzione acqua

calda sanitaria 0 10

FS 58 Selezione sonda per Dt pannelli solari in riscaldamento 0 10

FS 59 Dt abilitazione pannelli solari in produzione acqua calda

sanitaria

0.1

0

25.0

45

°C

°F

Dec

int

FS 60 Dt abilitazione pannelli solari in riscaldamento 0.1

0

25.0

45

°C

°F

Dec

int

FS 61 Tempo massimo utilizzo pannelli solari se set non

soddisf atto

0 250 min

FS 62 Selezione sonda per termine Free cooling per bassa

temperatura 0 10

FS 63 Set point per termine Free cooling per bassa temperatura -50.0

-58

110.0

230

°C

°F

FS 64 Dif f erenziale per termine Free cooling per bassa

temperatura

0.1

0

25.0

45

°C

°F

Allarmi

Parametri Descrizione min max udm Risoluzion

e

Allarme bassa

AL 1 Ritardo allarme bassa pressione da ingresso digitale /

analogico 0 250 Sec

Page 64: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 64/72

AL 2 Il parametro AL02 def inisce il f unzionamento dell’ allarme

di bassa pressione con pump down abilitato

AL02 = 0 l’allarme di bassa pressione v iene inibito durante

la f ermata del compressore in pump down e con

compressore f ermo

AL02 ≠ 0 l’allarme di bassa pressione v iene inibito durante

la f ermata del compressore in pump down e con

compressore f ermo per il tempo impostato

0 250 10

Sec

AL 3 Set point allarme bassa pressione ingresso analogico -50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

AL 4 Dif f erenziale allarme bassa pressione ingresso analogico 0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

bar

psi

Dec

int

Dec

Int

AL 5 Numero massimo interv enti ora allarme bassa pressione

ingresso digitale / analogico

Il riarmo è sempre manuale se AL05 = 0

Il riarmo è sempre automatico se AL05 =16

Il riarmo passa da automatico a manuale se AL05 v a da

1 a 15

0 16

AL 6 Allarme di bassa temperatura / pressione in sbrinamento

0= non abilitato

1= abilitato

0 1

AL 7 Ritardo allarme di bassa temperatura / pressione in

sbrinamento 0 250 Sec

AL 8 Allarme bassa temperatura / pressione con unità in OFF

remoto o stand - by

0 = rilev azione allarme non abilitata

1= rilev azione allarme abilitata

0 1

Allarme alta

AL 9 Set point allarme alta temperatura / pressione di

condensazione ingresso analogico

-50.0

-58

0.0

0

70.0

158

50.0

725

°C

°F

bar

psi

Dec

int

Dec

int

AL 10 Dif f erenziale alta temperatura / pressione di

condensazione ingresso analogico

0.1

0

0.1

1

25.0

45

14.0

203

°C

°F

bar

psi

Dec

int

Dec

int

Allarme olio compressore

AL 11 Ritardo allarme bassa pressione / liv ello olio da ingresso

digitale 0 250 Sec

AL 12 Durata ingresso allarme bassa pressione / liv ello olio

attiv o da ingresso digitale in f unzionamento a regime 0 250 Sec

AL 13 Numero massimo interv enti ora bassa pressione / liv ello

olio

Il riarmo è sempre manuale se AL13= 0

Il riarmo è sempre automatico se AL13 =16

Il riarmo passa da automatico a manuale se AL13 v a da

1 a 15

0 16

Page 65: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 65/72

Funzionamento flussostato condensatore

AL 14 Funzionamento f lussostato condensatore

0= disabilitato

1= solo chiller

2= solo pompa di calore

3= chiller e pompa di calore

0 3

Allarme flussostato evaporatore

AL 15 Ritardo allarme f lussostato ev aporatore / termica v ent. di

mandata da attiv azione pompa acqua ev aporatore /

v entilatore di mandata

0 250 Sec

AL 16 Tempo massimo permanenza allarme f lussostato

ev aporatore prima di trasf ormarsi in manuale e bloccare,

se in moto, la pompa dell’acqua ev aporatore

0 250

AL 17 Durata ingresso f lussostato ev aporatore / termica v ent.

di mandata attiv o 0 250 Sec

AL 18 Durata ingresso f lussostato ev aporatore / termica v ent.

di mandata non attiv o 0 250 Sec

Allarme termica compressori

AL 19 Ritardo allarme termica compressori alla partenza 0 250 Sec

AL 20 Numero massimo interv enti ora termica compressori

Il riarmo è sempre manuale con richiesta di password se

AL20 = 0

Il riarmo è sempre manuale se AL20 =16

Il riarmo passa da manuale a manuale con richiesta di

password se AL20 v a da 1 a 15

0 16

Allarme pump down

AL 21 Numero massimo interv enti di allarme pump down ora in

f ermata

superati i quali l’allarme v iene registrato e segnalato con

codice a display e l’attiv azione del relè allarme + buzzer

Il riarmo è sempre manuale se AL21 = 0

Il riarmo è sempre automatico se AL21 =16

Il riarmo passa da automatico a manuale se AL21 v a da

1 a 15

0 16

AL 22 Numero massimo interv enti di allarme pump down ora in

av v iamento

superati i quali l’allarme div enta a riarmo manuale v iene

registrato e c’è l’attiv azione del relè allarme + buzzer

Il riarmo è sempre manuale se AL22 = 0

Il riarmo è sempre automatico se AL22 = 16

Il riarmo passa da automatico a manuale se AL22 v a da

1 a 15 e in base alla conf igurazione del Par. AL23

0 16

AL 23 Abilitazione riarmo automatico o manuale allarme di pump

– down in av v iamento se v iene raggiunto il numero di

interv enti ora AL22

0= rimane a riarmo automatico anche se v engono

raggiunti il numero di interv enti ora

1=abilita riarmo manuale raggiunti il numero di interv enti

ora

0 1

Allarme antigelo in chiller

Page 66: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 66/72

AL 24 set point limite minimo antigelo in chiller (v a da –30 °C a

AL24)

-50.0

-58 AL26

°C

°F

Dec

int

AL 25 set point limite massimo antigelo in chiller (v a da AL24 a

70 °C) AL26

70.0

158

°C

°F

Dec

int

AL 26 Set allarme antigelo chiller permette di impostare un

v alore di temperatura al di sotto del quale v iene attiv ato

l’allarme antigelo, bassa temperatura aria ambiente (unità

aria/aria ), bassa temperatura aria in uscita (unità

aria/aria). (v a da AL24 a AL25)

AL24 AL25 °C/°F Dec/int

AL 27 Dif f erenziale allarme antigelo in chiller, bassa temperatura

aria ambiente, bassa temperatura aria in uscita.

Permette di impostare un dif f erenziale di temperatura che

determina il reset dell’allarme

0.1

0

25.0

45

°C

°F

Dec

int

AL 28 Ritardo allarme antigelo, bassa temperatura aria

ambiente, bassa temperatura aria in uscita in chiller.

Permette di impostare un tempo durante il quale la

temperatura dev e rimanere sotto il set impostato dal Par.

AL26 perché v enga attiv ato l’allarme di antigelo.

0 250 Sec

AL 29 Numero massimo di interv enti ora allarme di antigelo,

bassa temperatura aria in uscita in chiller.

Determina un numero massimo di interv enti ora di allarme

antigelo, bassa temperatura aria ambiente, bassa

temperatura aria in uscita superati i quali l’allarme passa

da un riarmo automatico ad un riarmo manuale.

Il riarmo è sempre manuale se AL29 = 0

Il riarmo è sempre automatico se AL29 =16

Il riarmo passa da automatico a manuale se AL29 v a da

1 a 15

0 16

AL 30 Funzionamento allarme antigelo in chiller

0= spegne SOLO i compressori quando la temperatura

misurata dalla sonda di regolazione dell’antigelo scende

sotto il set AL26 segnala l’allarme antigelo con una label

ma non attiv a il buzzer e il relè allarme

1= spegne i compressori quando la temperatura misurata

dalla sonda di regolazione dell’antigelo scende sotto il set

AL26 e segnala allarme antigelo con label + buzzer + relè

allarme

0 1

Allarme antigelo in pompa di calore

AL 31 set point limite minimo antigelo in pompa di calore (v a da

– 30 °C a AL32)

-50.0

-58 AL33

°C

°F

Dec

int

AL 32 set point limite massimo antigelo in pompa di calore (v a

da AL31 a 70 °C) AL33

70.0

158

°C

°F

Dec

int

AL 33 Set allarme antigelo in pompa di calore

Permette di impostare un v alore di temperatura al di sotto

del quale v iene attiv ato l’allarme antigelo, bassa

temperatura aria ambiente (unità aria/aria ), bassa

temperatura aria in uscita (unità aria/aria). (v a da AL31 a

AL32)

AL31 AL32 °C/°F Dec/int

Page 67: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 67/72

AL 34 Dif f erenziale allarme antigelo in pompa di calore, bassa

temperatura aria ambiente, bassa temperatura aria in

uscita.

Permette di impostare un dif f erenziale di temperatura che

determina il reset dell’allarme.

0.1

0

25.0

45

°C

°F

Dec

int

AL 35 Ritardo allarme antigelo (bassa temperatura aria in uscita

unità aria /aria) alla partenza dell’unità in f unzionamento

pompa di calore

Attenzione

Se in f unzionamento stand by / OFF remoto, l’unità

presenta una situazione di allarme antigelo e il tempo

impostato nel Par. AL35 è div erso da zero; selezionando il

f unzionamento in pompa di calore da tasto o da ingresso

digitale v iene resettata la situazione di antigelo ed è

consentita l’accensione dei compressori per il tempo

impostato nel Par. AL35 in quanto l’unità v a a scaldare

l’acqua o l’aria. Trascorso il tempo di ritardo AL35 se la

sonda di regolazione per l’antigelo Pbr misura ancora una

temperatura < del set AL33 per almeno AL36 secondi

l’unità v iene bloccata e v iene generato un allarme di

antigelo.

0 250 Sec

AL 36 Ritardo allarme antigelo, bassa temperatura aria

ambiente, bassa temperatura aria in uscita a regime in

p.d.c..

Permette di impostare un tempo durante il quale la

temperatura dev e rimanere sotto il set impostato dal

PAR. AL33 perché v enga attiv ato l’allarme di antigelo.

0 250 Sec

AL 37 Numero massimo di interv enti ora allarme di antigelo,

bassa temperatura aria in uscita in pompa di calore

Determina un numero massimo di interv enti ora di allarme

antigelo, bassa temperatura aria ambiente, bassa

temperatura aria in uscita superati i quali l’allarme passa

da un riarmo automatico ad un riarmo manuale.

Il riarmo è sempre manuale se AL37 = 0

Il riarmo è sempre automatico se AL37 =16

Il riarmo passa da automatico a manuale se AL37 v a da

1 a 15

0 16

AL 38 Funzionamento allarme antigelo in pompa di calore

0= spegne SOLO i compressori quando la temperatura

misurata dalla sonda di regolazione dell’antigelo scende

sotto il set AL33 segnala l’allarme antigelo con una label

ma non attiv a il buzzer e il relè allarme

1= spegne i compressori quando la temperatura misurata

dalla sonda di regolazione dell’antigelo scende sotto il set

AL33 e segnala allarme antigelo con label + buzzer + relè

allarme

0 1

Alta temperatura di mandata compressori

AL 39 Set allarme alta temperatura di mandata compressori 0

32

150

302

°C

°F

Dec / int

int

AL 40 Dif f erenziale allarme alta temperatura di mandata

compressori

0.1

0

25.0

45

°C

°F

Dec

int

Page 68: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 68/72

AL 41 Numero massimo di interv enti ora allarme alta

temperatura di mandata compressori

Determina un numero massimo di interv enti ora allarme

alta temperatura di mandata compressori, superati i quali

l’allarme passa da un riarmo automatico ad un riarmo

manuale.

Il riarmo è sempre manuale se AL41 = 0

Il riarmo è sempre automatico se AL41 =16

Il riarmo passa da automatico a manuale se AL41 v a da

1 a 15

0 16

Allarme generico blocco unità

AL 42 Numero massimo di interv enti ora allarme generico

blocco unità

Determina un numero massimo di interv enti ora allarme

generico blocco unità, superati i quali l’allarme passa da

un riarmo automatico ad un riarmo manuale

Il riarmo è sempre manuale se AL42 = 0

Il riarmo è sempre automatico se AL42 =16

Il riarmo passa da automatico a manuale se AL42 v a da

1 a 15

0 16

AL 43 Tempo di ritardo allarme generico blocco unità con

ingresso digitale attiv o 0 250 Sec

AL 44 Tempo di ritardo allarme generico blocco unità con

ingresso digitale non attiv o 0 250

10

sec 10 sec

Relè allarme

AL 45 Abilita uscita relè allarme in OFF remoto o stand - by

0= uscita allarme abilitata

1= uscita allarme non abilitata

0 1

Password reset storico allarmi – allarme termica compressori

AL 46 Valore password reset storico allarmi, allarme termica

compressori e allarme antigelo (v edi procedure) 0 999

AL 47 Funzionamento allarme di termica compressore

0= blocca il singolo compressore

1= blocca il circuito

0 1

AL 48 Allarme termica compressore con compressore in OFF

0 = rilev azione allarme non abilitata

1= rilev azione allarme abilitata

0 1

Gestione allarme olio compressore

AL 49 Allarme pressostato / galleggiante olio con compressore

in OFF

0 = rilev azione allarme non abilitata

1= rilev azione allarme abilitata

0 1

Allarme generico blocco / segnalazione unità N° 2

AL50 Funzionamento allarme generico n° 2

0 = solo segnalazione non dipende da AL51 (relè allarme e

buzzer attiv ati) sempre riarmo automatico

1= l’allarme blocca l’unità il reset dell’allarme dipende dal

v alore del parametro AL51

0 1

Page 69: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 69/72

AL51 Numero massimo di interv enti ora allarme generico

blocco unità N° 2

Determina un numero massimo di interv enti ora allarme

generico blocco unità, superati i quali l’allarme passa da

un riarmo automatico ad un riarmo manuale

Il riarmo è sempre manuale se AL51 = 0

Il riarmo è sempre automatico se AL51 =16

Il riarmo passa da automatico a manuale se AL51 v a da

1 a 15

0 16

AL52 Tempo di ritardo allarme generico blocco unità con

ingresso digitale attiv o 0 250 Sec sec

AL53 Tempo di ritardo allarme generico blocco unità con

ingresso digitale non attiv o 0 250 sec sec

Riarmo allarme alta pressione

AL54 Numero massimo interv enti ora allarme di alta

temperatura / pressione di condensazione da ingresso

digitale / analogico

Il riarmo è sempre manuale se AL54 = 0

Il riarmo è sempre automatico se AL54 = 16

Il riarmo passa da automatico a manuale se AL54 se v a

da 1 a 15

0 16

Allarme flussostato pompa acqua lato condensatore

AL55 Ritardo allarme f lussostato condensatore da attiv azione

pompa acqua condensatore 0 250 Sec

AL56 Tempo massimo permanenza allarme f lussostato

condensatore prima di trasf ormarsi in manuale e

bloccare, se in moto, la pompa dell’acqua condensatore

0 250 Sec

AL57 Durata ingresso f lussostato condensatore attiv o 0 250 Sec

AL58 Durata ingresso f lussostato condensatore non attiv o 0 250 Sec

Allarme alta temperatura ingresso acqua evaporatore

AL59 Numero massimo interv enti ora allarme sonda alta

temperatura acqua ingresso impianto

Il riarmo è sempre manuale se AL59 = 0

Il riarmo è sempre automatico se AL59 =16

Il riarmo passa da automatico a manuale se AL59 v a da

1 a 15

0 16

AL60 Ritardo allarme sonda alta temperatura acqua ingresso

impianto da ON compressore

0 250 sec 10 sec

AL61 Set point allarme sonda alta temperatura acqua ingresso

impianto

-40.0

-40

110

230

°C

°F

Dec

int

AL62 Dif f erenziale allarme sonda alta temperatura acqua

ingresso impianto

0.1

0

25.0

45

°C

°F

Dec

int

AL63 Conf igurazione ingresso analogico NTC / PTC per la

gestione dell’allarme alta temperatura acqua ingresso

impianto

0 = f unzione disabilitata

0 10

AL64 Ritardo segnalazione allarme bassa pressione da

attiv azione ingresso digitale

0 250 sec

Allarme flussostato pompa acqua calda sanitaria

AL65 Ritardo allarme f lussostato pompa acqua calda sanitaria 0 250 Sec

Page 70: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 70/72

AL66 Ritardo allarme manuale f lussostato pompa acqua calda

sanitaria 0 250 Sec

AL67 Durata ingresso f lussostato pompa acqua calda sanitaria

attiv o 0 250 Sec

AL68 Durata ingresso f lussostato pompa acqua calda sanitaria

non attiv o 0 250 Sec

Allarme flussostato pompa acqua pannelli solari

AL69 Ritardo allarme f lussostato pompa pannelli solari 0 250 Sec

AL70 Ritardo allarme manuale f lussostato pompa pannelli solari 0 250 Sec

AL71 Durata ingresso f lussostato pompa pannelli solari attiv o 0 250 Sec

AL72 Durata ingresso f lussostato pompa pannelli solari non

attiv o 0 250 Sec

Allarme termica resistenze acqua sanitaria

AL73 Numero massimo interv enti ora allarme termica

resistenze acqua sanitaria

Il riarmo è sempre manuale se AL73 = 0

Il riarmo è sempre automatico se AL73 =16

Il riarmo passa da automatico a manuale se AL73 v a da

1 a 15

0 16

Selezione del tipo di riarmo dell’ allarme antigelo

AL74 Allarme antigelo a riarmo manuale con richiesta di

password

0= password non richiesta

1= password richiesta

0 1

Allarme termica pompa acqua sanitaria

AL75 Numero massimo interv enti ora allarme termica pompa

acqua sanitaria

Il riarmo è sempre manuale se AL75 = 0

Il riarmo è sempre automatico se AL75 =16

Il riarmo passa da automatico a manuale se AL75 v a da

1 a 15

0 16

Allarme olio compressore

AL76 Allarme olio compressore come sola segnalazione

0= allarme olio a riarmo automatico o manuale (AL13) con

blocco del compressore

1= allarme olio compressore come sola segnalazione

0 1

Allarme termica compressore

AL77 Allarme termica compressore a reset automatico

0= allarme termica compressore sempre a reset manuale

1= allarme termica compressore a reset automatico

0 1

Allarme pressione differenziale compressore o circuito

AL78

Dt per allarme dif f erenziale olio compressore o circuito

0.1

1

14.0

203

bar

psi

Dec

int

AL79 Dif f erenziale riarmo allarme dif f erenzale olio compressore

o circuito

0.1

1

14.0

203

bar

psi

Dec

int

Page 71: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 71/72

AL80 Numero massimo interv enti ora allarme dif f erenziale olio

compressore

Il riarmo è sempre manuale se AL73 = 0

Il riarmo è sempre automatico se AL73 =16

Il riarmo passa da automatico a manuale se AL73 v a da

1 a 15

0 16

AL81 Abilitazione alla rilev azione dell’allarme pressione

dif f erenziale olio

0= non abilitato

1= abilitato per compressore a pistoni

2= abilitato per compressore a v ite

0 2

Allarme flussostato pompa FC

AL82 Ritardo allarme f lussostato pompa FC 0 250 Sec

AL83 Ritardo allarme manuale f lussostato pompa FC 0 250 Sec

AL84 Durata ingresso f lussostato pompa FC attiv o 0 250 Sec

AL85 Durata ingresso f lussostato pompa FC non attiv o 0 250 Sec

Tipo di riarmo dell’allarme flussostato

AL86 Tipo di riarmo dell’allarme f lussostato

0= sempre manuale

1= riarmo automatico dopo 1 minuto

2= riarmo automatico dopo 2 minuti

...

250= riarmo automatico dopo 250 minuti

0 250

AL87 Tempo by -pass f lussostato ev aporatore e sanitario da

commutazione Out1 o Out2 0 250 Sec

Pr1 Password 0 999

Pr2 Password 0 999

Pr3 Password 0 999

17. Dati Tecnici

IC260L / IC261L:

Contenitore:

ABS autoestinguente

Formato:

Frontale 38x185mm; profondità 76mm

Montaggio:

A pannello su foro 31x150mm

Grado di protezione frontale: IP65 util izzando la guarnizione retrofrontale

IC260D / IC261D:

Contenitore:

ABS autoestinguente

Formato: 10 moduli Din

Montaggio: su barra Din / a muro tramite le 4 staffe di fissaggio estraibil i

Grado di protezione: IP20

Grado di protezione frontale della tastiera: IP65 util izzando la guarnizione retrofrontale

-------------------------------------------------------------------------------------------------------------------------

Page 72: (versione FW 1.9) - Emerson Electricclimate.emerson.com/documents/ic260l-it-it-3948236.pdfSupervisione / tele assistenza / monitoraggio Collegabile tramite uscita RS485 con protocollo

1591015870 GRU IC260_261L_D DUO FW 1.9 05-04-2016 IC260/261L/D 72/72

Visualizzazione:

Display superiore 3 cifre con punto decimale, d isplay inferiore 4 cifre con punto decimale

Connessioni:

Connettori sconnettibil i

Alimentazione:

12Vac/dc (-10% ÷ 15% 50/60 hz)

24 Vac/dc±10% 50/60 HZ (opzionale)

Potenza assorbita:

10VA max

Ingressi sonda:

6 sonde di temperatura configurabili (NTC/PTC) + 4 sonde di temperatura o pressione

configurabili (NTC/PTC/ 4 ÷ 20ma / 0 ÷ 5Volt )

Ingressi digitali :

N° 18 (puliti)

Uscite su relè:

IC260L/D: 10 SPDT 5(2) A, 250Vac

IC261L/D: 14 SPDT 5(2) A, 250Vac

Max corrente sui comuni 12A

Mantenimento dati:

Su memoria non volatile (EEPROM)

Temperatura di impiego:

-10÷55 °C

Temperatura di immagazzinamento:

-30÷85 °C

Umidità relativ a:

20÷85% ( senza condensa).

Campo di misura:

Sonda di temperatura NTC: - 50÷110 °C (- 58 ÷ 230 °F);

Sonda di temperatura PTC: -50÷150 °C (-58÷302 °F )

Pressione: 0÷ 50 bar (0÷725 psi)

Risoluzione:

0.1 °C oppure 1°F

Precisione ( a 25 °C temp. Ambiente ):

± 0.7 °C ± 1 digit