FIRST ROMANIAN PUBLIC NZEB PROPOSAL FOR A FUTURE EU PROJECT
Associate Professor Cătălin LUNGU PhD, FII-UTCB & AIIR
SOURCE: REHVA NZEB TC
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 2
SUMMARY
1. GENERAL CONTEXT & RO-NZEB CONSORTIUM
2. ARCHITECTURE & STRUCTURAL CONCEPT
4. PROPOSALS FOR MECHANICAL EQUIPMENTS
3. ENERGY CONSUMPTION-ESTIMATION
5. FINANCIAL ESTIMATIONS
6. CONCLUSIONS
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 3
1a. General context • EU/2010/31 Directive and VERY NEW law 159/2013
• no definition of Romanian NZEB (ongoing task of ICECON)
• no definition and procedure for optimal cost calculation
• no already certified PASSIVE building constructed in Romania
• no national strategy according to provisions of EU/27&31 Directives
• approx. 10 green office/coomercial buildings LEED or BREEAM
• only one research about bioclimatic buildings
• 3 national programmes for the refurbishment of residential buildings
(OUG 69/2010, OUG 63/2012 and HG 1160/2012 POR) – success rate volatile !!!
• average energy consumption of RO building stock twice at least compared to the EU average level
• approx. 2bln Euro funds for 2014-2020 to be spent for energy efficiency in RO
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 4
1b. RO-NZEB CONSORTIUM
?! NOT YET COMPANIES FOR MECHANICAL EQUIPMENT ?!
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 5
2. Architecture concept (1)
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 6
2. Architecture concept (2)
• footprint ~ 200-250 sqm
• height: U+GF+5S
• ventilated double-skin facade
• outside opaque walls with YTONG,
rockwool and alubond
• three-layers windows
(U=0,9W/m2K, g=0,6, float, e-low)
• green roof
• green-house emmbeded
• light inside walls (open spaces)
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 7
2. Architecture concept (3)
NORTH-WEST VIEW
N
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 8
2. Architecture concept (3)
NORTH VIEW
N
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 9
2. Architecture concept (3)
SOUTH-WEST VIEW
N
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 10
2. Architecture concept (3)
EAST VIEW
N
11:41
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 11
2. Architecture concept (4)
GROUND FLOOR
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 12
2. Architecture concept (4)
CURRENT FLOOR
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 13
2. Architecture concept (4)
Vth (LAST) FLOOR
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 14
Superstructure - metal frame with
metal pillars and metal beams,
cross-beams against wind, rein-
forced concrete floors, shaped on
pleated metal sheet.
Infrastructure – reinforced
concrete with general foundation.
(recycling principle)
2. Structural concept (5)
M1-0,503s M2-0,474s M3-0,295s
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 15
3. Energy consumption-estimation
Building component type RO-NZEB C107
U’ [W/m2K]
U’min [W/m2K]
Outside walls (YTONG, min wool) 0,10 0,56
Double skin glass (g=0,59) 0.68 1,30
Terrace (green roof or concrete+rockwool) 0,10 0,20
Underground floor (heated underground) 0,18 0,21
Exterior walls under ground 0,10 0,35
Calculation hypothesis:
Useful area: 1400sqm
Inside volume: 4600 m3
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 16 16
Time Set point
Heating
Monday-Friday => 7-19 20
Monday-Friday => 19-7 15
Friday-Monday => 19-7 15
Cooling Monday-Friday => 7-19 26
Monday-Friday => 19-7 Off
Friday-Monday => 19-7 Off
Mechanical Ventilation 24h On
HVAC equipment functioning schedule
3. Energy consumption-estimation (cont.)
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 17 17
Min Max Avg
Text (0C) -15,4 35,4 20,6
Qheat (kW) 87
Qcool (kW) 159
Heating period (hour) 1869
Cooling period (hour) 1730
TRNSYS
3. Energy consumption-estimation (cont.)
Qheating=46kWh/sqm/y Qcooling=85kWh/sqm/y
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 18
4. Proposals for mechanical equipment (3)
CHP (1)
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 19
4. Proposals for mechanical equipment (3)
CHP(2)-Stirling Advantages
-can be used with many fuel sources,
including low-temperature souces
-the source is external to the engine, so
Stirling engines can be coupled to a
biomass combustion unit
-Stirling operatesvery quietly because there
is no exhaust of the gas
-very efficient
-reversible
Disadvantages
-higher capital costs
-not so widely used till now (only few
applications)
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 20
4. Proposals for mechanical equipment (3)
CHP(2)-Stirling Exemple of a 55 kW (electrical) generator set for combined heat and power applica-tions. The total enclosure length is about 2.5 metres, and this assembly has a mass of about 1300 kg.
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 21
• ~ 3,5kW
• HEX refrigerant-water-soil
• cooling or heating
• Borehole of approx. 7 m deep and 70cm in diameter
4. Proposals for mechanical equipment (1)
GEOCOLUMN
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 22
4. Proposals for mechanical equipment (2)
SOLAR TUBES
• Super Silver SunPipe • 75…6300 lux depending on diameter and natural light outside (7,5…70sqm) • reflectance 0,95 • combined with LED
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 23
4. Proposals for mechanical equipment (4)
Other complementary solutions for RO-NZEB :
• thermodinamic solar collectors
• Canadian tube (earth-to-air heat exchangers-EAHX) for ventilation combined with ventilation through double-skin facades
• absorbtion chiller
• used water cleaning devices
• rain water storage
• PV pannels
• microturbines with vertical axle
• BMS
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 24
5. Financial estimations
1,1
0,4
1,3
0,4
1,8
0
0,2
0,4
0,6
0,8
1
1,2
1,4
1,6
1,8
RO-NZEB COST ESTIMATION
Enveloppe 1,1
Structure 0,4
Mechanical equips 1,3
Field refurbishment 0,4
Laboratories 1,8
Cost (Mil Euro)
AVERAGE CONSTRUCTION COST 2078 Euro (VAT excluded)
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 25
6. Conclusions
• AIIR initiative gathering 2 Universities and 6 private companies
• proposal for a public NZEB building (model)
• RO-NZEB will be also green (BREEAM) and bioclimatic building
• for research (itself for monitoring), with laboratories and offices
• heating 40-50kWh/sqm/y, cooling 80-90kWh/sqm/y, lighting 5kWh/sqm/y
• 2078 Euro/sqm construction cost (included field rehabilitation, excluded research equipment, excluded design cost)
• RO-NZEB promoting the companies in the consortium (50-50)
• RO-NZEB for high-tech technology visiting tour in Bucharest
• RO-NZEB searching now for EU financing funds
11:42
Prof.ass.dr.eng. Cătălin LUNGU Lect.dr.eng. Raluca TEODOSIU
Arch. Mădălina IORDĂCHESCU Eng. Ionela ION 26
Assoc.prof.dr.eng. Cătălin Lungu www.aiiro.ro
www.instalatii.utcb.ro Tel/fax +4021.252.42.95 [email protected] [email protected]
Contact info:
Thank you for your questions !