    XAVIER UNIVERSITY-ATENEO DE CAGAYAN

    College of Engineering

    Cagayan de Oro City

    Mechanical Engineering Department

    Mechanical Engineering Technical Elective 3

    An Evaluation of the Fire Protection System of a Building: AGRICLUTURE BUILDING

    Submitted by:

    Rivera, John Renzel

    Hibaya, Alexis

    Eduria, Tracy Keenan

    Marfa, Ralph Marion

    Submitted to:

    Engr. Cyril G. Fabrea, PME

  • 7/30/2019 Mete Aggies

    2/16

    Introduction:

    The building to be evaluated is the Agriculture building of Xavier University in Corrales

    street, Cagayan de Oro City. The floor area of the six-storey building is 80.96x10.55 m2. The

    buildings Fire sprinkler system will be evaluated to check if it is in compliance to the NFPA 13

    standard for fire protection. The system is usually activated by heat from a fire, and the sprinkler

    heads will discharge water over the fire area. Fire Sprinkler systems are almost 100% efficient.

    General Objective:

    The objective of this paper is to evaluate the fire protection system of the Agriculture

    Building of Xavier University in accordance to the NFPA 13 and compare the evaluation to the

    existing/installed sprinkler system.

  • 7/30/2019 Mete Aggies

    3/16

    EXISTING PARAMETERS

    1st

    floor

    Number of branchline- 22

    Number of Sprinkler per floor- 45

    Distance between branchline- 3m ( referred to autocad drawing of the building)

    Distance between sprinklers - 3.45m (referred to autocad drawing of the building)

    Number of Sprinkler per branch- 3

    2nd

    floor

    Number of branchline- 22

    Number of Sprinkler per floor- 57

    Distance between branchline- 4.5m ( referred to autocad drawing of the building)

    Distance between sprinklers - 3.15m (referred to autocad drawing of the building)

    Number of Sprinkler per branch- 3

    3rd

    floor

    Number of branchline- 23

    Number of Sprinkler per floor- 67

    Distance between branchline- 2.7m ( referred to autocad drawing of the building)

    Distance between sprinklers2.85m (referred to autocad drawing of the building)

    Number of Sprinkler per branch- 3

    4th

    floor

    Number of branchline- 25

    Number of Sprinkler per floor- 75

    Distance between branchlines - 3m (referred to autocad drawing of the building)

    Distance between sprinklers4.35m/2.85m (referred to autocad drawing of the building)

    Number of Sprinkler per branch- 3

    5th

    floor

    Number of branchline- 20

    Number of Sprinkler per floor- 62

    Distance between branchline- 3m (referred to autocad drawing of the building)

    Distance between sprinklers2.85m/4.35m (referred to autocad drawing of the building)

    Number of Sprinkler per branch- 3

  • 7/30/2019 Mete Aggies

    4/16

    6th

    floor

    Number of branchline- 25

    Number of Sprinkler per floor- 76

    Distance between branchline- 3.25m (referred to autocad drawing of the building)

    Distance between sprinklers3.6 (referred to autocad drawing of the building)

    Number of Sprinkler per branch- 3

    SUMMARY OF DATA GATHERED BASED ON AUTOCAD DRAWING FROM PPO

    Number of

    branchlines

    Number of

    Sprinklers

    per Branch

    Number of

    Sprinklers

    per floor

    Distance

    Between

    Branchlines

    (m)

    Distance

    Between

    Sprinklers

    (m)

    1st

    floor 22 3 45 3 3.45

    2n floor 22 3 57 4.5 3.15

    3r

    floor 23 3 67 2.7 2.85

    4t floor 25 3 75 3 2.85/4.35

    5t floor 20 3 62 3 2.85/4.35

    6t

    floor 25 3 76 3 3.6

    Evaluation in accordance to NFPA 13

    Light HazardEach occupancy classification for a fire protection system has a maximum floor area to be

    protected by sprinklers supplied on each system riseron any one floor shall be as follows:

    NFPA 13 PSME CODE

    Area Limitation

    Light hazard 52,000.00 ft2

    4830 m2

    Ordinary hazard 52,000.00 ft2

    4830 m2

    Extra hazard 40,000.00 ft2

    2323 m2

    (Lmax=15ft=4.572m, Area coverage of sprinkler, As=18.6m2)

  • 7/30/2019 Mete Aggies

    5/16

    1st

    floor

    Width=80.94m Length=10.55m

    Number of Branchlines

    NB =

    =

    =17.718 branchline

    Distance between branchlines

    Lb=

    = 4.5m

    Distance between Sprinkler

    S =

    =

    Number of Sprinklers per branch

    Nb=

    Actual Distance between sprinklers

    Sact=

    Distance of sprinkler to the wall

    Number of Sprinkler per floor

    Ns=(3 sprinklers/branch)x(18 branch)=54 Sprinklers

    Verification of Sprinkler Coverage

    A= (Sact) (Lb)= 3.52x4.5 = 15.84m

    A

  • 7/30/2019 Mete Aggies

    6/16

    2nd floor

    Width=80.94m Length=10.55m

    Number of Branchlines

    NB =

    =

    =17.718 branchline

    Distance between branchlines

    Lb=

    = 4.5m

    Distance between Sprinkler

    S =

    =

    Number of Sprinklers per branch

    Nb=

    Actual Distance between sprinklers

    Sact=

    Distance of sprinkler to the wall

    Number of Sprinkler per floor

    Ns=(3 sprinklers/branch)x(18 branch)=54 Sprinklers

    Verification of Sprinkler Coverage

    A= (Sact) (Lb)= 3.52x4.5 = 15.84m

    A

  • 7/30/2019 Mete Aggies

    7/16

    3rd floor

    Width=80.94m Length=10.55m

    Number of Branchlines

    NB =

    =

    =17.718 branchline

    Distance between branchlines

    Lb=

    = 4.5m

    Distance between Sprinkler

    S =

    =

    Number of Sprinklers per branch

    Nb=

    Actual Distance between sprinklers

    Sact=

    Distance of sprinkler to the wall

    Number of Sprinkler per floor

    Ns=(3 sprinklers/branch)x(18 branch)=54 Sprinklers

    Verification of Sprinkler Coverage

    A= (Sact) (Lb)= 3.52x4.5 = 15.84m

    A

  • 7/30/2019 Mete Aggies

    8/16

    4th floor

    Width=80.94m Length=10.55m

    Number of Branchlines

    NB =

    =

    =17.718 branchline

    Distance between branchlines

    Lb=

    = 4.5m

    Distance between Sprinkler

    S =

    =

    Number of Sprinklers per branch

    Nb=

    Actual Distance between sprinklers

    Sact=

    Distance of sprinkler to the wall

    Number of Sprinkler per floor

    Ns=(3 sprinklers/branch)x(18 branch)=54 Sprinklers

    Verification of Sprinkler Coverage

    A= (Sact) (Lb)= 3.52x4.5 = 15.84m

    A

  • 7/30/2019 Mete Aggies

    9/16

    5th floor

    Width=80.94m Length=10.55m

    Number of Branchlines

    NB =

    =

    =17.718 branchline

    Distance between branchlines

    Lb=

    = 4.5m

    Distance between Sprinkler

    S =

    =

    Number of Sprinklers per branch

    Nb=

    Actual Distance between sprinklers

    Sact=

    Distance of sprinkler to the wall

    Number of Sprinkler per floor

    Ns=(3 sprinklers/branch)x(18 branch)=54 Sprinklers

    Verification of Sprinkler Coverage

    A= (Sact) (Lb)= 3.52x4.5 = 15.84m

    A

  • 7/30/2019 Mete Aggies

    10/16

    6th

    floor

    Width=80.94m Length=10.55m

    Number of Branchlines

    NB =

    =

    =17.718 branchline

    Distance between branchlines

    Lb=

    = 4.5m

    Distance between Sprinkler

    S =

    =

    Number of Sprinklers per branch

    Nb=

    Actual Distance between sprinklers

    Sact=

    Distance of sprinkler to the wall

    Number of Sprinkler per floor

    Ns=(3 sprinklers/branch)x(18 branch)=54 Sprinklers

    Verification of Sprinkler Coverage

    A= (Sact) (Lb)= 3.52x4.5 = 15.84m

    A

  • 7/30/2019 Mete Aggies

    11/16

    Hydraulically Most demanding area

    2nd

    floor

    A=16.8m x 10m = 168m2

    Density=3.8 LPM/m2=0.092GPM/ft

    2

  • 7/30/2019 Mete Aggies

    12/16

    Flow to the design area

    Q= AxD

    =168x 3.8

    Q=638.4LPM

    Length of Design Area

    Lmin= 1.2

    Lmin= 1.2

    Lmin=15.55m

    Number of Sprinklers on the design length

    Ns= Lmin/S, S=3.15m

    Ns=15.55/3.15

    Ns=4.945 sprinklers

    Actual Length of the design area

    Lact=Ns X S

    Lact= 5 x 4.13

    Lact=20.65 m

    Width of the design area

    W= A/ Lact

    W= 168/ 20.65

    W=8.14m

    Sprinkler Coverage, As

    As= 14.175m2

    The design area is 168 m2, 14.175x 12 sprinklers= 170.1 > 168; therefore it meets the

    desired minimum criteria.

    Minimum flow at the hydraulically most demanding sprinkler

    Q= D x As

    Q= 3.8

    x 14.175m

    2

    Q=53.865 LPM = 14.23GPM

  • 7/30/2019 Mete Aggies

    13/16

    Minimum pressure at the hydraulically most demanding sprinkler

    P= (Q/K)2, K=5.3-5.8

    At K=5.3 P= (14.23/5.3)2

    P=7.21 PSI

    At K=5.4 P= (14.23/5.4)2

    P=6.94 PSI

    At K=5.5 P= (14.23/5.5)2

    P=6.69 PSI

    At K=5.6 P= (14.23/5.6)2

    P=6.46 PSI

    At K=5.7 P= (14.23/5.7)2

    P=6.23 PSI

    At K=5.8 P= (14.23/5.8)2

    P=6.02 PSI

    According to NFPA 13 the minimum pressure at any sprinkler shall be at 7.0 psi

    Determine the Friction Loss

    Pf=

    ;

    Pf=fiction loss per one foot of pipe

    C= C-factor measure of relative roughness or smoothness of the internal surface of a pipe

    compared to other pipe. From tale B-1 of NFPA 13 c-factor (galvanized)- 120

    d = internal diameter of pipe, Table C-1= 1.61 in

    Pf=

    = 0.0086 psi/ft

  • 7/30/2019 Mete Aggies

    14/16

    Comparative tables between existing design and in accordance to NFPA 13 design

    OCCUPANCY EXISTING NFPA 13 REMARKS

    ORDINARY

    HAZARD:GROUP 2

    855 m

    4830m

    PASS

    NUMBER OF BRANCHLINES EXISTING NFPA 13 REMARKS

    1 FLOOR 22 18 PASS2 FLOOR 22 18 PASS3 FLOOR 23 18 PASS4 FLOOR 25 18 PASS5 FLOOR 20 18 PASS6 FLOOR 25 18 PASS

    The more number of branch lines the betterDISTANCE BETWEEN BRANCHLINES EXISTING NFPA 13 REMARKS

    1 FLOOR 3 4.5 PASS2 FLOOR 4.5 4.5 PASS3 FLOOR 2.7 4.5 PASS4 FLOOR 3 4.5 PASS5 FLOOR 3 4.5 PASS6 FLOOR 3 4.5 PASS

    The closer branch lines is more efficient in fire protectionDISTANCE BETWEEN SPRINKLERS EXISTING NFPA 13 REMARKS

    1 FLOOR 3.45 4.13 PASS2 FLOOR 3.15 4.13 PASS3 FLOOR 2.85/3.75 4.13 PASS4 FLOOR 2.85/4.35 4.13 PASS/FAIL5 FLOOR 2.85/4.35 4.13 PASS/FAIL6 FLOOR 3.6 4.13 PASS

    The sprinkler should be closer to each other for effective coverage

  • 7/30/2019 Mete Aggies

    15/16

    NUMBER OF SPRINKLERS PER BRANCH EXISTING NFPA 13 REMARKS

    1 FLOOR 3 3 PASS2 FLOOR 3 3 PASS3 FLOOR 3 3 PASS4 FLOOR 3 3 PASS5 FLOOR 3 3 PASS6 FLOOR 3 3 PASS The number of sprinklers per branch should comply with the minimum number in NFPA

    13

    NUMBER OF SPRINKLER

    PER FLOOR

    EXISTING NFPA 13 REMARKS

    1 FLOOR 45 54 PASS2 FLOOR 57 54 PASS3 FLOOR 67 54 PASS4 FLOOR 75 54 PASS5 FLOOR 62 54 PASS6 FLOOR 76 54 PASS

    Sprinkler Coverage EXISTING NFPA 13 REMARKS

    1 FLOOR 10.35 15.84 PASS

    2 FLOOR 14.175 15.84 PASS

    3 FLOOR 7.7/10.125 15.84 PASS

    4 FLOOR 8.55/13.05 15.84 PASS

    5 FLOOR 8.55/13.05 15.84 PASS

    6 FLOOR 10.8 15.84 PASS

  • 7/30/2019 Mete Aggies

    16/16

    MINIMUM PRESSURE AT THE

    HYDRAULICALLY MOST DEMANDING

    AREA

    EXISTING (PSI) NFPA 13 REMARKS

    2n

    floor, 168m Major portion Faculty Area

    At K=5.3 7.21 7 PASS

    At K=5.4 6.94 7 FAIL

    At K=5.5 6.69 7 FAIL

    At K=5.6 6.46 7 FAIL

    At K=5.7 6.23 7 FAIL

    At K=5.8 6.02 7 FAIL